3: Configuring Multi-Master DF1 As a member of Lantronix's Industrial Automation Protocol (IAP) suite of products, the Multi-Master DF1 firmware can be loaded into any of the IAP family of products. DF1 is a serial communications protocol used by most Rockwell Automation's (Allen Bradley) Programmable Controllers. Lantronix provides an intelligent Ethernet-enabling technology for the most commonly used Industrial Serial Protocols, including DF1. You must configure certain parameters before the IAP Device Server can be used on a network. Accessing the DF1 Setup Mode over Telnet You can use a Telnet connection to configure the unit over the network. 1. Access the Multi-Master DF1 Setup Mode screen via Telnet to port 9999 and the unit's IP address. 2. Within 5 seconds, press Enter. The Setup Mode screen displays. Serial Number 6410064 MAC address 00:20:4A:64:27:50 Software version V01.0 (010321) Press Enter to go into Setup Mode Model: IAP Device Server Plus+! (Firmware Code:AD) Multi-Master DF1 1) TCP/IP Network Settings: Ethernet Autodetect IP addr 172.20.198.72, no gateway set, netmask 255.255.255.000 Telnet config password set 2) DF1 Settings: Protocol DF1 Full-Duplex Serial Interface ......... RS232 19200,8,N,1 Check Sum CRC (16-bit) Redirector Sockets ....... 2 (port:03001) Raw Tunneled Sockets ..... 2 (port:10001) 3) MSG Block Remote IP Routing Table: (* None Defined *) R)eset all to factory Defaults S)ave all to EEPROM and Quit Q)uit without saving Select Command or parameter set (1,2,R,S,Q) to change: Note: If you just reflashed the IAP Device Server with Multi-Master DF1 firmware, we recommend that you reset all of the parameters to the factory defaults. 3. To reset the parameters to the factory defaults, type R on the command line. The default parameters display. Multi-Master DF1 Protocol User Guide 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

Multi-Master DF1 Protocol User Guide
7
3:
Configuring Multi-Master DF1
As a member of Lantronix’s Industrial Automation Protocol (IAP) suite of products,
the Multi-Master DF1 firmware can be loaded into any of the IAP family of products.
DF1 is a serial communications protocol used by most Rockwell Automation’s (Allen
Bradley) Programmable Controllers. Lantronix provides an intelligent
Ethernet-enabling technology for the most commonly used Industrial Serial Protocols,
including DF1.
You must configure certain parameters before the IAP Device Server can be used on
a network.
Accessing the DF1 Setup Mode over Telnet
You can use a Telnet connection to configure the unit over the network.
1.
Access the Multi-Master DF1 Setup Mode screen via Telnet to port 9999 and the
unit’s IP address.
2.
Within 5 seconds, press
Enter
. The Setup Mode screen displays.
Serial Number 6410064 MAC address 00:20:4A:64:27:50
Software version V01.0 (010321)
Press Enter to go into Setup Mode
Model: IAP Device Server Plus+!
(Firmware Code:AD)
Multi-Master DF1
1) TCP/IP Network Settings:
Ethernet Autodetect
IP addr 172.20.198.72, no gateway set, netmask
255.255.255.000
Telnet config password set
2) DF1 Settings:
Protocol
.................
DF1 Full-Duplex
Serial Interface
.........
RS232 19200,8,N,1
Check Sum
................
CRC (16-bit)
Redirector Sockets
.......
2 (port:03001)
Raw Tunneled Sockets
.....
2 (port:10001)
3) MSG Block Remote IP Routing Table:
(* None Defined *)
R)eset all to factory Defaults
S)ave all to EEPROM and Quit
Q)uit without saving
Select Command or parameter set (1,2,R,S,Q) to change:
Note:
If you just reflashed the IAP Device Server with Multi-Master DF1
firmware, we recommend that you reset all of the parameters to the
factory defaults.
3.
To reset the parameters to the factory defaults, type
R
on the command line. The
default parameters display.