HP Server rp2400 rp24xx A180 User Manual - Page 26
Cooling Requirements, Temperature Parameters, Relative Humidity
View all HP Server rp2400 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 26 highlights
A-Class Server Installation A-Class Server Site Preparation • Nominal Frequency: 50 or 60 Hz • Typical current requirements: 1.0A at 100V 0.43A at 240V. If an Uninterruptible Power Supply (UPS) is to be used, ensure that it is properly connected to the server. Refer to the, External Connections section for UPS information. Power cord plugs for stand-alone servers are configured to meet unique power configurations used all over the world. Cabinet-mounted servers have the same power requirements as stand-alone servers. However, the power cords for cabinets are dependent on the type of Power Distribution Unit (PDU) operation. PDU power cords with one end stripped are also available for attaching country-specific power plugs. Refer to the cabinet documentation for more electrical power information. Cooling Requirements Temperature Parameters The operating and non-operating temperatures shown below are the extremes at which server parameters have been established. Operating Non-Operati ng +5°-+35°C -40° - +65°C (41° - 95°F) (-40° - 149°F) Relative Humidity Operating and non-operating relative humidity parameters are shown below: Operating Relative Humidity 15% to 80%, non-condensing Non-Operating Relative Humidity 5% to 90%, non-condensing 26 Chapter 2