- HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 1
hp Integrity rx1600 Site Preparation Guide Regulatory Model Number: RSVLA-0302 Version 2.0 Manufacturing Part Number: rx1600_siteprep January 2004 U.S.A. © Copyright 2004 Hewlett-Packard Development Company, L.P.. - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 2
The HP Server Documentation CD-ROM has been provided with your server. It contains a complete documentation set for the server, including localized versions of key documents. Included on the CD-ROM are the Site Preparation and Operations and Maintenance guides, which contain in-depth troubleshooting - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 3
Documents 7 HP Encourages Your Comments 8 Where to Get Help 8 Information to Collect Before You Contact Support 8 2. System Specifications System Configuration 11 Dimensions and Weights 12 Component Dimensions 12 Grounding 12 Electrical Specifications 12 Circuit Breaker 12 System AC Power - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 4
Contents Operational Space Requirements 33 Floor Plan Grid 34 Conversion Factors and Formulas 34 Conversion Factors 34 Formulas 35 Sample of an Installation Schedule 35 Sample Site Inspection Checklist 36 Delivery Survey 38 Glossary 41 Index 43 4 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 5
Figures Figure 2-1. hp Integrity rx1600 Server 11 Figure 2-2. Airflow through hp Integrity rx1600 Server 17 Figure 3-1. Raised Floor Metal Strip Ground System 24 Figure 3-2. Delivery Survey (Part 1 39 Figure 3-3. Delivery Survey (Part 2 40 5 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 6
Figures 6 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 7
product support service. See your HP sales representative for details. IMPORTANT The latest version of this document can be found online at http://docs.hp.com. What's in This Document The hp Integrity rx1600 Site Preparation Guide contains these chapters: • Chapter 2, "System Specifications." Use - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 8
Resource Center at http://itrc.hp.com. Information to Collect Before You Contact Support Before you contact HP support, you should: Step 1. Check information on troubleshooting and attempt to solve the problem. See the hp Integrity rx1600 Operation and Maintenance Guide. • Note failure symptoms and - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 9
of processor, memory, and PCI cards are used and where are they installed? • What accessories are installed? Step 4. Determine the following: • Which firmware versions are in use? • When did the problem start? • Have recent changes been made to the system? • Which operating system and version is - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 10
About This Document Where to Get Help 10 Chapter 1 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 11
2 System Specifications System Configuration The following table lists the minimum and maximum configurations for an hp Integrity rx1600 Server. Table 2-1 Minimum/Maximum Configuration System Name CPU Power Supplies Memory Optional Internal Disks Optional Internal Media Core I/O Minimum 1 1 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 12
System Specifications Dimensions and Weights Dimensions and Weights This section provides dimensions and weights of hp Integrity rx1600 Server components. Component Dimensions Table 2-2 Server Component Dimensions Dimension Height-Inches (Centimeters) Width-Inches (Centimeters) Depth-Inches ( - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 13
System Specifications Electrical Specifications System AC Power Specifications Power Cords Table 1-3 lists the various power cables available for use with the hp Integrity rx1600 Server system. Table 2-3 Power Cords Part Number Description Country 8120-5341 8120-1351 8120-1369 8120-1689 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 14
@240VAC Maximum Theoretical Typical configurationb 400 Maximum PSU load 346@120VAC 370@240VAC Typical a. Maximum power is the sum of the worst case power consumption values of every subsystem in your hp Integrity rx1600 Server. These worst case values should be used to calculate the worst case - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 15
Power Consumption Values CPU Qty Memory Gigabytes PCI Cards (assuming 10W each) DVDs Hard Disk Drives Bulk Power Supplies Typical AC Source Power Specifications This section provides the temperature/humidity requirements, noise emission, and air flow specifications for the HP Server The system - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 16
fan circuitry. The location of the fan status LED is on the control panel of the system. Bulk Power Supply Cooling Cooling for the power supply is provided by two externally mounted fans. Air is pushed through the power supply by the fans and exhausted out the rear of the chassis. Air is ducted out - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 17
Figure 2-2 Airflow through hp Integrity rx1600 Server System Specifications Environmental Specifications Acoustic Noise Specification The acoustic noise specification for the HP Server is as follows: • 6.8 db LpA (sound pressure level at bystander position in a dedicated computer room environment - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 18
System Specifications Environmental Specifications 18 Chapter 2 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 19
(LAHJ) and should make the final decision regarding adherence to region-specific or area-specific electrical codes and guidelines. Proper design and installation of a power distribution system for an hp Integrity rx1600 Server requires specialized skills. Those responsible for this task must have - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 20
connectors to 80% of their RMS current ratings. Power Quality The hp Integrity rx1600 Server is designed to operate over a wide range of voltages and frequencies. The server is tested and shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are exceeded. Severe - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 21
conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for HP computer equipment: • Dedicated power source-Isolates an hp Integrity rx1600 Server power distribution system from other circuits in the - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 22
Systems IT Power System This product has not been evaluated for connection to an IT power system (an AC distribution system having no direct connection to earth according to IEC 60950). An hp Integrity rx1600 Server , or a conductive type cold water service pipe provide an earth ground. Electrical - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 23
) should be used for connecting the system cabinet to the site grounding grid (customer-supplied). When connecting this ground, ensure that the raised floor is properly grounded for high frequency. Power panels located in close proximity to the computer equipment should also be connected to the - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 24
resistance and attachment points for connection to service entrance ground and HP computer equipment). The use of conductive System Ground wire to power panel Floor panel Hex bolt Band and pedestal Grounding braid to computer equipment Equipment Grounding Implementation Details Connect all HP - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 25
System Installation Guidelines This section contains information about installation practices. Some common pitfalls are highlighted. Both power guide for installation procedures. Wiring Connections Expansion and contraction rates vary among different metals. Therefore, the integrity serious problems, - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 26
that penetrate the envelope. • Use at least a 12-inch raised floor system for minimum favorable room air distribution system (underfloor distribution). • Ensure a minimum clearance of 12 inches between the top of the hp Integrity rx1600 Server cabinet and the ceiling to allow for return air flow and - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 27
to the cooling air intake vents of the hp Integrity rx1600 Server equipment cabinets. Supply air temperature should be maintained within the following parameters: • Ceiling supply system-From 55° F (12.8° C) to 60° F (15.6° C) • Floor supply system-At least 60° F (15.6° C) If a ceiling plenum return - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 28
the cooling air intake vents of the hp Integrity rx1600 Server cabinets. • Ceiling plenum air distribution system-Supply air is ducted into the ceiling plenum potential. ESD can cause component damage during servicing operations. Paper feed problems on high-speed printers are usually encountered in - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 29
Environmental Elements Specifically, disk drives build up on the boards. Other failures to power supplies and other electronic components can be caused by problems in mechanical parts. Small dust particles can be prevented from entering the computer room by maintaining the air conditioning system - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 30
General Site Preparation Guidelines Environmental Elements Electrostatic Discharge (ESD) Prevention Static charges (voltage levels) occur when objects are separated or rubbed together. The voltage level of a static charge is determined by the following factors: • Types of materials • Relative - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 31
floor installations. NOTE An appropriate floor system consultant should verify any floor system under consideration for an hp Integrity rx1600 Server installation. Raised Floor Loading Raised floor loading is a function of the manufacturer's load specification and the positioning of the equipment - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 32
panel can support (without failure) when a wheel of specified diameter and width is rolled across the panel. Computed by dividing total equipment weight by the floor system that is satisfactory for the installation of an hp Integrity rx1600 Server. Based on specific information provided by HP, - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 33
may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system. Space Requirements This section contains information about space requirements for an hp Integrity rx1600 Server. This data - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 34
vents • Lighting fixtures • Utility outlets • Doors • Access areas for power wiring and air conditioning filters • Equipment cable routing Conversion Factors and Formulas The conversion factors provided here are intended to ease data calculation for systems that do not conform specifically to the - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 35
sequence of events for a typical system installation: • 60 days before an HP task) • 30 days before installation - Primary power and air specialist to resolve any last minute problems NOTE Not all installations follow a hp Integrity rx1600 Server is scheduled to be installed. Chapter 3 35 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 36
floor installed and in good condition? 6. Is the raised floor adequate for equipment loading? 7. Are there channels or cutouts for cable routing? 8. Is there a remote console telephone line available with an RJ11 jack? Comment or Date 36 Chapter 3 - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 37
line available? 10. Are customer supplied peripheral cables and LAN cables lighting levels adequate for maintenance? 14. Are there AC outlets available for servicing needs? (for example, vacuuming) 15. Does the input voltage correspond to equipment specifications? 15A Is dual source power - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 38
. Area or Condition 33 Are personnel enrolled in the System Administrator's Course? 34 Is on-site training required? Comment instructions or recommendations form. The following list gives examples of special instructions or issues: • Packaging restrictions at the facility, such as size and weight - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 39
Figure 3-2 Delivery Survey (Part 1) General Site Preparation Guidelines Delivery Survey DELIVERY CHECKLIST DOCK DELIVERY Is dock large enough for a semitrailer? Yes No ___________ Circle the location of the dock and give street name if different than address. North West East South - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 40
General Site Preparation Guidelines Delivery Survey Figure 3-3 Delivery Survey (Part 2) ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb or kg Depth Height Width Depth Width Height STAIRS Please list number of flights and stairway - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 41
rate. C CompactPCI The newest specification for PCI-based industrial computers is system's capability to remove heat from the air. Leakage current A term relating to current flowing between the AC supply wires and earth ground. The term does not necessarily denote a fault condition. In power supplies - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 42
specification. Power factor The ratio of true power to apparent power in an AC circuit. In power conversion technology, power factor is used in conjunction with describing the AC input current to the power supply , vinyl wall coverings and vinyl floor systems, in combination with careful sealing of - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 43
ground, 22 grounding systems, 22 lighting requirements, 20 main building electrical ground, 22, 23 power distribution safety grounding, 22 power panel grounds, 22 power quality, 20 sources of electrical disturbances, 21 system installation guidelines, 25 electrical specifications, 12 environmental - HP Integrity rx1600 | Site Preparation Guide, Second Edition - HP Integrity rx16 - Page 44
Index 44