Connecting Electric Dryers

Page 21 highlights

6 Check all pipe connections (both internal and external) for gas leaks with a noncorrosive leak-detection fluid. 7 Proceed to Venting the Dryer. a c b d a 3/8" NPT gas Connection b AGA/CSA-Certified Stainless Steel Flexible Connector c 1/8" NPT Pipe Plug d Gas Supply Shutoff Valve High-Altitude Installations The BTU rating of this dryer is AGA-certified for elevations below 10,000 feet. If your gas dryer is being installed at an elevation above 10,000 feet, it must be derated by a qualified technician or gas supplier. Connecting Electric Dryers WARNING • To reduce the risk of fire or explosion, electric shock, property damage, injury to persons, or death when using this appliance, fulfill the following requirements. Electrical Requirements for Electric Models WARNING • The wiring and grounding must conform to the latest edition of the National Electrical Code, ANSI/NFPA 70 and all applicable local regulations. Please contact a qualified electrician to check your home's wiring and fuses to ensure that your home has adequate electrical power to operate the appliance. • This appliance must be connected to a grounded metal, permanent wiring system, or an INSTALLATION 21 equipment-grounding conductor must be run with the circuit conductors and connected to the equipment-grounding terminal or lead on the appliance. • The appliance has its own terminal block that must be connected to a separate 240 VAC, 60Hertz, single-phase circuit, fused at 30 amperes. (The circuit must be fused on both sides of the line.) ELECTRICAL SERVICE FOR THE APPLIANCE SHOULD BE OF THE MAXIMUM RATE VOLTAGE LISTED ON THE NAMEPLATE. DO NOT CONNECT THE APPLIANCE TO 110-, 115-, OR 120-VOLT CIRCUIT. • If the branch circuit to appliance is 15 ft. (4.5 m) or less in length, use UL (Underwriters Laboratories) listed No.-10 AWG wire (copper wire only), or as required by local codes. If over 15 ft. (4.5 m), use UL-listed No.-8 AWG wire (copper wire only), or as required by local codes. Allow sufficient slack in wiring so the appliance can be moved from its normal location when necessary. • The power cord (pigtail) connection between the wall receptacle and the appliance terminal block IS NOT supplied with the appliance. Type of pigtail and gauge of wire must conform to local codes and with instructions on the following pages. • Do not modify the plug and internal wire provided with the appliance. • The appliance should be connected to a 4-hole outlet. • If the plug does not fit the outlet, a proper outlet will need to be installed by a qualified electrician. • Connect the power cord to the terminal block. Each colored wire should be connected to the same color screw. Wire color indicated in manual is connected to the same color screw in the block. • Grounding through the neutral conductor is prohibited for: (1) new branch-circuit installations and (2) areas where local codes prohibit grounding through the neutral conductor. • This appliance is supplied with the neutral wire grounded. This white ground wire MUST BE MOVED to the neutral terminal when a 4-wire cord is to be used, or where grounding through the neutral conductor is prohibited. ENGLISH

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

21
INSTALLATION
ENGLISH
6
Check all pipe connections (both internal and
external) for gas leaks with a noncorrosive
leak-detection fluid.
7
Proceed to Venting the Dryer.
a
3/8” NPT gas Connection
b
AGA/CSA-Certified Stainless Steel Flexible
Connector
c
1/8” NPT Pipe Plug
d
Gas Supply Shutoff Valve
High-Altitude Installations
The BTU rating of this dryer is AGA-certified for
elevations below 10,000 feet.
If your gas dryer is being installed at an elevation
above 10,000 feet, it must be derated by a
qualified technician or gas supplier.
Connecting Electric Dryers
WARNING
To reduce the risk of fire or explosion, electric
shock, property damage, injury to persons, or
death when using this appliance, fulfill the
following requirements.
Electrical Requirements for Electric
Models
WARNING
The wiring and grounding must conform to the
latest edition of the National Electrical Code,
ANSI/NFPA 70 and all applicable local
regulations. Please contact a qualified electrician
to check your home’s wiring and fuses to ensure
that your home has adequate electrical power to
operate the appliance.
This appliance must be connected to a grounded
metal, permanent wiring system, or an
equipment-grounding conductor must be run
with the circuit conductors and connected to the
equipment-grounding terminal or lead on the
appliance.
The appliance has its own terminal block that
must be connected to a separate 240 VAC, 60-
Hertz, single-phase circuit, fused at 30 amperes.
(The circuit must be fused on both sides of the
line.) ELECTRICAL SERVICE FOR THE APPLIANCE
SHOULD BE OF THE MAXIMUM RATE VOLTAGE
LISTED ON THE NAMEPLATE. DO NOT CONNECT
THE APPLIANCE TO 110-, 115-, OR 120-VOLT
CIRCUIT.
If the branch circuit to appliance is 15 ft. (4.5 m)
or less in length, use UL (Underwriters
Laboratories) listed No.-10 AWG wire (copper
wire only), or as required by local codes. If over
15 ft. (4.5 m), use UL-listed No.-8 AWG wire
(copper wire only), or as required by local codes.
Allow sufficient slack in wiring so the appliance
can be moved from its normal location when
necessary.
The power cord (pigtail) connection between the
wall receptacle and the appliance terminal block
IS NOT supplied with the appliance. Type of
pigtail and gauge of wire must conform to local
codes and with instructions on the following
pages.
Do not modify the plug and internal wire
provided with the appliance.
The appliance should be connected to a 4-hole
outlet.
If the plug does not fit the outlet, a proper outlet
will need to be installed by a qualified electrician.
Connect the power cord to the terminal block.
Each colored wire should be connected to the
same color screw. Wire color indicated in manual
is connected to the same color screw in the
block.
Grounding through the neutral conductor is
prohibited for: (1) new branch-circuit
installations and (2) areas where local codes
prohibit grounding through the neutral
conductor.
This appliance is supplied with the neutral wire
grounded. This white ground wire MUST BE
MOVED to the neutral terminal when a 4-wire
cord is to be used, or where grounding through
the neutral conductor is prohibited.
a
b
c
d