HP Integrity rx5670 Generic Site Preparation Guide, Fourth Edition - Page 25
Windows, Space Requirements, Delivery Space Requirements, Table 1-5: Product Technical Requirements
View all HP Integrity rx5670 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Windows Do not house computers in a room with windows. Sunlight entering a computer room can cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system. Space Requirements This section contains information about space requirements for the server. Use this data as the basic guideline for space plan developments. Also consider factors such as airflow, lighting, and equipment space requirements. Delivery Space Requirements The site must have enough clearance to move equipment safely from the receiving area to the computer room. Permanent obstructions such as pillars or narrow doorway's can cause equipment damage. Include the possible removal of walls or doors in the delivery plans. Operational Space Requirements Consider the following factors in addition to the basic equipment dimensions: • Eliminate obstructions to equipment intake or exhaust flow. • Determine locations of lighting fixtures and utility outlets affecting servicing operations. Plan equipment layout to take advantage of lighting and utility outlets. Do not forget to include clearance for opening and closing equipment doors. • Provide sufficient clearance around the cabinets for proper cooling airflow through the equipment. If other equipment is located so that it exhausts heated air near the cooling air intakes of the server cabinets, more space is needed to keep ambient air intake to the server cabinets within the specified temperature and humidity ranges. See Table 1-5: Product Technical Requirements Based on Customer Environments for operating ranges. Table 1-5 Product Technical Requirements Based on Customer Environments Environment Industry Equivalent:1 ASHRAE Operating Environment (ambient)2 Temp ºC, dry bulb3 (ºF) Relative Humidity %: Noncondensing Allowable5 Recommended Allowable6 Recommended7 Dew-point (max) 4 Rate of Chg ºC/hr, max (ºF/hr, max) Controlled Computer 1 15 to 32 20 to 25 20 to 80 40 to 55 17 5 Room (59 to 90) (68 to 77) (41) Office Controlled 2 10 to 35 20 to 25 20 to 80 40 to 55 (50 to 95) (68 to 77) Uncontrolled 3 5 to 35 NA8 (41 to 95) 8 to 85 NA 21 5 (41) 28 NA Home 4 5 to 35 NA (41 to 95) 8 ot 85 NA 28 NA Light Industrial 4 5 to 40 NA (41 to 104) 8 to 90 NA 28 NA Space Requirements 25