Haier HSU12XH7 HSU12XH7-W HSU12XH7-G User Manual - Page 3
Outdoor unit - g force
View all Haier HSU12XH7 HSU12XH7-W HSU12XH7-G manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 3 highlights
Outdoor unit Installation of Outdoor Unit Install according to Drawing for the installation of indoor and outdoor units Indoor unit Outdoor unit Connecting wiring: AWG18X6, Power Cable: AWG12X3. SN-18000-H Indoor unit Outdoor unit Connecting wiring: AWG18X6, Power Cable: AWG12X3. SN-24000-H 1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. The type of connecting wire is H05RN-F or H07RN-F. 2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V. 3. The wiring method should be in line with the local wiring standard. 4. After installation, the power plug should be easily reached. 5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the distance between its two contacts should be not less than 3mm. Connection of pipes ƽ To bend a pipe, be careful not to crush the pipe, and the bending radius should be 30 to 40 mm or longer. ƽ Connecting the pipe of gas side first makes working easier. ƽ The connection pipe is specialized for R410A. Half union Flare nut Forced fastening without careful centering may damage the threads and cause a leakage of gas. Spanner Pipe Diameter(ǿ) Fastening torque Liquid side6.35mm(1/4") 18N.m Liquid/Gas side9.52mm(3/8") 42 N.m Torque wrench Gas side 12.7mm(1/2") Gas side 15.88mm(5/8") 55N.m 60 N.m Ensure that on dirt or debris enters the pipe. The standard pipe length is 5m. If it is over 7m, the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should be charged, according to 50 g/m. But the charge of refrigerant must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional refrigerant. CAUTION Outdoor unit B Indoor unit A B A Indoor unit Outdoor unit Outdoor unit B A Oil trap Indoor unit ● Max.Elevation: Amax=15m ● In case the elevation A is more than 5m, oil trap shoud be installed every 5~7m ● Max. Length: Bmax=25m ● In case the pipe length B is more than 7m, the refrigerant should be charged,according to 20 g/m.(for 18k) In case the pipe length B is more than 7m, the refrigerant should be charged,according to 50 g/m.(for 24k) Connection ƽ Take off the panel(top), by removing the 5 screws. ƽ Remove the plugs on the conduit plate. ƽ Temporarily mount the conduit tubes on the conduit plate. ƽ Connect both the power supply and unit wire harness to the corresponding terminals on the terminal board. ƽ Ground the unit in accordance with local codes. ƽ Allow several extra inches of wire for making wiring connections. ƽ Use lock nuts to secure conduit tubes. Attaching Drain-Elbow ƽ If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.) 3