HP Xw25p HP BladeSystem p-Class System Overview and Planning - Page 44

Deployment considerations: ProLiant BL p-Class GbE Interconnect Switches

Page 44 highlights

Table 20: Ethernet and FC Cable Requirements (continued) Interconnect F-GbE2 Interconnect Kit Storage Connectivity Kit Ethernet 1 to 8 optical cables with LC connectors per server blade enclosure 1 to 4 cables per server blade enclosure 1 cable for the centralized server blade management module on enclosures with enhanced backplane components N/A FC Requires Storage Connectivity Kit Same as RJ-45 Patch Panel 2 Deployment considerations: ProLiant BL p-Class GbE Interconnect Switches The C-GbE Interconnect Kit provides eight 10/100T and four 10/100/1000T external Ethernet ports all with RJ-45 connectors; one to twelve ports may be used. Therefore, plan on one to twelve network cables (CAT5 or better) per server blade enclosure. The F-GbE Interconnect Kit provides eight 10/100T external Ethernet ports with RJ-45 connectors and four 1000SX external Ethernet ports with LC connectors; one to twelve ports may be used. Therefore, plan on one to eight network cables (CAT5 or better) and one to four optical network cables per server blade enclosure. LC-to-SC optical connector converters can be used if SC connectors are preferred. HP BladeSystem rack specifications HP BladeSystem enclosures are designed to fit in the following HP ProLiant and third-party racks: • HP ProLiant 10000 Series Racks (recommended) • ProLiant 9000 Series Racks • Telco racks (optional telco rack kit available) Server blade enclosures fit in 6U of panel height in a standard 19-inch wide rack. The enclosure dimensions are: • Height-26.7 cm (10.5 in) • Width-44.5 cm (17.5 in) • Depth- 71.8 cm (28.25 in) deep The following minimum rack specifications should be considered when deploying server blade systems in third-party racks and cabinets: • Compatible with 19-in Standard EIA rail sets • EIA rail-to-rail depth is 73.66 to 76.20 cm (29 to 30 in) • Cabinet depth must be at least 91.44 cm (36 in) deep overall [additional minimum 8.89 cm (3.5 in) clearance from rear RETMA rail to rear door, inclusive in the 91.44 cm (36 in) overall depth] • Ample room for top and bottom cable egress [approximately 20.32 sq cm (8 sq in) for full rack configuration with the patch panel] • Must be capable of supporting 725.75 kg (1600 lb) for full rack configuration • Perforated front and rear doors to accommodate front-to-back cooling • Must have 65% open perforation on server blade enclosure doors to support airflow requirements 44

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

44
Table 20: Ethernet and FC Cable Requirements (
continued
)
Interconnect
Ethernet
FC
F-GbE2 Interconnect
Kit
1 to 8 optical cables with LC connectors per server
blade enclosure
1 to 4 cables per server blade enclosure
1 cable for the centralized server blade
management module on enclosures with enhanced
backplane components
Requires Storage Connectivity Kit
Storage Connectivity
Kit
N/A
Same as RJ-45 Patch Panel 2
Deployment considerations: ProLiant BL p-Class GbE Interconnect Switches
The C-GbE Interconnect Kit provides eight 10/100T and four 10/100/1000T external Ethernet ports
all with RJ-45 connectors; one to twelve ports may be used. Therefore, plan on one to twelve network
cables (CAT5 or better) per server blade enclosure.
The F-GbE Interconnect Kit provides eight 10/100T external Ethernet ports with RJ-45 connectors and
four 1000SX external Ethernet ports with LC connectors; one to twelve ports may be used. Therefore,
plan on one to eight network cables (CAT5 or better) and one to four optical network cables per
server blade enclosure. LC-to-SC optical connector converters can be used if SC connectors are
preferred.
HP BladeSystem rack specifications
HP BladeSystem enclosures are designed to fit in the following HP ProLiant and third-party racks:
HP ProLiant 10000 Series Racks (recommended)
ProLiant 9000 Series Racks
Telco racks (optional telco rack kit available)
Server blade enclosures fit in 6U of panel height in a standard 19-inch wide rack. The enclosure
dimensions are:
Height–26.7 cm (10.5 in)
Width–44.5 cm (17.5 in)
Depth– 71.8 cm (28.25 in) deep
The following minimum rack specifications should be considered when deploying server blade
systems in third-party racks and cabinets:
Compatible with 19-in Standard EIA rail sets
EIA rail-to-rail depth is 73.66 to 76.20 cm (29 to 30 in)
Cabinet depth must be at least 91.44 cm (36 in) deep overall [additional minimum 8.89 cm
(3.5 in) clearance from rear RETMA rail to rear door, inclusive in the 91.44 cm (36 in) overall
depth]
Ample room for top and bottom cable egress [approximately 20.32 sq cm (8 sq in) for full rack
configuration with the patch panel]
Must be capable of supporting 725.75 kg (1600 lb) for full rack configuration
Perforated front and rear doors to accommodate front-to-back cooling
Must have 65% open perforation on server blade enclosure doors to support airflow requirements