Jenn-Air JXW8030WS Dimension Guide - Page 1

Jenn-Air JXW8030WS Manual

Page 1 highlights

30" (76.2 cm), 36" (91.4 cm) and 42" (106.7 cm) Wall-Mount Canopy Range Hood PRODUCT MODEL NUMBERS JXW8030W JXW8036W JXW8042W ELECTRICAL REQUIREMENTS A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is required. VENTING METHODS This canopy hood is factory set for venting through the roof or wall. A 8" (20.0 cm) round vent system is needed for installation (not included). The hood exhaust opening is 8" (20.0 cm) round. NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance. Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed. Rear discharge A 90° elbow may be installed immediately above the hood. For Non-Vented (recirculating) Installations If it is not possible to vent cooking fumes and vapors to the outside, the hood can be used in the non-vented (recirculating) version, fitting a charcoal filter and the deflector. Fumes and vapors are recycled through the top grille. Roof Venting A Wall Venting Non-vented (recirculating) A B B B A Example vent system 90 elbow 6 ft (1.8 m) Wall cap 2 ft (0.6 m) The following example falls within the maximum recommended vent length of 35 ft (10.7 m). 1 - 90° elbow 1 - wall cap 8 ft (2.4 m) straight = 5.0 ft (1.5 m) = 0.0 ft (0.0 m) = 8.0 ft (2.4 m) Length of system = 13.0 ft (3.9 m) LOCATION REQUIREMENTS Have a qualified technician install the range hood. It is the installer's responsibility to comply with installation clearances specified on the model/serial rating plate. The model/serial rating plate is located behind the left filter on the rear wall of the vent hood. Canopy hood location should be away from strong draft areas, such as windows, doors and strong heating vents. For Mobile Home Installations The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local codes. PRODUCT DIMENSIONS A. Roof cap B. 8" (20.0 cm) round vent A. Wall cap B. 8" (20.0 cm) round vent A. Deflector B. 8" (20.0 cm) round vent Calculating Vent System Length To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system. Vent Piece 45° elbow 8" (20.0 cm) Round 2.5 ft (0.8 m) 90° elbow 5.0 ft (1.5 m) 10¾" (27.3 cm) 13 33.5 cm) 4⁵⁄₈" (11.7 cm) 7 20.2 cm) 30" (76.2 cm) 36" (91.4 cm) 42" (106.7 cm) *28 71.9 cm) min. 42⁵⁄₈" (108.3 cm) max. 24" (60.8 cm) 20½" (52.0 cm) **24⁵⁄₈" (62.5 cm) min. 38¾" (98.4 cm) max. 5" (12.7 cm) 19 50.0 cm) *For non-vented (recirculating) installations **For vented installations Maximum equivalent vent length is 35 ft (10.7 m). Because Whirlpool Corporation policy includes a continuous commitment to improve our Dimensions are for planning purposes only. For complete details, see Installation products, we reserve the right to change materials and specifications without notice. Instructions packed with product. Specifications subject to change without notice. Page 1 of 2 Ref. W10274311A 10/14/09

  • 1
  • 2

PRODUCT MODEL NUMBERS
ELECTRICAL REQUIREMENTS
A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is required.
VENTING METHODS
This canopy hood is factory set for venting through the roof or wall.
A 8" (20.0 cm) round vent system is needed for installation (not included).
The hood exhaust opening is 8" (20.0 cm) round.
NOTE:
Flexible vent is not recommended. Flexible vent creates back
pressure and air turbulence that greatly reduce performance.
Vent system can terminate either through the roof or wall. To vent through
a wall, a 90° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.
For Non-Vented (recirculating) Installations
If it is not possible to vent cooking fumes and vapors to the outside, the
hood can be used in the non-vented (recirculating) version, fitting a charcoal
filter and the deflector. Fumes and vapors are recycled through the top grille.
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet
(meters) for each vent piece used in the system.
30" (76.2 cm), 36" (91.4 cm) and 42" (106.7 cm) Wall-Mount
Canopy Range Hood
Because Whirlpool Corporation policy includes a continuous commitment to improve our
products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation
Instructions packed with product. Specifications subject to change without notice.
Ref. W10274311A
10/14/09
A. Roof cap
B. 8" (20.0 cm)
round vent
A. Wall cap
B. 8" (20.0 cm)
round vent
A. Deflector
B. 8" (20.0 cm)
round vent
A
A
B
B
B
A
Roof Venting
Non-vented
(recirculating)
Wall Venting
Example vent system
The following example falls within the maximum recommended vent length of
35 ft (10.7 m).
LOCATION REQUIREMENTS
Have a qualified technician install the range hood. It is the installer's
responsibility to comply with installation clearances specified on the
model/serial rating plate. The model/serial rating plate is located behind the left
filter on the rear wall of the vent hood.
Canopy hood location should be away from strong draft areas, such as
windows, doors and strong heating vents.
For Mobile Home Installations
The installation of this range hood must conform to the Manufactured Home
Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal
Standard for Mobile Home Construction and Safety, Title 24, HUD, Part 280) or
when such standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI
A225.1/NFPA 501A, or latest edition, or with local codes.
PRODUCT DIMENSIONS
*For non-vented (recirculating) installations
**For vented installations
Vent Piece
8" (20.0 cm) Round
45° elbow
2.5 ft (0.8 m)
90° elbow
5.0 ft (1.5 m)
Maximum equivalent vent length is 35 ft (10.7 m).
1 - 90° elbow
1 - wall cap
8 ft (2.4 m) straight
= 5.0 ft (1.5 m)
= 0.0 ft (0.0 m)
= 8.0 ft (2.4 m)
Length of system
= 13.0 ft (3.9 m)
90
elbow
6 ft (1.8 m)
2 ft
(0.6 m)
Wall cap
10¾" (27.3 cm)
13
³⁄₁₆
" (33.
5 cm)
4
⁵⁄₈
" (11.7 cm)
7
¹⁵⁄₁₆
" (20.2 cm)
*28
⁵⁄₁₆
" (71.9 cm) min.
42
⁵⁄₈
" (108.3 cm) max.
**24
⁵⁄₈
" (62.5 cm) min.
38
¾
" (98.4 cm) max.
24"
(60.8 cm)
20
½
"
(52.0 cm)
5"
(12.7 cm)
19
¹¹⁄₁₆
" (50.0 cm)
30" (76.2 cm)
36" (91.4 cm)
42" (106.7 cm)
JXW8030W
JXW8036W
JXW8042W
Page 1 of 2