HP Designjet L25500 HP Designjet L25500 Printer Series - Site preparation guid - Page 10

Requirements, printer input ratings, power cord plug type, plug type - 42 printer

Page 10 highlights

Requirements To make sure you have the right wall socket outlets (wall receptacles) ready for installation, check the following: 1. The wall socket outlets must be suitable for printer input ratings. See Single phase power on page 4. 2. The wall socket outlets must be suitable for the power cord plug type used in the country of installation. Table 2-6 60 inch printer power cord specifications on page 6 and Table 2-7 42 inch printer power cord specifications on page 6 list several examples of the power cords and the plugs provided with the printer according to the country. To make sure you have the right wall receptacle, find your country in the appropriate table and check the plug type. WARNING! Use only use the power cord supplied by HP with the printer. Do not use a power strip (relocatable power tap) to connect both power cords. Do not damage, cut or repair the power cord. With a damaged power cord, there is risk of fire and electric shock. Always replace a damaged power cord with an HP-approved power cord. Table 2-6 60 inch printer power cord specifications Country HP Part Number * Length Plug type Plug USA, Canada, Mexico, 8120-6893 Japan, Philippines, Thailand 14.8 ft (4.5 m) NEMA 6-20P, 240 V, 20A, non-locking International 8120-6897 14.8 ft (4.5 m) IEC 60309, 240 V, 16 A, 2L+PE International - other 8120-6895 14.8 ft (4.5 m) Stripped end termination, 240 V, 1.5 mm² cross sectional area WARNING! A qualified electrician must attach a suitable plug according to local laws where the printer is installed, and to the printer's electrical requirements. * Alternative part numbers are valid with the same specifications and markings. Table 2-7 42 inch printer power cord specifications Country HP Part Number * Length Plug type Plug Argentina 8121-0925 8.2 feet (2.5 m) IRAM 2073 Brazil 8121-1101 8.2 feet (2.5 m) NBR 14136 Chile, Uruguay 8121-0923 8.2 feet (2.5 m) CEI 23-50 6 Chapter 2 Site preparation requirements ENWW

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14

To make sure you have the right wall socket outlets (wall receptacles) ready for installation, check the
following:
1.
The wall socket outlets must be suitable for
printer input ratings
. See
Single phase power
on page
4
.
2.
The wall socket outlets must be suitable for the
power cord plug type
used in the country of
installation.
Table
2
-
6
60 inch printer power cord specifications
on page
6
and
Table
2
-
7
42 inch
printer power cord specifications
on page
6
list several examples of the power cords and the
plugs provided with the printer according to the country. To make sure you have the right wall
receptacle, find your country in the appropriate table and check the
plug type
.
WARNING!
Use only use the power cord supplied by HP with the printer. Do not use a power
strip (relocatable power tap) to connect both power cords. Do not damage, cut or repair the power
cord. With a damaged power cord, there is risk of fire and electric shock. Always replace a damaged
power cord with an HP-approved power cord.
Table 2-6
60 inch printer power cord specifications
Country
HP Part Number *
Length
Plug type
Plug
USA, Canada, Mexico,
Japan, Philippines,
Thailand
8120-6893
14.8 ft (4.5 m)
NEMA 6-20P, 240 V,
20A, non-locking
International
8120-6897
14.8 ft (4.5 m)
IEC 60309, 240 V, 16
A, 2L+PE
International – other
8120-6895
14.8 ft (4.5 m)
Stripped end
termination, 240 V, 1.5
mm² cross sectional
area
WARNING!
A
qualified electrician
must attach a suitable
plug according to local
laws where the printer
is installed, and to the
printer's electrical
requirements.
* Alternative part numbers are valid with the same specifications and markings.
Table 2-7
42 inch printer power cord specifications
Country
HP Part Number *
Length
Plug type
Plug
Argentina
8121-0925
8.2 feet (2.5 m)
IRAM 2073
Brazil
8121-1101
8.2 feet (2.5 m)
NBR 14136
Chile, Uruguay
8121-0923
8.2 feet (2.5 m)
CEI 23-50
6
Chapter 2
Site preparation requirements
ENWW
Requirements