Honeywell 4219 Installation Guide - Page 2

See The Control Panel's Installation And Setup Guide For Complete Information, Regarding - addressing a

Page 2 highlights

DIP SWITCH FOR SETTING ADDRESS AND ZONE A RESPONSE 4219 NOTE FOR CE INSTALLATIONS A N6361EMI SUPPRESSION BEAD IS REQUIRED. REED (TAMPER) SWITCH TAMPER JUMPER POSITION 4219 IN CABINET (NOT TAMPER) 4219 REMOTE (TAMPER PROTECTED) 4-PIN CONSOLE PLUG CONNECTIONS SAME AS TB2 TB1 1 2 3 4 5 6 7 8 9 10 11 12 TB2 4 3 4 3 22 11 GRN DATA OUT TO CONTROL BLK (-) GROUND RED (+) 12VDC YEL DATA IN FROM CONTROL ZONES A B CD EF GH Figure 2. Summary of Connections TERMINATE EACH PROGRAMMED ZONE WITH 1000 OHM END-OF-LINE RESISTOR (EACH ZONE'S MAX. LOOP RESISTANCE: 300 OHMS + EOL) 4219-SOC-V0 © 12 3 4 5 OFF ON © © © © SWITCH NUMBER 4219 ADDRESS SETTINGS ("-"means"OFF") 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 ON - ON - ON - ON - ON - ON - ON - ON - 3 ON ON - - ON ON - - ON ON - - ON ON - - 4 ON ON ON ON - - - - ON ON ON ON - - - - 5 ON ON ON ON ON ON ON ON DIP SWITCH: (WHITE AREAS DENOTE SWITCH HANDLES) POSITIONS 2-5: DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS FOR ADDRESS USE. SWITCH SETTING SHOWN SET FOR ADDRESS "0". POSITION 1: DETERMINES ZONE A's RESPONSE TIME: ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED). OFF = FAST (10MS) RESPONSE TO AN OPEN. 4219-001-V0 Figure 3. DIP Switch Settings SEE THE CONTROL PANEL'S INSTALLATION AND SETUP GUIDE FOR COMPLETE INFORMATION REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SYSTEM.

  • 1
  • 2
  • 3
  • 4

4219
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4
3
2
1
ZONES
A
B
C
D
F
G
H
TAMPER JUMPER POSITION
4219 IN CABINET
(NOT TAMPER)
4219 REMOTE
(TAMPER PROTECTED)
TB1
TB2
4-PIN CONSOLE PLUG
CONNECTIONS SAME
AS TB2
1
2
3
4
DATA OUT
TO CONTROL
DATA IN
FROM CONTROL
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE:
300 OHMS + EOL)
5
8
11
REED (TAMPER) SWITCH
2
E
1
3
4
6
7
9
10
12
DIP SWITCH
FOR SETTING ADDRESS
AND ZONE A RESPONSE
NOTE
FOR CE INSTALLATIONS A
N6361EMI SUPPRESSION
BEAD IS REQUIRED.
4219-SOC-V0
Figure 2.
Summary of Connections
4219 ADDRESS SETTINGS
SWITCH
NUMBER
("—" means"OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
ON
ON
ON
ON
ON
ON
ON
ON
3
ON ON
ON
ON
ON
ON
ON
ON
4
ON ON
ON
ON
ON
ON
ON
ON
5
ON ON
ON
ON
ON
ON
ON
ON
1
2
3
4
5
OFF
ON
DIP SWITCH:
(WHITE AREAS DENOTE SWITCH HANDLES)
4219-001-V0
POSITIONS 2-5:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS.
CONSULT CONTROL'S INSTRUCTIONS FOR ADDRESS USE.
SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES ZONE A's RESPONSE TIME:
ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED).
OFF = FAST (10MS) RESPONSE TO AN OPEN.
Figure 3.
DIP Switch Settings
SEE THE CONTROL PANEL’S INSTALLATION AND SETUP GUIDE FOR COMPLETE INFORMATION
REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SYSTEM.