LG LCN340CP Service Manual - Page 44

Troubleshooting CH32, CH33

Page 44 highlights

Troubleshooting Guide Troubleshooting CH32, CH33 Display code 32 Title D-pipe (Inverter) temp. high (105°C(221°F) ) D-pipe (Constant) 33 temp. high (105°C(221°F) ) Cause of error • Discharge sensor (Inverter) temp. high • Discharge sensor (Cons.) temp. high Check point & Normal condition • Check the discharge pipe sensor for INV. • Check the install condition for over load. • Check the leakage of refrigerant. • Check the SVC V/V open. • Check the discharge pipe sensor for Cons. • Check the install condition for over load. • Check the leakage of refrigerant. • Check the SVC V/V open. 105°C (221°F) 95°C (203°F) 90°C (194°F) COMP OFF LEV OPEN/Hz down LEV OPEN/Hz down NORMAL Inverter Check Point • CH 32 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. 105°C (221°F) 90°C (194°F) 80°C (176°F) COMP OFF LEV OPEN LEV OPEN NORMAL Constant • CH 33 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. 4. Check the constant compressor. (same with CH21) 44 Ceiling Cassette Air Conditioner

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61

44
Ceiling Cassette Air Conditioner
Troubleshooting Guide
Troubleshooting CH32, CH33
32
33
D-pipe (Inverter)
temp. high
(105
°
C(221
°
F)
)
D-pipe (Constant)
temp. high
(105
°
C(221
°
F)
)
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
Check the discharge pipe sensor for INV.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Check the discharge pipe sensor for Cons.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
CH 32
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
CH 33
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
4. Check the constant compressor. (same with CH21)
90
°
C
(194
°
F)
80
°
C
(176
°
F)
95
°
C
(203
°
F)
Inverter
Constant
105
°
C
(221
°
F)
105
°
C
(221
°
F)
COMP OFF
COMP OFF
LEV OPEN
LEV OPEN
NORMAL
NORMAL
LEV OPEN/Hz down
LEV OPEN/Hz down
90
°
C
(194
°
F)