Haier AU60NFIERA Installation Instructions - Page 68

Failure code from 24 to 27, from 30 to 40, Communication with power module failure, Suction

Page 68 highlights

8. Suction temperature protection Measure if the actual air return temperature is over 40degree yes no Check the suction temperature Check the system: if the stop valve is normal; if EEV works normally; if the system is lack of refrigerant; if the system is clogged or leaks 9. Communication with power module failure Check if PCB is electrified with the power module no Check if the wiring between them is normal yes Check if the sequence of A and B is correct 10.Failure code from 24 to 27, from 30 to 40 Re-electrified, check if the failure disappears no Replace power module 11. Failure code 28 and 29: Check if the voltage input is in the range of 380V± 15%. Then check if the wiring connection is proper, such as if the terminal of power module is inserted firmly, PTC control wire is normal. 68

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70

11. Failure code 28 and 29: Check if the voltage input is in the range of 380V
±
15%. Then check if the wiring connection is proper, such as if the terminal of power
module is inserted firmly, PTC control wire is normal.
Replace power module
no
Re-electrified, check if the
failure disappears
10.Failure code from 24 to 27, from 30 to 40
Check if the sequence of A and B is correct
yes
9. Communication with power module failure
Check if PCB is electrified with
the power module
no
Check if the wiring between them is normal
Check the suction
temperature
Check the system: if the stop valve is normal;
if EEV works normally; if the system is lack of
refrigerant; if the system is clogged or leaks
yes
Measure if the actual air return
temperature is over 40degree
no
8. Suction temperature protection
68