Honeywell 4229 Installation Guide - Page 1

Honeywell 4229 - Ademco 8 Zone Expander Manual

Page 1 highlights

N8910 9/97 Rev. B ADEMCO 4229 WIRED ZONE EXPANDER/RELAY MODULE INSTALLATION AND SETUP GUIDE GENERAL INFORMATION The ADEMCO 4229 Wired Zone Expander/Relay Module adds up to eight end-of-line resistor supervised zones and two dry form C (SPDT) relay outputs to compatible control communicators via the control's keypad wiring. The module may be mounted within the control's cabinet (if room permits), or remotely. If mounted remotely, there are provisions to tamper-protect the unit. Communication to the module is supervised so that it cannot be disconnected from the keypad wiring without detection by the control. If the wiring is cut, a tamper or alarm signal will result, to indicate that this device (and possibly other similarly connected devices) has become inoperative. INSTALLATION When the module is to be mounted inside the control's cabinet, it should be mounted horizontally. Insert selftapping screws (provided) in two adjacent raised tabs at the back of the cabinet. Leave the heads projecting 1/8". Hang the module on the screw heads via two of the slotted holes on the back of its housing. In this case, the module's cover need not be tamper protected. If the tamper jumper (see the diagram) is placed in its upper position, the module's cover can be left off. See the control's instructions for additional information. When the module is to be mounted remotely, holes on its back permit it to be mounted horizontally or vertically. Wires can exit from the side or the breakout on the back of its housing. The tamper jumper should be put into its lower position and, when the installation is completed, the module's cover put on. A magnet in the cover, positioned near a reed switch in the unit, will cause a tamper signal to be sent to the control if the cover is removed. If a zone is not programmed, the resistor need not be used. The method of programming each zone for type of alarm and reporting code to the central monitoring station varies with the control to which the module is connected. Refer to the installation instructions for that control unit. Set the DIP switch to one of 16 addresses, as shown in the table below, so the control can identify the module and communicate with it properly. The address to be set is determined by the particular control to be used, and the control's installation instructions must be consulted. As shipped, the DIP switch is set for an address of "0". Zone A can be set for a fast response time of 10ms to an open circuit, if desired, by setting position 1 of the DIP switch to "OFF". As shipped, it is set to "ON" for a response time of 300ms, as shown in the table below. All of the module's other protection zones have a nominal response time of 300ms. Connections to the module's two relays are made via the 7conductor cord provided. Refer to the control's installation instructions for specific information on how to program the control's various activation options for the relays. Connections to the control's keypad wiring points can be made via 4-position terminal block TB2, the 4-pin plug, or both (wire color connections are the same) SPECIFICATIONS Physical 6-7/16"W x 4-1/4"H x 1-1/4"D (163mm x 108mm x 32mm) Electrical Input Voltage: 12VDC (from control's remote keypad connection points) Affix the connections label that accompanies the unit to the inside of the module's cover (if the cover is to be used)) or to the inside of the control's cover CONNECTIONS AND SETTINGS Input Current: 30mA (relays off) 100mA (relays on) Relay Contact Rating: 2A max. at 28VDC/AC See the table below and the diagram on the reverse side. Make protection zone connections to 12-position terminal block TB1. Each zone that is used must have a 1000 ohm end-of-line resistor connected across the end of its loop, as shown. DIP SWITCH SETTINGS OFF ON SWITCH NUMBER W I R E D Z O N E E X PA N D E R / R E L AY A D D R E S S S E T T I N G S ("-" means "OFF") © 12 3 4 5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 ON - ON - ON - ON - ON - ON - ON - ON - 3 ON ON - - ON ON - - ON ON - - ON ON - - 4 ON ON ON ON - - - - ON ON ON ON - - - - 5 ON ON ON ON ON ON ON ON © © © © 4229-003-V0

  • 1
  • 2

N8910
9/97
Rev. B
ADEMCO 4229
WIRED ZONE EXPANDER/RELAY MODULE
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 4229 Wired Zone Expander/Relay Module
adds up to eight end-of-line resistor supervised zones and
two dry form C (SPDT) relay outputs to compatible control
communicators via the control’s keypad wiring.
The module may be mounted within the control’s cabinet (if
room permits), or remotely.
If mounted remotely, there are
provisions to tamper-protect the unit.
Communication to the
module is supervised so that it cannot be disconnected from
the keypad wiring without detection by the control.
If the
wiring is cut, a tamper or alarm signal will result, to indicate
that this device (and possibly other similarly connected
devices) has become inoperative.
INSTALLATION
When the module is to be mounted inside the control
s
cabinet
, it should be mounted horizontally.
Insert self-
tapping screws (provided) in two adjacent raised tabs at the
back of the cabinet.
Leave the heads projecting 1/8
.
Hang
the module on the screw heads via two of the slotted holes
on the back of its housing.
In this case, the module
s cover
need not be tamper protected.
If the tamper jumper (see the
diagram) is placed in its upper position, the module
s cover
can be left off.
See the control
s instructions for additional
information.
When the module is to be mounted remotely
, holes on its
back permit it to be mounted horizontally or vertically.
Wires
can exit from the side or the breakout on the back of its
housing.
The tamper jumper should be put into its lower
position and, when the installation is completed, the
module
s cover put on.
A magnet in the cover, positioned
near a reed switch in the unit, will cause a tamper signal to
be sent to the control if the cover is removed.
Affix the connections label that accompanies the unit to the
inside of the module
s cover (if the cover is to be used)) or to
the inside of the control
s cover
CONNECTIONS AND SETTINGS
See the table below and the diagram on the reverse side.
Make protection zone connections
to 12-position terminal
block TB1.
Each zone that is used must have a 1000 ohm
end-of-line resistor connected
across the end of its loop
, as
shown.
If a zone is not programmed, the resistor need not be used.
The method of programming each zone for type of alarm
and reporting code to the central monitoring station varies
with the control to which the module is connected.
Refer to
the installation instructions for that control unit.
Set the DIP switch to one of 16 addresses, as shown in the
table below
, so the control can identify the module and
communicate with it properly.
The address to be set is
determined by the particular control to be used, and the
control
s installation instructions must be consulted.
As
shipped, the DIP switch is set for an address of
0
.
Zone A can be set for a fast response time
of 10ms to an
open circuit, if desired, by setting position 1 of the DIP
switch to
OFF
.
As shipped, it is set to
ON
for a response
time of 300ms, as shown in the table below.
All of the
module
s other protection zones have a nominal response
time of 300ms.
Connections to the module
s two relays are made via the 7-
conductor cord provided.
Refer to the control
s installation
instructions for specific information on how to program the
control
s various activation options for the relays.
Connections to the control
s keypad wiring points
can be
made via 4-position terminal block TB2, the 4-pin plug, or
both (wire color connections are the same)
SPECIFICATIONS
Physical
6-7/16
W x 4-1/4
H x 1-1/4
D
(163mm x 108mm x 32mm)
Electrical
Input Voltage:
12VDC (from control
s remote keypad
connection points)
Input Current:
30mA (relays off)
100mA (relays on)
Relay Contact
Rating:
2A max. at 28VDC/AC
WIRED ZONE EXPANDER/RELAY ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
ON
ON
ON
ON
ON
ON
ON
ON
3
ON
ON
ON
ON
ON
ON
ON
ON
4
ON
ON
ON
ON
ON
ON
ON
ON
5
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
5
OFF
ON
4229-003-V0
DIP SWITCH SETTINGS