Air conditioner Edition: 10070808 3.2 . Introduction to electrical control functions Including brief introduction to air conditioners of series models and electric control function. Brief introduction to electric control function 3.2.1 Automatic running (applicable to fan-coil model) When the running mode is turned to automation after starting the system, the system will first determine the running mode according to the current room temperature and then will run according to the determined mode. Tr in the following selection conditions means room temperature, Ts means setting temperature, Tp means temperature of indoor coil pipe a. Tr≥23℃ b. Tr Ts+2℃, compressor, outdoor fan run continuously, indoor fan runs as per setting wind speed (State 1); 3.2.3.2 Ts+2℃≥ Tr≥Ts, compressor, outdoor fan run intermittently with 10 minutes ON, 6 minutes OFF. (Compressor and outdoor fan are synchronous) indoor fan runs in fixed lower wind speed, and will cease at the stand-by time of 3 minutes (State 2) 3.2.3.3 Tr

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27

Air conditioner
Edition: 10070808
- 5 -
3.2 .
Introduction to electrical control functions
Including brief introduction to air conditioners of series models and electric control
function.
Brief introduction to electric control function
Automatic running (applicable to fan-coil model)
When the running mode is turned to automation after starting the system, the system
will first determine the running mode according to the current room temperature and then
will run according to the determined mode. Tr in the following selection conditions means
room temperature, Ts means setting temperature, Tp means temperature of indoor coil
pipe
a. Tr
23
running refrigerating mode Ts=26
b. Tr<23
running heating mode Ts=23
After turning to the automation mode, the running mode can be switched between
refrigerating mode, fan mode and heating mode according to the change of the indoor
ambient temperature. But the automatic conversion between refrigerating mode and
heating mode must be conducted after 15 minutes.
Indoor temperature control
Compressor ON
Dehumidification running
The compressor, outdoor fan and indoor fan will run as per the following working
pattern so as to realize the refrigerating running of dehumidification:
Tr> Ts+2
, compressor, outdoor fan run continuously, indoor fan runs as
per setting wind speed (State 1);
Ts+2
℃≥
Tr
Ts, compressor, outdoor fan run intermittently with 10
minutes ON, 6 minutes OFF. (Compressor and outdoor fan are synchronous)
indoor fan runs in fixed lower wind speed, and will cease at the stand-by time of 3
minutes (State 2)
Tr <Ts, compressor, outdoor fan ceases, indoor fan runs in lower wind speed.
(State 3)
Heating
-1
+1
Compressor OFF
Setting temperature
Compressor
OFF
Setting temperature
Refrigerating
+1
-1
Compressor ON
3.2.1
3.2.2
3.2.3
3.2.3.1
3.2.3.2
3.2.3.3