LiftMaster LA412UL LA412UL Wiring Diagram - Page 1

LiftMaster LA412UL Manual

Page 1 highlights

WIRING DIAGRAM Model LA412UL CONTROLS To reduce the risk of INJURY or DEATH: • DISCONNECT power and battery BEFORE installing or servicing operator. • Replace ONLY with fuse of same type and rating. • To be compliant with UL325 and industry safety guidelines, qualified monitored external entrapment protection devices such as photoelectric sensors or edge sensors are required to be installed with this operator at each entrapment zone. Use ONLY LiftMaster approved entrapment protection devices (refer to the accessory page of manual). • See manual prior to servicing regarding maintenance and required safety testing. Diagnostic Codes TO VIEW THE CODES: Press and hold STOP... ...then press and hold CLOSE... ...then press and hold OPEN until "Er" shows. The operator will show the code sequence number followed by the code number: A SECOND LATER.... CODE SEQUENCE NUMBER The first number shown is the most recent code (example: "01"). The display will show the sequence of codes that occurred starting with "01" and going up to code "20". CODE COLOR KEY: LiftMaster System Installed System Informational CODE NUMBER The second number shown after the code sequence number is the code itself (31-99, example" "31"). External Entrapment Protection Inherent Entrapment Protection CODE MEANING SOLUTION Main control board has experienced an internal Disconnect all power, wait 15 seconds, then 31 failure. reconnect power (reboot). If issue continues, replace main control board. 32 Linear Drive Disengaged (Arm 1) 33 Linear Drive Disengaged (Arm 2) Disengage then re-engage arm. Check wiring and connections. 35 Max-Run-Time Exceeded Error Check for an obstruction, then reprogram the limits. Product ID Error 36 Was the control board just replaced? If so, erase limits, enter limit setup mode and set limits. If not, disconnect all power, wait 15 seconds, then reconnect power before changing product ID harness. Product ID Failure 37 Unplug product ID harness then plug back in. Disconnect all power, wait 15 seconds, then reconnect power before replacing product ID harness. 38 Hard Stop Limit (Arm 1) 39 Hard Stop Limit (Arm 2) Limit may be set too tightly against a nonresilient hard stop (re-adjust limit). Operator may be at end of travel (re-adjust mounting). Battery overvoltage 40 Too much voltage on the battery. Check harness. Make sure there is NOT a 24V battery on a 12V system. Battery overcurrent 41 Possible short of the battery charge harness. Check harness. Make sure you do NOT have a 12V battery on a 24V system. No battery at boot up 42 Check battery connections and installation. Replace batteries if depleted to less than 20V on a 24V system or less than 10V on a 12V system. Make sure there is NOT a single 12V battery on a 24V system. 43 Exit Loop Error 44 Shadow Loop Error Interrupt Loop Error 45 Failure or missing loop (SHORT or OPEN LiftMaster Plug-in Loop Detector only) Check loop wiring throughout connection. May be a short in the loop, or an open connection in the loop. 46 Wireless edge battery low Replace batteries in wireless edge. 51 Pass-point not detected (Arm 1) 52 Pass-point not detected (Arm 2) Check yellow pass-point wiring. If limits are not accurate, reprogram. Brownout occurred 53 AC/DC board supply dipped below allowable level. Review power supply and wiring. If rebooting, ensure enough time for discharge of power to force a fresh boot. Wireless Second Operator Communication Error Check the second operator for power. If OFF, 54 restore power and try to run the system. If powered, deactivate the wireless feature and then reprogram the second operator. Minimum number of monitored entrapment Review monitored entrapment protection device protection devices not installed. connections. This swing gate operator will 60 operate only after installation of a minimum of one external safety device in either the open or close direction. 61 CLOSE EYE/INTERRUPT held more than 3 minutes Check wired input on main control board; check for alignment or obstruction. 62 CLOSE EDGE held more than 3 minutes 63 OPEN EYE/EDGE held more than 3 minutes 64 CLOSE EYE/INTERRUPT held more than 3 minutes Check wired input on expansion board; check for alignment or obstruction. 65 CLOSE EYE/EDGE held more than 3 minutes 66 OPEN EYE/EDGE held more than 3 minutes 67 Wireless edge triggered more than 3 minutes Check wired input for wiring issue or obstruction. 68 Wireless edge loss of monitoring Check wireless edge inputs. Wireless edge triggered 69 IF an obstruction occurred, no action required. If an obstruction did NOT occur, check inputs and wiring. 70 CLOSE EYE/INTERRUPT triggered, causing reversal, preventing close, or resetting TTC 71 CLOSE EDGE triggered, causing reversal, preventing close, or canceling TTC IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on main control board. 72 OPEN EYE/EDGE triggered, causing reversal or preventing opening 73 CLOSE EYE/INTERRUPT triggered, causing reversal, preventing close, or resetting TTC IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, 74 CLOSE EYE/EDGE triggered, causing reversal and preventing close or canceling TTC inputs, and wiring on expansion board. 75 OPEN EYE/EDGE triggered, causing reversal or preventing opening 80 Close input (EYE/EDGE) communication fault from other operator Check inputs and communication method between operators, either wired bus or radio. Open input (EYE/EDGE) communication fault Ensure operator is powered. May have to erase 81 from other operator the wireless communication and reprogram the two operators. 82 Close input (EYE/EDGE) communication fault (expansion board) Check the connections between the main board and the expansion board. 83 Open input (EYE/EDGE) communication fault (expansion board) Non-monitored device detected on the wireless Non-monitored contact closure devices are not 84 safety system supported. Make sure connected devices are monitored. Check edges for proper orientation and resistive end cap connection. 91 Force Reversal (Operator 1) Force Reversal (Operator 2) 92 Check for obstruction. If no obstruction, check that the mechanical assembly is engaged and free to move. See section on Limit and Force Adjustment, and Obstruction Test in the manual. 93 RPM / STALL Reversal (Operator 1) RPM / STALL Reversal (Operator 2) 94 Check for obstruction. If no obstruction, check the operator wiring and that the mechanical assembly is engaged and free to move. Replace APE assembly. 99 Normal Operation No action required COAXIAL CABLE ANTENNA Control DIAGNOSTICS Board DIAGNOSTICS DIAGNOSTICS DIAGNOSTICS DIAGNOSTICS DIAGNOSTICS (see below) LOOPS Control Station Fire Department Access Control Device Edge Sensor for close cycle Photoelectric Sensors for close cycle Exit Loop Shadow Loop Interrupt Loop Photoelectric Sensors for open cycle Edge Sensor for open cycle OR ENTRAPMENT PROTECTION (see below) LOCKS Maglock (Optional) (not provided) OR Solenoid Lock (Optional) (not provided) ACCESSORY POWER 24 Vdc switched PLUG-IN LOOP DETECTOR Model LOOPDETLM Expansion Board POWER 24 Vdc always on Photoelectric Sensors for open or close cycle Photoelectric Sensor for open or close cycle Edge Sensor for open or close cycle TO MAIN BOARD TO MAIN BOARD ENTRAPMENT CONTROLS PROTECTION (Optional Accessory) POWER SHADOW INTERUPT EXIT TO MAIN TBOOAMRAIDN BOARD POPWOEWRER 11 EYEEYE ONOLNYLY 22 EYEEY/ E/ EDEGDEGE 3 3 EEDEYGEDEEYG/ EE/ COCMOM SBSCBC OPONPN CLCSLS STSPTP COCMOM CCLOLOPOPOESESNENE SHADOW INTERUPT EXIT SHADOW INTERUPT EXIT Wireless Edge Kit Model LMWEPKOIWTEUR 1 EYE ONLY 2 EYE/ EDGE 3 EYE/ EDGE COM OPEN CLOSE POWER SBC OPN TO MAIN BOARD OPEN CLOSE 1 EYE ONLY 2 EYE/ EDGE 1 3 EYE/ OENYLEYEDGE 2 EEDYGEEC/ OM 3 EYE/ EDGE COMSBC SBCOPN OPN CLS CLS STP STPCOM COM Jumper N.C. Control Stations OR Photoelectric Sensor for open or close cycle Edge Sensor for open or close cycle OR LOOPS TO MAIN BOARD CLS AUXILIARY RELAYS STP COM Interrupt Loop OPEN CLOSE 1 EYE ONLY 2 3 EYE/ 1EDGE EYE/ EDGE OFCF OM 2 OFF OFF OFF SBC OFFOPN ON CLS OFF ON STP ONCOM OFF SWITCH SETTINGS 3 RELAY 1 RELAY 2 OFF Relay always off Relay always off ON Energizes at open limit Energizes at open limit OFF Energizes when not at DIAGNOSTICS Energizes when not at close limit close limit ON Energizes when motor Energizes when motor is is on on OFF Energizes 3 seconds Energizes 3 seconds prior prior/during gate motion and during gate motion RED/GREEN LIGHT FUNCTIONALITY Red light wired to AUX RELAY 1. Green light wired to AUX RELAY 2. GATE STATE AUX RELAY 1 SWITCHES 1 OFF 2 OFF 3 OFF CLOSED Red light OFF* AUX RELAY 2 SWITCHES 1 ON 2 ON 3 ON Green light OFF OPENING Red light ON/FLASH Green light OFF OPEN CLOSING Red light OFF Red light ON/FLASH Green light ON Green light OFF SHADOW INTERUPT EXIT Shadow Loop DIAGNOSOTINCS ON OFF Energizes with AC or solar power Energizes with battery power ON OFF ON Energizes when gate is Energizes when gate is tampered with tampered with ON ON ON LEDs will blink cycle count Not used Defined Mid Stop Undefined Mid Stop Timer more than 5 seconds n/a Red light ON Red light OFF n/a Green light OFF Green light ON Exit Loop Timer less than 5 seconds Red light ON/FLASH * For red light ON when gate is closed, set switch 1 on AUX RELAY 1 to ON Green light OFF CONTROL BOARD CONTROL BOARD White White Blue Normally Closed Common Normally Open 4321 Normally Closed Common Normally Open J15 Plug PRIMARY OPERATOR SECONDARY OPERATOR PRODUCT ID ALARM Red Black Earth Ground Rod 20A Battery 12V 7AH Red Battery 12V 7AH Black Optional 33AH Battery Configuration For 33AH battery configuration please use harness K94-37236. The Large Solar Control Box (XLSOLARCONTUL) can be used with either 7AH or 33AH batteries. Diode Solar Panels 10W minimum - 30W maximum, wired in parallel Black 10W 12V Red Black 10W 12V Red Black 10W 12V Red RESET BUTTON LiftMaster.com © 2018, LiftMaster All Rights Reserved 01-39240-11

  • 1
  • 2

Press and hold
STOP...
...then press and
hold CLOSE...
...then press and hold OPEN
until "Er" shows.
CODE SEQUENCE NUMBER
The first number shown is the most
recent code (example: “01”). The
display will show the sequence of
codes that occurred starting with “01”
and going up to code “20”.
CODE NUMBER
The second number shown after the code
sequence number is the code itself
(31-99, example” “31”).
A SECOND LATER
....
The operator will show the code sequence number followed by the code number:
Diagnostic Codes
TO VIEW THE CODES:
LiftMaster.com
© 2018, LiftMaster
All Rights Reserved
01-39240-11
LiftMaster System
Installed System
Informational
External Entrapment Protection
Inherent Entrapment Protection
WIRING DIAGRAM
Model LA412UL
CODE COLOR KEY:
DIAGNOSTICS
EYE
ONLY
EYE/
EDGE
EYE/
EDGE
COM
OPEN
CLOSE
SBC
OPN
CLS
STP
COM
20A
10W 12V
10W 12V
10W 12V
4321
Photoelectric Sensors
for close cycle
Edge Sensor
for close cycle
OR
Edge Sensor
for open cycle
Photoelectric Sensors
for open cycle
ENTRAPMENT
PROTECTION
LOCKS
ACCESSORY
POWER
ENTRAPMENT
PROTECTION
CONTROLS
OR
24 Vdc
switched
OR
OR
Expansion Board
(Optional Accessory)
Maglock
(Optional)
(not provided)
Solenoid Lock
(Optional)
(not provided)
24 Vdc
always on
Photoelectric Sensors
for open or close cycle
Photoelectric Sensor
for open or close cycle
Edge Sensor
for open or close
cycle
Edge Sensor
for open or close
cycle
Photoelectric Sensor
for open or close cycle
Control Board
COAXIAL CABLE
ANTENNA
(see below)
PLUG-IN LOOP DETECTOR
Model LOOPDETLM
(see below)
AUXILIARY RELAYS
LOOPS
Shadow Loop
Exit Loop
Interrupt Loop
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
SWITCH SETTINGS
1
2
3
RELAY 1
RELAY 2
OFF
Relay always off
Relay always off
OFF
OFF
OFF
OFF
ON
Energizes at open limit
Energizes at open limit
OFF
OFF
ON
Energizes when not at
close limit
Energizes when not at
close limit
OFF
ON
ON
Energizes when motor
is on
Energizes when motor is
on
ON
OFF
OFF
Energizes 3 seconds
prior/during gate motion
Energizes 3 seconds prior
and during gate motion
ON
OFF
ON
Energizes with AC or
solar power
Energizes with battery
power
ON
ON
OFF
Energizes when gate is
tampered with
Energizes when gate is
tampered with
ON
ON
ON
LEDs will blink
cycle count
Not used
RED
/
GREEN
LIGHT FUNCTIONALITY
1
2
3
Red light
wired to AUX RELAY 1.
Green light
wired to AUX RELAY 2.
AUX RELAY 1 SWITCHES
OFF
Red light OFF*
OFF
OFF
CLOSED
GATE STATE
AUX RELAY 2 SWITCHES
Green light OFF
1
2
3
ON
ON
ON
OPENING
OPEN
CLOSING
Defined Mid Stop
Undefined Mid
Stop
Timer more than
5 seconds
Timer less than
5 seconds
* For red light ON when gate is closed, set switch 1 on AUX RELAY 1 to ON
Red light ON/FLASH
Red light OFF
Red light ON/FLASH
n/a
Red light ON
Red light OFF
Red light ON/FLASH
Green light OFF
Green light ON
Green light OFF
Green light OFF
n/a
Green light OFF
Green light ON
Battery
12V 7AH
Battery
12V 7AH
Solar Panels
10W minimum - 30W maximum, wired in parallel
Black
Red
ALARM
CONTROL BOARD
Blue
PRODUCT
ID
White
White
RESET BUTTON
PRIMARY
OPERATOR
SECONDARY
OPERATOR
CONTROL BOARD
J15 Plug
Black
Black
Earth Ground Rod
Black
CONTROLS
LOOPS
Black
Red
Optional 33AH Battery Configuration
For 33AH battery configuration please use harness K94-37236.
The Large Solar Control Box (XLSOLARCONTUL) can be used with
either 7AH or 33AH batteries.
Red
Red
Red
Shadow Loop
Exit Loop
Interrupt Loop
Access
Control
Device
Control Station
Fire Department
Control Stations
Jumper
Diode
Wireless Edge Kit
Model LMWEKITU
N.C.
CODE
MEANING
SOLUTION
31
Main control board has experienced an internal
failure.
Disconnect all power, wait 15 seconds, then
reconnect power (reboot). If issue continues,
replace main control board.
32
Linear Drive Disengaged (Arm 1)
Disengage then re-engage arm. Check wiring and
connections.
33
Linear Drive Disengaged (Arm 2)
35
Max-Run-Time Exceeded Error
Check for an obstruction, then reprogram the
limits.
36
Product ID Error
Was the control board just replaced? If so, erase
limits, enter limit setup mode and set limits. If
not, disconnect all power, wait 15 seconds, then
reconnect power before changing product ID
harness.
37
Product ID Failure
Unplug product ID harness then plug back in.
Disconnect all power, wait 15 seconds, then
reconnect power before replacing product ID
harness.
38
Hard Stop Limit (Arm 1)
Limit may be set too tightly against a non-
resilient hard stop (re-adjust limit). Operator may
be at end of travel (re-adjust mounting).
39
Hard Stop Limit (Arm 2)
40
Battery overvoltage
Too much voltage on the battery. Check harness.
Make sure there is NOT a 24V battery on a 12V
system.
41
Battery overcurrent
Possible short of the battery charge harness.
Check harness. Make sure you do NOT have a
12V battery on a 24V system.
42
No battery at boot up
Check battery connections and installation.
Replace batteries if depleted to less than 20V on
a 24V system or less than 10V on a 12V system.
Make sure there is NOT a single 12V battery on a
24V system.
43
Exit Loop Error
Failure or missing loop (SHORT or OPEN -
LiftMaster Plug-in Loop Detector only) Check
loop wiring throughout connection. May be a
short in the loop, or an open connection in the
loop.
44
Shadow Loop Error
45
Interrupt Loop Error
46
Wireless edge battery low
Replace batteries in wireless edge.
51
Pass-point not detected (Arm 1)
Check yellow pass-point wiring. If limits are not
accurate, reprogram.
52
Pass-point not detected (Arm 2)
53
Brownout occurred
AC/DC board supply dipped below allowable
level. Review power supply and wiring. If
rebooting, ensure enough time for discharge of
power to force a fresh boot.
54
Wireless Second Operator Communication Error
Check the second operator for power. If OFF,
restore power and try to run the system. If
powered, deactivate the wireless feature and then
reprogram the second operator.
60
Minimum number of monitored entrapment
protection devices not installed.
Review monitored entrapment protection device
connections. This swing gate operator will
operate only after installation of a minimum of
one external safety device in either the open or
close direction.
61
CLOSE EYE/INTERRUPT held more than 3
minutes
Check wired input on main control board; check
for alignment or obstruction.
62
CLOSE EDGE held more than 3 minutes
63
OPEN EYE/EDGE held more than 3 minutes
64
CLOSE EYE/INTERRUPT held more than 3
minutes
Check wired input on expansion board; check for
alignment or obstruction.
65
CLOSE EYE/EDGE held more than 3 minutes
66
OPEN EYE/EDGE held more than 3 minutes
67
Wireless edge triggered more than 3 minutes
Check wired input for wiring issue or
obstruction.
68
Wireless edge loss of monitoring
Check wireless edge inputs.
69
Wireless edge triggered
IF an obstruction occurred, no action required. If
an obstruction did NOT occur, check inputs and
wiring.
70
CLOSE EYE/INTERRUPT triggered, causing
reversal, preventing close, or resetting TTC
IF an obstruction occurred, no action required. If
an obstruction did NOT occur, check alignment,
inputs, and wiring on main control board.
71
CLOSE EDGE triggered, causing reversal,
preventing close, or canceling TTC
72
OPEN EYE/EDGE triggered, causing reversal or
preventing opening
73
CLOSE EYE/INTERRUPT triggered, causing
reversal, preventing close, or resetting TTC
IF an obstruction occurred, no action required. If
an obstruction did NOT occur, check alignment,
inputs, and wiring on expansion board.
74
CLOSE EYE/EDGE triggered, causing reversal
and preventing close or canceling TTC
75
OPEN EYE/EDGE triggered, causing reversal or
preventing opening
80
Close input (EYE/EDGE) communication fault
from other operator
Check inputs and communication method
between operators, either wired bus or radio.
Ensure operator is powered. May have to erase
the wireless communication and reprogram the
two operators.
81
Open input (EYE/EDGE) communication fault
from other operator
82
Close input (EYE/EDGE) communication fault
(expansion board)
Check the connections between the main board
and the expansion board.
83
Open input (EYE/EDGE) communication fault
(expansion board)
84
Non-monitored device detected on the wireless
safety system
Non-monitored contact closure devices are not
supported. Make sure connected devices are
monitored. Check edges for proper orientation
and resistive end cap connection.
91
Force Reversal (Operator 1)
Check for obstruction. If no obstruction, check
that the mechanical assembly is engaged and
free to move. See section on Limit and Force
Adjustment, and Obstruction Test in the manual.
92
Force Reversal (Operator 2)
93
RPM / STALL Reversal (Operator 1)
Check for obstruction. If no obstruction, check
the operator wiring and that the mechanical
assembly is engaged and free to move. Replace
APE assembly.
94
RPM / STALL Reversal (Operator 2)
99
Normal Operation
No action required
To reduce the risk of INJURY or DEATH:
DISCONNECT power and battery BEFORE installing or servicing operator.
Replace ONLY with fuse of same type and rating.
To be compliant with UL325 and industry safety guidelines, qualified monitored
external entrapment protection devices such as photoelectric sensors or edge
sensors are required to be installed with this operator at each entrapment zone.
Use ONLY LiftMaster approved entrapment protection devices (refer to the
accessory page of manual).
See manual prior to servicing regarding maintenance and required safety testing.