Purging Method

Page 8 highlights

Outdoor unit 5.Purging Method: Push the air out of the indoor unit and piping as followes: (1) Remove the valve cap on 2-way valve in outdoor unit. (2) Loosen by 1/2 turn the flare nut of gas pipe, which is is conneted to 3-way valve. (3) Loosen 2-way valve by 90o using hexagon wrench, and after approx.10 sec tighten it up. Gas comes out through flare nut on wide pipe. If no gas is discharged, tighten flare nut with specified torque. (4) Open 2-way and 3-way valves using specified torque. (5) Tighten the caps on the valves with specified torque. Tighten torque N.m Valve rod 7-9 Valve cap 20-25 When connecting pipe exceeds 5 meters, 20g refrigerant shall be added per exceeding meter. Charge according to the following list. Piping length Additional amount for 9k 12k 5m 7m No need 40g 10m 100g 2-way valve 6.35mm(1/4") 3-way valve 9.52mm(3/8") Outdoor unit Indoor unit Outdoor unit Max. Length: 10m A Oil trap for 9K : A=7m for 12K : A=10m Indoor unit Max.Elevation:5m CAUTION In case more than 5m Oil trap shoud be installed every 5~7m no more gas if the length of connecting pipe is less than 7m(9K) or 10m(12K). The height difference between any two indoor or outdoor units can not be more than 5m. Note: When extending piping, air inside piping shall be removed by using external refrigerant gas, charge according to the following list. Brand new outdoor unit is charged 50g more refrigerant than regulated weight. Only for first installation, this extra 50g can be used to purge air in pipes. During this procedure, 50g refrigerant will be discharged in piping. (This must be strictly controlled within 90o and 10 sec.) 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10

Outdoor unit
7
When connecting pipe exceeds 5 meters, 20g refrigerant
shall be added per exceeding meter. Charge according to
the following list.
During this procedure, 50g
refrigerant will be discharged in piping.
(This must be strictly controlled within 90
o
and 10 sec.)
Brand new outdoor unit is charged 50g
more refrigerant than regulated
weight. Only for first installation, this extra 50g
can be used to purge air
in pipes.
Note: When extending piping, air inside piping shall be removed by using external
refrigerant gas, charge according to the following list.
5.Purging Method:
Piping length
Additional amount
5m
7m
No need
40g
10m
100g
for
9k
12k
Push the air out of the indoor unit
and piping as followes:
(1) Remove the valve cap on 2-way valve in outdoor unit.
(2) Loosen by 1/2 turn the flare nut of gas pipe, which is
is conneted to 3-way valve.
(3) Loosen 2-way valve by 90
o
using hexagon wrench,
and after approx.10 sec tighten it up. Gas comes out
through flare nut on wide pipe. If no gas is discharged,
tighten flare nut with specified torque.
(4) Open 2-way and 3-way valves using specified torque.
(5) Tighten the caps on the valves with specified torque.
Valve rod
Valve cap
7-9
20-25
Tighten torque N.m
CAUTION
In case more than 5m
Oil trap shoud be installed every 5~7m
m
7
=
A
:
K
9
r
o
f
:
h
t
g
n
e
L
.
x
a
M
for 12K : A=10m
Max.Elevation:
5m
no more gas if the length of connecting pipe is less than
7m(
9K)
or 10m(12K).
The height difference between any two indoor or outdoor units can not be
more than 5m.
A
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Oil trap
10m
3-way valve
2-way valve
6.35mm(1/4")
9.52mm(3/8")