Electrical Requirements - U.S.A. Only WARNING ■ This range is manufactured with a 4-wire power supply cord rated at 240 volts, 40 amps, rated at 194°F (90°C) and investigated for use with this range. Electrical Shock Hazard Electrically ground range. Failure to do so can result in death, fire, or electrical shock. Be sure that the electrical connection and wire size are adequate and in conformance with the National Electrical Code, ANSI/ NFPA 70-latest edition and all local codes and ordinances. A copy of the above code standards can be obtained from: National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 WARNING: Improper connection of the equipment-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service technician if you are in doubt as to whether the appliance is properly grounded. Do not modify the power supply cord plug. If it will not fit the outlet, have a proper outlet installed by a qualified electrician. Range Rating* Specified Rating of Power Supply Cord Kit and Circuit Protection 120/240 Volts 120/208 Volts Amps Temp Rating 8.8 - 16.5 kW 7.8 - 12.5 kW 40 or 50 194°F (90°C) 16.6 - 22.5 kW 12.6 - 18.5 kW 50 194°F (90°C) *The NEC calculated load is less than the total connected load listed on the model/serial/rating plate. ■ When a 4-wire, single phase 240 volt, 60 Hz., AC only electrical supply is available, a 40-amp minimum circuit protection is required on 30" (76.2 cm) ranges, fused on both sides of the line. ■ A time-delay fuse or circuit breaker is recommended. ■ This range is equipped with a UL or CSA International Certified Power Cord intended to be plugged into a standard 14-50R wall receptacle. Be sure the wall receptacle is within reach of range's final location. Electrical Connection Check local codes and consult gas supplier. Check existing electrical supply and gas supply. See "Gas Supply Requirements" sections. It is recommended that all electrical connections be made by a licensed, qualified electrical installer. ■ Range must be connected to the proper electrical voltage and frequency as specified on the model/serial/rating plate. The model/serial/rating plate is located on the right vertical surface of the oven door frame. Refer to the illustrations in the "Product Dimensions" section of the "Location Requirements" section. ■ Do not use an extension cord. ■ The wiring diagram is located on the back of the range or in a clear plastic bag. 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

6
Electrical Requirements - U.S.A. Only
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
WARNING:
Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. Check with a
qualified electrician or service technician if you are in doubt as to
whether the appliance is properly grounded. Do not modify the
power supply cord plug. If it will not fit the outlet, have a proper
outlet installed by a qualified electrician.
Electrical Connection
Check local codes and consult gas supplier. Check existing
electrical supply and gas supply. See “Gas Supply
Requirements” sections.
It is recommended that all electrical connections be made by a
licensed, qualified electrical installer.
Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial/rating plate.
The model/serial/rating plate is located on the right vertical
surface of the oven door frame. Refer to the illustrations in the
“Product Dimensions” section of the “Location
Requirements” section.
This range is manufactured with a 4-wire power supply cord
rated at 240 volts, 40 amps, rated at 194°F (90°C) and
investigated for use with this range.
*The NEC calculated load is less than the total connected load
listed on the model/serial/rating plate.
When a 4-wire, single phase 240 volt, 60 Hz., AC only
electrical supply is available, a 40-amp minimum circuit
protection is required on 30" (76.2 cm) ranges, fused on both
sides of the line.
A time-delay fuse or circuit breaker is recommended.
This range is equipped with a UL or CSA International
Certified Power Cord intended to be plugged into a standard
14-50R wall receptacle. Be sure the wall receptacle is within
reach of range’s final location.
Do not use an extension cord.
The wiring diagram is located on the back of the range or in a
clear plastic bag.
WARNING
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or
electrical shock.
Range Rating*
Specified Rating of Power
Supply Cord Kit and
Circuit Protection
120/240 Volts
120/208 Volts
Amps
Temp Rating
8.8 - 16.5 kW
16.6 - 22.5 kW
7.8 - 12.5 kW
12.6 - 18.5 kW
40 or 50
50
194°F (90°C)
194°F (90°C)