HP LH3000r HP Netserver LXr 8000 Rack Cabling Guide - Page 26
Orient the star-washer on the hex nut toward the painted
View all HP LH3000r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 26 highlights
Chapter 2 Connecting and Routing Cables to the HP NetServer LXr 8000 Figure 2-5. Mounting the PDU Vertically 2. Use the row of mounting holes nearest the outside edge of the vertical column. Use the hex nut and screw supplied with the PDU. Hold the nut behind the column and insert the screw through the top mounting bracket of the PDU, and through the face of the vertical column. Start it in the nut. See Figure 2-5. 3. Insert a screw through the other mounting bracket of the PDU, through the vertical column, and into a nut. Tighten both screws. CAUTION Orient the star-washer on the hex nut toward the painted surface of the rack. Ensure the screw and nut are tightened sufficiently to cause the star washers to pierce the paint and bring the lock washer teeth in contact with metal. This ensures that the rack ground connection to the PDU is reliable. 22