For R290, Amount Of, Refrigerant Kg, Min. Room Area M², Warning, Caution, > 0.1520 And ≥ 0.1672 - manual

Page 5 highlights

NS-AC06PWH1/NS-AC07PWH1/NS-AC08PWH1 • Appliance should be installed, operated, and stored in a room with a floor area according to the amount of refrigerant to be charged. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself. When there are differences between the label and the manual on the Min. room area description, the description on the label shall prevail. FOR R290 AMOUNT OF REFRIGERANT (KG) > 0.0836 and ≥ 0.1045 > 0.1045 and ≥ 0.1254 > 0.1254 and ≥ 0.1520 > 0.1520 and ≥ 0.1672 > 0.1672 and ≥ 0.1881 > 0.1881 and ≥ 0.2090 MIN. ROOM AREA (M²) AMOUNT OF REFRIGERANT (KG) 4 > 0.2090 and ≥ 0.2299 4 > 0.2299 and ≥ 0.2508 4 > 0.2508 and ≥ 0.2717 8 > 0.2717 and ≥ 0.2926 9 > 0.2926 and ≥ 0.3040 10 MIN. ROOM AREA (M²) 11 12 13 14 15 • Compliance with national gas regulations shall be observed. • Keep ventilation openings clear of obstruction. • The appliance shall be stored so as to prevent mechanical damage from occurring. • A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. • Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification. • Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. • Please follow the instruction carefully to handle, install, clear, and service the air conditioner to avoid any damage or hazard. Flammable Refrigerant R32 is used within this air conditioner. When maintaining or disposing the air conditioner, the refrigerant (R32 or R290) shall be recovered properly. It shall not be discharge to the air directly. • No open fire or device like switch which may generate spark/arcing shall be around air conditioner to avoid causing ignition of the flammable refrigerant used. Please follow the instruction carefully to store or maintain the air conditioner to prevent mechanical damage from occurring. • Flammable refrigerant R32 is used in air conditioner. Please follow the instruction carefully to avoid any hazard. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself. Caution: Risk of fire/ flammable materials (Required for R32/R290 units only) Explanation of symbols displayed on the unit (When the unit uses R32/R290 Refrigerant only): WARNING This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire. CAUTION This symbol shows that the operation manual should be read carefully. CAUTION This symbol shows that a service personnel should be handling this equipment with reference to the installation manual. CAUTION This symbol shows that information is available such as the operating manual or installation manual. 1 Transport of equipment containing flammable refrigerants See transport regulations 2 Marking of equipment using signs See local regulations www.insigniaproducts.com 5

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30

www.insigniaproducts.com
5
NS-AC06PWH1/NS-AC07PWH1/NS-AC08PWH1
Appliance should be installed, operated, and stored in a room with a floor area according to the amount of refrigerant
to be charged. For specific information on the type of gas and the amount, please refer to the relevant label on the unit
itself. When there are differences between the label and the manual on the Min. room area description, the description
on the label shall prevail.
Compliance with national gas regulations shall be observed.
Keep ventilation openings clear of obstruction.
The appliance shall be stored so as to prevent mechanical damage from occurring.
A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation.
Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate
from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in
accordance with an industry recognized assessment specification.
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair
requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent
in the use of flammable refrigerants.
Please follow the instruction carefully to handle, install, clear, and service the air conditioner to avoid any damage or
hazard. Flammable Refrigerant R32 is used within this air conditioner. When maintaining or disposing the air
conditioner, the refrigerant (R32 or R290) shall be recovered properly. It shall not be discharge to the air directly.
No open fire or device like switch which may generate spark/arcing shall be around air conditioner to avoid causing
ignition of the flammable refrigerant used. Please follow the instruction carefully to store or maintain the air
conditioner to prevent mechanical damage from occurring.
Flammable refrigerant R32 is used in air conditioner. Please follow the instruction carefully to avoid any hazard. For
specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.
Explanation of symbols displayed on the unit (When the unit uses R32/R290 Refrigerant only):
1
Transport of equipment containing flammable refrigerants
See transport regulations
2
Marking of equipment using signs
See local regulations
FOR R290
AMOUNT OF
REFRIGERANT (KG)
MIN. ROOM AREA (M²)
AMOUNT OF
REFRIGERANT (KG)
MIN. ROOM AREA (M²)
> 0.0836 and ≥ 0.1045
4
> 0.2090 and ≥ 0.2299
11
> 0.1045 and ≥ 0.1254
4
> 0.2299 and ≥ 0.2508
12
> 0.1254 and ≥ 0.1520
4
> 0.2508 and ≥ 0.2717
13
> 0.1520 and ≥ 0.1672
8
> 0.2717 and ≥ 0.2926
14
> 0.1672 and ≥ 0.1881
9
> 0.2926 and ≥ 0.3040
15
> 0.1881 and ≥ 0.2090
10
WARNING
This symbol shows that this appliance used a flammable refrigerant.
If the refrigerant is leaked and exposed to an external ignition
source, there is a risk of fire.
CAUTION
This symbol shows that the operation manual should be read
carefully.
CAUTION
This symbol shows that a service personnel should be handling this
equipment with reference to the installation manual.
CAUTION
This symbol shows that information is available such as the
operating manual or installation manual.
Caution: Risk of fire/
flammable materials
(Required for R32/R290 units only)