Kenmore 31813 Owners Manual - Page 9

Temperature-Pressure, Relief, Valve

Page 9 highlights

Installation Instructions (cont'd) Temperature-Pressure Relief Valve _,WARNING At the time of manufacture this water heater was provided with a combination temperature-pressures relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, and the current edition of ANSI Z21.22, CSA 4.4 and the code requirements of ASME. If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4 by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials. The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 Ibsdsq. in.) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3412 equal BTU/Hr. rate.) Your local jurisdictional authority, while mandating the use of a temperature-pressure relief valve complying with ANSI Z21.22 • CSA 4.4 and ASME, may require a valve model different from the one furnished with the water heater. Compliance with such local requirements must be satisfied by the installer or end user of the water heater with a locally prescribed temperature-pressure relief valve installed in the designated opening in the water heater in place of the factory furnished valve. For safe operation of the water heater, the relief valve must not be removed from it's designated opening or plugged. The temperature-pressure relief valve must be installed directly into the fitting of the water heater designated for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet, or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve. No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6" air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. The Discharge Pipe: • Must not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restriction. • Must not be plugged or blocked. • Must be of material listed for hot water distribution. • Must be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe. • Must terminate at an adequate drain. • Mustnothaveanyvalvebotweenthereliefvalveandtank. _,WARNING The temperature-pressure relief valve must be manually operated at least once a year. Caution should be taken to ensure that (I) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately, close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one. TEMPERATURE-PRESSURE RELIEF VALVE DISCHARGE PIPE (Do not cap or plug) 6 ,f AIR GAP FLOOR DRAIN 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

Installation
Instructions
(cont'd)
Temperature-Pressure
Relief
Valve
_,WARNING
At the time of manufacture this water heater was
provided
with a combination
temperature-pressures
relief valve certi-
fied by a nationally recognized
testing
laboratory that main-
tains periodic inspection of production of listed equipment
or materials,
as
meeting the requirements for Relief Valves
and
Automatic
Gas Shutoff Devices for Hot Water
Supply
Systems,
and
the current
edition
of ANSI
Z21.22,
CSA 4.4
and
the
code requirements
of ASME. If replaced,
the
valve
must
meet
the
requirements
of local codes, but not less
than
a combination
temperature
and pressure
relief
valve
certified
as
meeting
the
requirements
for Relief Valves and
Automatic
Gas Shutoff
Devices
for
Hot
Water
Supply
Systems, ANSI
Z21.22 • CSA 4.4 by a nationally
recognized
testing
laboratory that
maintains
periodic
inspection of pro-
duction of listed equipment or materials.
The valve must be marked
with a maximum
set pressure
not to exceed
the
marked hydrostatic working pressure of
the
water
heater (150 Ibsdsq. in.) and a discharge capacity
not less than the water
heater input rate
as
shown on
the
model rating plate. (Electric heaters
-
watts divided by 1000
x 3412 equal BTU/Hr.
rate.)
Your local jurisdictional authority, while mandating the use
of a temperature-pressure
relief valve complying with ANSI
Z21.22
CSA 4.4 and ASME, may
require
a valve model dif-
ferent from the one furnished with the water
heater.
Compliance with such local
requirements
must
be satisfied
by the installer or
end
user of the water
heater with a locally
prescribed temperature-pressure
relief
valve installed in the
designated opening in the water
heater
in place of the facto-
ry
furnished valve.
For safe operation of the water
heater,
the
relief
valve
must
not
be
removed
from it's designated opening or plugged.
The
temperature-pressure
relief
valve must
be installed
directly into the fitting of the water
heater
designated for
the
relief
valve. Position the valve downward
and provide
tubing so that any discharge will
exit
only within
6 inches
above,
or at any distance below the structural floor. Be cer-
tain that
no
contact
is made with
any live
electrical
part.
The discharge opening
must
not
be blocked or
reduced
in
size under
any
circumstances. Excessive length, over 30 feet,
or use of
more
than four
elbows
can cause
restriction
and
reduce
the discharge capacity of the valve.
No valve or other obstruction is to be placed between the
relief
valve
and
the
tank.
Do not connect tubing directly to
discharge drain unless a 6" air gap is provided. To prevent
bodily injury,
hazard
to life, or property damage, the
relief
valve
must
be allowed
to discharge
water
in quantities
should circumstances demand.
If the discharge pipe is not
connected to a drain or other suitable
means,
the water flow
may
cause property damage.
The Discharge Pipe:
Must
not
be smaller in size than the outlet pipe size of
the valve, or
have
any
reducing
couplings or other
restriction.
Must
not
be plugged or blocked.
Must be of
material
listed for
hot
water distribution.
Must be installed
so as to allow
complete
drainage
of
both the temperature-pressure
relief
valve, and the dis-
charge pipe.
Must terminate
at an adequate drain.
Mustnothaveanyvalvebotweenthereliefvalveandtank.
_,WARNING
The
temperature-pressure
relief valve must be manually
operated
at least once a year. Caution
should be taken to
ensure that (I)
no one is in front
of or around the outlet
of the
temperature-pressure
relief
valve discharge
line,
and (2) the water
manually
discharged will not cause any
bodily injury or property
damage because the water
may
be extremely
hot.
If after manually
operating
the valve, it fails to complete-
ly reset
and continues
to
release
water,
immediately,
close the cold water
inlet to the water
heater, follow
the
draining
instructions,
and replace
the temperature-pres-
sure
relief
valve with
a new one.
TEMPERATURE-PRESSURE
RELIEF VALVE
DISCHARGE
PIPE
(Do not cap
or plug)
6 ,f
AIR
GAP
FLOOR
DRAIN
9