Maytag MED5500FC Installation Guide - Page 15

Connect Inlet Hose, Steam Model Only

Page 15 highlights

Determine vent path: ■■Select route that will provide straightest and most direct path outdoors. ■■Plan installation to use fewest number of elbows and turns. ■■When using elbows or making turns, allow as much room as possible. ■■Bend vent gradually to avoid kinking. ■■Use as few 90° turns as possible. Determine vent length and elbows needed for best drying performance: ■■Use the following "Vent System Charts" to determine type of vent material and hood combinations acceptable to use. NOTE: Do not use vent runs longer than those specified in "Vent System Charts." Exhaust systems longer than those specified will: ■■Shorten life of dryer. ■■Reduce performance, resulting in longer drying times and increased energy usage. The "Vent System Charts" provide venting requirements that will help achieve best drying performance. Standard Vent System Chart Number of 90° elbows Type of vent Angled hoods 0 Rigid metal 64 ft. (20 m) 1 Rigid metal 54 ft. (16.5 m) 2 Rigid metal 44 ft. (13.4 m) 3 Rigid metal 35 ft. (10.7 m) 4 Rigid metal 27 ft. (8.2 m) Long Vent System Chart Number of 90° elbows Type of vent Angled hoods 0 Rigid metal 160 ft. (48.8 m) 1 Rigid metal 150 ft. (45.7 m) 2 Rigid metal 140 ft. (42.7 m) 3 Rigid metal 130 ft. (39.6 m) 4 Rigid metal 120 ft. (36.6 m) To determine if your model has a long vent system, refer to the type code located on the serial number plate in the inner door well. Example: An electric model would be DALV (Long Vent) - ELE - XXXXXXX-XXX. NOTE: For long vent systems, use of box/louvered hoods will improve venting, regardless of length. Install Vent System 1. Install exhaust hood 12" min. (305 mm) 12" min. (305 mm) Install exhaust hood and use caulking compound to seal exterior wall opening around exhaust hood. 2. Connect vent to exhaust hood Vent must fit over the exhaust hood. Secure vent to exhaust hood with 4" (102 mm) clamp. Run vent to dryer location using straightest path possible. Avoid 90° turns. Use clamps to seal all joints. Do not use duct tape, screws, or other fastening devices that extend into interior of vent to secure vent, because they can catch lint. CONNECT INLET HOSE (STEAM MODEL ONLY) For non-steam models, skip to "Connect Vent." The dryer must be connected to the cold water faucet using new inlet hoses (not supplied). Do not use old hoses. NOTE: Replace inlet hoses after 5 years of use to reduce the risk of hose failure. Record hose installation or replacement dates on the hoses for future reference. Periodically inspect and replace hoses if bulges, kinks, cuts, wear, or leaks are found. 1. Turn cold water off, remove hose, and replace rubber washer Turn cold water faucet off and remove washer inlet hose. Remove old rubber washer from inlet hose and replace with new rubber washer. 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26

15
The “Vent System Charts” provide venting requirements that
will help achieve best drying performance.
Determine vent path:
Select route that will provide straightest and most direct
path outdoors.
Plan installation to use fewest number of elbows and turns.
When using elbows or making turns, allow as much room
as possible.
Bend vent gradually to avoid kinking.
Use as few 90° turns as possible.
Determine vent length and elbows needed for best
drying performance:
Use the following “Vent System Charts” to determine type
of vent material and hood combinations acceptable to use.
NOTE:
Do not use vent runs longer than those specified
in “Vent System Charts.”
Exhaust systems longer than those specified will:
Shorten life of dryer.
Reduce performance, resulting in longer drying times
and increased energy usage.
Install Vent System
1.
Install exhaust hood
12" min.
(305 mm)
12" min.
(305 mm)
2.
Connect vent to exhaust hood
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
Vent must fit over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location using
straightest path possible. Avoid 90° turns. Use clamps to seal
all joints. Do not use duct tape, screws, or other fastening
devices that extend into interior of vent to secure vent,
because they can catch lint.
1.
Turn cold water off, remove hose,
and replace rubber washer
Turn cold water faucet off and remove washer inlet hose.
Remove old rubber washer from inlet hose and replace with
new rubber washer.
CONNECT INLET HOSE
(STEAM MODEL ONLY)
For non-steam models, skip to “Connect Vent.”
The dryer must be connected to the cold water faucet using
new inlet hoses (not supplied). Do not use old hoses.
NOTE:
Replace inlet hoses after 5 years of use to reduce the
risk of hose failure. Record hose installation or replacement
dates on the hoses for future reference.
Periodically inspect and replace hoses if bulges, kinks, cuts,
wear, or leaks are found.
To determine if your model has a long vent system, refer to
the type code located on the serial number plate in the inner
door well. Example: An electric model would be DA
LV
(Long
Vent) – ELE – XXXXXXX-XXX.
NOTE:
For long vent systems, use of box/louvered hoods will
improve venting, regardless of length.
Long Vent System Chart
Number of
90° elbows
Type
of vent
Angled
hoods
1
4
3
2
0
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Rigid metal
160 ft. (48.8 m)
150 ft. (45.7 m)
140 ft. (42.7 m)
130 ft. (39.6 m)
120 ft. (36.6 m)
Standard Vent System Chart
Number of
90° elbows
Type
of vent
Angled
hoods
1
4
3
2
0
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Rigid metal
64 ft. (20 m)
54 ft. (16.5 m)
44 ft. (13.4 m)
35 ft. (10.7 m)
27 ft. (8.2 m)