LiftMaster RSL12U RSL12U Quick Start Guide Manual - Page 2

Wiring And Adjustments - gate opener

Page 2 highlights

WIRING AND ADJUSTMENTS Install Monitored Entrapment Protection Device This operator contains an inherent (internal) entrapment protection system and REQUIRES the addition of a LiftMaster external monitored entrapment protection system (non-contact photoelectric sensor or contact edge sensor) for EACH entrapment zone prior to gate movement. System includes three monitored entrapment protection inputs to cover all entrapment zones (and a total of six inputs with the optional expansion board). Refer to the manual for complete information. Connect Power Wiring and Earth Ground Rod Turn off the AC power from the main power source circuit breaker. Connect the earth ground rod, incoming power, battery, and plug-in transformer (see images below). Refer to your manual for complete wiring information. Photoelectric Sensor Reflector Plug-In Transformer CONTROL BOARD (back of outlet housing) Outlet Outlet J15 Plug Red Black Black Red Battery 12V 7AH Black Green White HOT GROUND NEUTRAL Outlet Housing Incoming Power PROGRAM REMOTE CONTROL 1. Press and release the LEARN button on the control board (operator will beep and green XMITTER LED will light). 2. Press the remote control button. The operator will time out of programming mode after 30 seconds. 10W 12V SOLAR PANEL (OPTIONAL) 10W minimum - 30W maximum, wired in parallel (requires K94-37236 battery harness) Check national and local codes for proper depth EARTH GROUND ROD Install the earth ground rod within 3 feet (.9 m) of the operator. Set the Limits and Force INITIAL LIMITS AND FORCE ADJUSTMENT 1. Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter limit setting mode. 2. Press and hold one of the MOVE GATE buttons to move the gate to the open or close limit. 3. Press and release the SET CLOSE or SET OPEN button depending on which limit is being set. 4. Press and hold one of the MOVE GATE button to move the gate to the other limit. 5. Press and release the SET CLOSE or SET OPEN button depending on which limit is being set. 6. Cycle the gate open and close. This automatically sets the force. When limits are set properly the operator will automatically exit limit setting mode. FINE TUNE THE FORCE The REVERSAL FORCE DIAL on the control board is used for fine tuning the force in cases where wind or environmental changes may affect the gate travel. Based on the length and weight of the gate it may be necessary to make additional force adjustments. The force setting should be high enough that the gate will not reverse by itself nor cause nuisance interruptions, but low enough to prevent serious injury to a person. The force setting is the same for both the open and close gate directions. 1. Open and close the gate with the test buttons. 2. If the gate stops or reverses before reaching the fully open or closed position, increase the force by turning the force control slightly clockwise. 3. Perform the "Obstruction Test" after every force setting adjustment. Perform the Obstruction Test 1. Open and close the gate with the test buttons, ensuring that the gate is stopping at the proper open and close limit positions. 2. Place a solid object between the open gate and a rigid structure. Ensure that the gate, the solid object, and the rigid structure can withstand the forces generated during this obstruction test. 3. Run the gate in the close direction. The gate should stop and reverse upon contact with the solid object. If the gate does not reverse off the solid object, reduce the force setting by turning the force control slightly counter-clockwise. The gate should have enough force to reach both the open and close limits, but MUST reverse after contact with a solid object. 4. Repeat the test for the open direction. Installation Checklist Check the following before leaving the site: Are all the wiring and connections tightly connected? Is the AC power on? If the operator is left running on battery only, it will drain the battery and will result in a service call. Check the battery and battery connections. Make sure there is one 12V battery. Replace battery if depleted to less than 11.5 V. Make sure the antenna is in place when using wireless dual gates or on-board transmitters. Operator will be intermittent at times without it. Remove the protective anti-scratch film from the photoelectric sensors. Leaving the film on can result in poor sensitivity as the film decays/yellows/peels. Confirm whether the site should be fail safe or secure and set the operator accordingly. Confirm operation of the following (if applicable): Entrapment protection devices Loops TES relay SOS/emergency transponders Check operation of ALL legacy receivers using the MAX transmitter Timer-to-Close setting Quick close setting Anti-tailgate setting

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6

10W 12V
CONTROL BOARD
Plug-In Transformer
(back of outlet housing)
J15 Plug
Outlet Housing
Photoelectric Sensor
Reflector
Outlet
Outlet
Incoming Power
HOT
NEUTRAL
GROUND
Battery
12V 7AH
Black
Green
White
Black
Black
Red
Red
WIRING AND ADJUSTMENTS
EARTH GROUND ROD
Install the earth ground
rod within 3 feet (.9 m)
of the operator.
Check national
and local codes
for proper depth
PROGRAM REMOTE CONTROL
1.
Press and release the LEARN
button on the control board
(operator will beep and green
XMITTER LED will light).
2.
Press the remote control button.
The operator will time out of
programming mode after 30 seconds.
FINE TUNE THE FORCE
The REVERSAL FORCE DIAL on the control board is used for fine
tuning the force in cases where wind or environmental changes
may affect the gate travel. Based on the length and weight of the
gate it may be necessary to make additional force adjustments.
The force setting should be high enough that the gate will not
reverse by itself nor cause nuisance interruptions, but low enough
to prevent serious injury to a person. The force setting is the same
for both the open and close gate directions.
1.
Open and close the gate with
the test buttons.
2.
If the gate stops or reverses
before reaching the fully open
or closed position, increase
the force by turning the force
control slightly clockwise.
3.
Perform the “Obstruction
Test” after every force setting
adjustment.
1.
Open and close the gate with the test buttons, ensuring that the
gate is stopping at the proper open and close limit positions.
2.
Place a solid object between the open gate and a rigid structure.
Ensure that the gate, the solid object, and the rigid structure can
withstand the forces generated during this obstruction test.
3.
Run the gate in the close direction. The gate should stop and
reverse upon contact with the solid object. If the gate does not
reverse off the solid object, reduce the force setting by turning
the force control slightly
counter-clockwise. The
gate should have enough
force to reach both the
open and close limits,
but MUST reverse after
contact with a solid
object.
4.
Repeat the test for the
open direction.
Are all the wiring and connections tightly connected?
Is the AC power on? If the operator is left running on battery only, it
will drain the battery and will result in a service call.
Check the battery and battery connections. Make sure there is one 12V
battery. Replace battery if depleted to less than 11.5 V.
Make sure the antenna is in place when using wireless dual gates or
on-board transmitters. Operator will be intermittent at times without it.
Remove the protective anti-scratch film from the photoelectric sensors.
Leaving the film on can result in poor sensitivity as the film
decays/yellows/peels.
Confirm whether the site should be fail safe or secure and set the
operator accordingly.
Confirm operation of the following (if applicable):
Entrapment protection devices
Loops
TES relay
SOS/emergency transponders
Check operation of ALL legacy receivers using the MAX transmitter
Timer-to-Close setting
Quick close setting
Anti-tailgate setting
Check the following before leaving the site:
Turn off the AC power from the main power source circuit breaker.
Connect the earth ground rod, incoming power, battery, and plug-in
transformer (see images below). Refer to your manual for complete
wiring information.
Install Monitored Entrapment Protection Device
Connect Power Wiring and Earth Ground Rod
Set the Limits and Force
Perform the Obstruction Test
Installation Checklist
INITIAL LIMITS AND FORCE
ADJUSTMENT
1.
Press and release the SET
OPEN and SET CLOSE
buttons simultaneously to
enter limit setting mode.
2.
Press and hold one of the
MOVE GATE buttons to
move the gate to the open or
close limit.
3.
Press and release the SET
CLOSE or SET OPEN button
depending on which limit is
being set.
4.
Press and hold one of the
MOVE GATE button to move
the gate to the other limit.
5.
Press and release the SET CLOSE or SET OPEN button depending
on which limit is being set.
6. Cycle the gate open and close. This automatically sets the force.
When limits are set properly the operator will automatically exit limit
setting mode.
This operator contains an inherent (internal) entrapment protection
system and REQUIRES the addition of a LiftMaster external
monitored entrapment protection system (non-contact photoelectric
sensor or contact edge sensor) for EACH entrapment zone prior to
gate movement.
System includes three monitored entrapment
protection inputs to cover all entrapment zones (and a total of six
inputs with the optional expansion board). Refer to the manual for
complete information.
SOLAR PANEL (OPTIONAL)
10W minimum - 30W maximum,
wired in parallel (requires K94-37236
battery harness)