LG ARUN096DT2 Service Manual - Page 15
Outdoor Unit460v, Arun173dt2, Arun192dt2, Arun211dt2, Arun230dt2, Arun250dt2, Arun270dt2, Arun290dt2
View all LG ARUN096DT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 15 highlights
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes L4 L5 L3 L2 D L7 H L1 L6 160(6.4) W 60(2.4) D L8 Notes: 1. Height of walls in case of pattern1: Front side:1500mm, Suction side:500mm 2. If the above wall heights are exceeded, then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the following figure. 3. When installing the units, the most appropriate pattern should be selected from those shown. In order to obtain the best fit in the space available, always bear in mind the need to leave enough room for a person to pass between units and wall and for the air to circulate freely. Your layout should take into account the possibility of short circuits. 4. The Units should be installed to leave sufficient space in front for the on site refrigerant piping work to be carried out comfortably. 250mm or more 250mm or more 900mm or more Front side 250mm or more Outdoor Unit(460V) ARUN173DT2 ARUN192DT2 ARUN211DT2 ARUN230DT2 ARUN250DT2 ARUN270DT2 ARUN290DT2 ARUN310DT2 W mm(inch) H mm(inch) D mm(inch) L1 mm(inch) L2 mm(inch) L3 mm(inch) L4 mm(inch) L5 mm(inch) L6 mm(inch) L7 mm(inch) L8 mm(inch) 1280(50.4) 1607(63.3) 730(28.7) 1427(56.1) 692(27.2) 670(26.3) 900(35.4) 10(0.4) 704(27.7) 99(3.9) 82(3.2) - 15 - 1500mm h2 Front side Suction side 500mm h1 Dimensions LGE Internal Use Only 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lge.com/airconditioner CHASSIS CODE: UW