LG LA140CE Owners Manual - Page 28

Troubleshooting

Page 28 highlights

Maintenance and Service Troubleshooting The air conditioner may be operating abnormally when: Problem Possible Causes What To Do Air conditioner does not start Air conditioner does not cool as it should Air conditioner freezing up s The air conditioner is unplugged. s The fuse is blown/circuit breaker is tripped. s Power failure. s Airflow is restricted. s The thermostat may not be set high enough. s The air filter is dirty. s The room may have been hot. s Cold air is escaping. s Cooling coils have iced up. s Ice blocks the air flow and stops the air conditioner from cooling the room. • Make sure the air conditioner plug is pushed completely into the outlet. • Check the house fuse/circuit breaker box and replace the fuse or reset the breaker. • If power failure occurs, turn the mode control to Off. When power is restored, wait 3 minutes to restart the air conditioner to prevent tripping of the compressor overload. • Make sure there are no curtains, blinds, or furniture blocking the front of the air conditioner. • Turn the knob to a higher number. The highest setting provides maximum cooling. • Clean the filter at least every 2 weeks. See the care and Maintenance section. • When the air conditioner is first turned on, you need to allow time for the room to cool down. • Check for open furnace floor registers and cold air returns. • See Air Conditioner Freezing Up below. • Set the mode control at High Fan or High Cool with thermostat at 1 or 2. * You can refer to the Energy Star program in detail at www.energystar.gov. 28 Room Air Conditioner

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

28
Room Air Conditioner
Maintenance and Service
Troubleshooting
The air conditioner may be operating abnormally when:
Problem
The air conditioner is
unplugged.
The fuse is blown/circuit
breaker is tripped.
Power failure.
Airflow is restricted.
The thermostat may not be
set high enough.
The air filter is dirty.
The room may have been
hot.
Cold air is escaping.
Cooling coils have iced up.
Ice blocks the air flow and
stops the air conditioner from
cooling the room.
Air
conditioner
does not start
Air
conditioner
does not cool
as it should
Air
conditioner
freezing up
• Make sure the air conditioner plug is
pushed completely into the outlet.
• Check the house fuse/circuit breaker
box and replace the fuse or reset the
breaker.
• If power failure occurs, turn the mode
control to Off.
When power is restored, wait 3
minutes to restart the air conditioner
to prevent tripping of the compressor
overload.
• Make sure there are no curtains,
blinds, or furniture blocking the front of
the air conditioner.
• Turn the knob to a higher number.
The highest setting provides
maximum cooling.
• Clean the filter at least every 2 weeks.
See the care and Maintenance
section.
• When the air conditioner is first turned
on, you need to allow time for the
room to cool down.
• Check for open furnace floor registers
and cold air returns.
• See Air Conditioner Freezing Up
below.
• Set the mode control at High Fan or
High Cool with thermostat at 1 or 2.
What To Do
Possible Causes
* You can refer to the Energy Star program in detail at www.energystar.gov.