Honeywell DH90A1007 Installation Guide - Page 3

Installation Checklist, 1A Power Accessibility, 1B Accessibility, 1C Support Structure - review

Page 3 highlights

For HVAC Installer Only • Installation Guide 1. Intended Application for DH90 The DH90 is intended for use in residential applications to reduce the indoor humidity levels and increase comfort. With the optional ventilation ducting and ventilation control hookup, the device also provides precise amounts of ventilation air. 2. Approvals The DH90 is certified by ETL to meet UL 474 and CSA 22.2 No. 92. 3. Specifications Model: DH90 Electrical: 110-120 VAC, 6.2 Amps, 60 Hz, grounded Capacity: 90 pints/day @ 80°F, 60% RH Inlet air temperature range: 55°F min., 100°F max. Air Flow: 200 CFM without external ducting Refrigerant Charge: 1 lb., 12 oz. R22 Duct Connections: Round 10" inlet, 10" outlet, 6" ventilation inlet Filter Size: Pleated Merv 11: 14" x 14" x 1" Unit Size (w/o Duct Collars): 34.5"L x 15.75"W x 20.875"H Unit Weight: 92 lbs Shipping Weight: 99 lbs 4. Installation 4.1 Installation Checklist Important: Prior to installation of the DH90, the following checklist should be reviewed. The DH90 can be installed in a variety of locations to meet the owner's needs, and integrate with existing forced air systems or existing ductwork if desired. Choose a location with consideration to accessibility for service, drain availability, and power outlet location. 4.1A Power Accessibility Unit should be located in an area where the cord's length (10') should easily reach a 115 VAC electrical outlet with a minimum of a 15 A circuit capacity. 4.1B Accessibility The installed DH90 should have at least 14 inches of clearance in the front of the device to service the filter. 4.1C Support Structure and Suspension Place the DH90 on supports to raise the base of the unit. Do not place the DH90 directly on structural building members without vibration absorbers or unwanted noise may result. The DH90 may be suspended from structural members by supporting the entire base of the unit via cross members, rigid frame, or the like. Do not hang the a DH90 from the cabinet. Remember to place a drain pan under the unit if it is suspended above a finished area or above an area where water leakage could cause damage. 4.1D Sizing Chart *This sizing chart is based on extreme climates where Rh levels are between 70 and 90% outdoor Rh. For less extreme climates then larger homes can be adequetely served. Actual requirements may vary. Home Size (square feet) Dehumidifier Capacity Required to Maintain Desired Indoor Rh* 60% Indoor 55% Indoor 50% Indoor Rh Rh Rh Pints/day Pints/day Pints/day 2080 49-54 55-58 71-78 2600 61-68 65-72 90-97 3120 75-82 79-86 95-110 4.2 Electrical Requirements Warning: Installation must be performed by a qualified service technician and must comply with local codes. Remove power to the device before installing or servicing the device. Failure to connect the device according to these instructions may result in damage to the device or the controls. 

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12

For HVAC Installer Only
• Installation Guide
²
1. Intended Application for DH90
The DH90 is intended for use in residential
applications to reduce the indoor humidity levels
and increase comfort. With the optional ventilation
ducting and ventilation control hookup, the device
also provides precise amounts of ventilation air.
2. Approvals
The DH90 is certified by ETL to meet UL 474 and
CSA 22.2 No. 92.
3. Specifications
Model: DH90
Electrical: 110-120 VAC, 6.2 Amps,
60 Hz, grounded
Capacity: 90 pints/day @ 80°F, 60%
RH
Inlet air temperature range:
55°F min., 100°F max.
Air Flow: 200 CFM without external
ducting
Refrigerant Charge: 1 lb., 12 oz. R22
Duct Connections:
Round 10" inlet, 10"
outlet, 6" ventilation
inlet
Filter Size: Pleated MERV 11:
14" x 14" x 1"
Unit Size (w/o Duct Collars): 34.5"L x 15.75"W
x 20.875"H
Unit Weight: 92 lbs
Shipping Weight: 99 lbs
4. Installation
4.1 Installation Checklist
IMPORTANT:
Prior to installation of the
DH90, the following checklist should be
reviewed.
The DH90 can be installed in a variety of locations
to meet the owner’s needs, and integrate with
existing forced air systems or existing ductwork
if desired. Choose a location with consideration
to accessibility for service, drain availability, and
power outlet location.
4.1A Power Accessibility
Unit should be located in an area where the cord’s
length (10') should easily reach a 115 VAC electrical
outlet with a minimum of a 15 A circuit capacity.
4.1B Accessibility
The installed DH90 should have at least 14 inches
of clearance in the front of the device to service
the filter.
4.1C Support Structure and Suspension
Place the DH90 on supports to raise the base of the
unit. Do not place the DH90 directly on structural
building members without vibration absorbers or
unwanted noise may result.
The DH90 may be suspended from structural
members by supporting the entire base of the unit
via cross members, rigid frame, or the like.
Do not
hang the a DH90 from the cabinet.
Remember to
place a drain pan under the unit if it is suspended
above a finished area or above an area where
water leakage could cause damage.
4.1D Sizing Chart
*This sizing chart is based on extreme climates where Rh levels
are between 70 and 90% outdoor Rh. For less extreme climates
then larger homes can be adequetely served. Actual requirements
may vary.
4.2 Electrical Requirements
WARNING:
Installation must be performed
by a qualified service technician and must
comply with local codes. Remove power to
the device before installing or servicing the
device. Failure to connect the device
according to these instructions may result in
damage to the device or the controls.
Dehumidifier Capacity Required to
Maintain Desired Indoor Rh*
Home Size
(square
feet)
60% Indoor
Rh
55% Indoor
Rh
50% Indoor
Rh
Pints/day
Pints/day
Pints/day
2080
49-54
55-58
71-78
2600
61-68
65-72
90-97
3120
75-82
79-86
95-110