LG LMN120HE Service Manual - Page 16
Select the best location
View all LG LMN120HE manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
Installation Select the best location Indoor unit 1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit. 3. Make sure that condensation drainage can be conve- niently routed away. 4. Do not install near a doorway. 5. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. 6. Use a stud finder to locate studs to prevent unneces- sary damage to the wall. CAUTION: Install the indoor unit on the wall where the height from the floors more than 2.3m(7.5ft). Outdoor unit 1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. 2. Ensure that the spaces indicated by arrows around front, back and side of the unit. 3. Do not place animals and plants in the path of the warm air. 4. Take the air conditioner weight into account and select a place where noise and vibration are minimum. 5. Select a place so that the warm air and sound from the air conditioner do not disturb neighbors. Rooftop Installations: If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting. More than 5cm (2.0 inch) More than 5cm (2.0 inch) More than 2.3m (90.6 inch) More than 50cm More than 5cm (2.0 inch) More than 10cm More than 2m More than 50cm more than 20cm (7.9 inch) more than 20cm (7.9 inch) more than 70cm (27.6 inch) 16 Multi type Air Conditioner