Honeywell HM509 Owners Guide - Page 22
Installation Guide
![]() |
View all Honeywell HM509 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 22 highlights
Installation Guide Troubleshooting No. of Red Light Blinks 4 5 6 7 Fault Description AutoRecoverable? Steps to Fix To be Performed by Professional HVAC Technician Only Heating element No overheated. Input voltage insufficient. Yes, system will return to "Ready" if fault no longer exists in 1 hour. Water overflow sensed. Yes, system will return to "Ready" if fault no longer exists in 1 hour. HVAC power not Yes, system will present (monitor this return to "Ready" fault only when DIP 4 if fault no longer and 5 are OFF). exists in 1 hour. • Follow tank cleaning steps (pages 23-26). • Reassemble tank and press the RESET button. • If fault returns, replace with applicable TrueSTEAM. • Unplug and replug the unit in to see if the fault returns. • If fault returns, unplug unit and remove cover. • Ensure wiring connections are secure and attached. • If fault returns, replace the TrueSTEAM with a new one (field service is not recommended in the event line voltage is lost). • Ensure drain hose is not kinked or submerged in water at the drain. Check functionality of condensate pump if used. • Check for water coming out of drain/overflow line. If continuous water flow is present, follow the cleaning steps on pages 23-26. • Press EMPTY button to drain tank. • Set humidistat RH setpoint to Test mode. • If fault returns, unplug TrueSTEAM. • Loosen cover screw and remove cover. • Disconnect water level sensor wiring and lift snap-hinge clamp to remove water sensor assembly. See image on page 17. • Clean probes using warm soapy water so that the metal is exposed. • Reassemble the sensor assembly in the unit, reattach and secure cover. • Plug unit in, and press RESET button. • If fault reappears, replace water sensor assembly and/or solenoid valve. • Unplug and replug the unit in to see if power returns. • If not, ensure HVAC equipment has power. Check circuit breaker and replace fuse if circuit is tripped. • Unplug TrueSTEAM and remove cover. • Ensure DIP 4 is ON and reattach cover. • Plug unit in. • If fault reappears, ensure the circuit being used has the rating to support the unit. Unplug any additional equipment plugged into this circuit. If fault disappears, the circuit capacity is not properly sized to your unit. • If fault returns, replace unit. 69-2036EFS-07 20
![](/manual_guide/products/honeywell-hm509vpiaq-owners-guide-4d4e3cb/22.png)