Maytag MEDB755DW Dimension Guide - Page 2

Venting Requirements, Installation Requirements - electric dryer

Page 2 highlights

INSTALLATION REQUIREMENTS GAS SUPPLY REQUIREMENTS Gas supply: This dryer is equipped for use with Natural gas. Dryer can be converted to L.P. gas. When rigid pipe is used it should be 1/2" IPS. When acceptable to the gas supplier and local codes, 3/8" approved tubing may be used for lengths under 20 ft (6.1 m). For lengths over 20 ft (6.1 m), larger tubing should be used. Pipe-joint compounds resistant to the action of L.P. gas must be used. An individual manual shutoff valve must be installed within 6 ft (1.8 m) of the dryer in accordance with the National Fuel Gas Code ANSI Z223.1. ELECTRICAL REQUIREMENTS - Gas models only A 120-volt, 60 Hz, AC-only, 15 or 20 amp fused electrical supply is required. A time-delay fuse or circuit breaker and a separate circuit are recommended. ELECTRICAL REQUIREMENTS - Electric models only To supply the required 3 or 4 wire, single phase, 120/240 volt, 60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt electrical supply, if specified on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect to an individual branch circuit. WATER (STEAM MODELS ONLY) REQUIREMENTS The dryer must be connected to the cold water faucet using new inlet hoses. Do not use old hoses. Do not overtighten. Damage to the coupling can result. VENTING REQUIREMENTS Exhaust venting: Exhaust your dryer to the outside. 4" (102 mm) diameter vent is required. Rigid or flexible metal exhaust vent must be used. Do not use plastic or metal foil vet. Exhaust hood must be at least 12" (305 mm) from the ground or any object that may be in the path of the exhaust. Exhaust hoods: Recommended Styles: Determine vent length and elbows needed for best drying performance: ■■ Use following Vent System Chart to determine type of vent material and hood combinations acceptable to use. NOTE: Do not use vent runs longer than those specified in Vent System Chart. Exhaust systems longer than those specified will: ■■ Shorten life of dryer. ■■ Reduce performance, resulting in longer drying times and increased energy usage. Louvered Hood Acceptable Style: Box Hood Angled Hood Determine vent path: ■■ Select route that will provide straightest and most direct path outdoors. ■■ Plan installation to use fewest number of elbows and turns. ■■ When using elbows or making turns, allow as much room as possible. ■■ Bend vent gradually to avoid kinking. ■■ Use as few 90° turns as possible. The "Vent System Chart" provides venting requirements that will help achieve best drying performance. Number of 90° turns or elbows 0 1 2 3 4 Vent System Chart Type of vent Box/louvered hoods Angled hoods Rigid metal Rigid metal Rigid metal Rigid metal Rigid metal 64 ft. (20 m) 54 ft. (16.5 m) 44 ft. (13.4 m) 35 ft. (10.7 m) 27 ft. (8.2 m) 58 ft. (17.7 m) 48 ft. (14.6 m) 38 ft. (11.6 m) 29 ft. (8.8 m) 21 ft. (6.4 m) NOTE: Bottom exhaust installations have a 90° turn inside the dryer. To determine maximum exhaust length, add one 90° turn to the charts. Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to change materials and specifications without notice. Dimensions are for planning purposes only. For complete details, see Installation Instructions packed with product. Specifications subject to change without notice.

  • 1
  • 2

Because Whirlpool Corporation policy includes a continuous commitment to improve
Dimensions are for planning purposes only. For complete details, see Installation
our products, we reserve the right to change materials and specifications without notice.
Instructions packed with product. Specifications subject to change without notice.
ELECTRICAL REQUIREMENTS - Gas models only
VENTING REQUIREMENTS
E
xhaust venting: Exhaust your dryer to the outside. 4" (102 mm)
diameter vent is required. Rigid or flexible metal exhaust vent
must be used. Do not use plastic or metal foil vet. Exhaust hood
must be at least 12" (305 mm) from the ground or any object that
may be in the path of the exhaust.
Determine vent length and elbows needed for best
drying performance:
Use following Vent System Chart to determine type of vent
material and hood combinations acceptable to use.
NOTE:
Do not use vent runs longer than those specified
in Vent System Chart. Exhaust systems longer than those
specified will:
Shorten life of dryer.
Reduce performance, resulting in longer drying times
and increased energy usage.
Louvered Hood
Angled Hood
Box Hood
Exhaust hoods:
Recommended Styles:
Acceptable Style:
The dryer must be connected to the cold water faucet using new inlet hoses. Do not use old hoses. Do not overtighten.
Damage to the coupling can result.
A 120-volt, 60 Hz, AC-only, 15 or 20 amp fused electrical supply is required. A time-delay fuse or circuit breaker and a separate circuit
are recommended.
GAS SUPPLY REQUIREMENTS
Gas supply
:
This dryer is equipped for use with Natural gas. Dryer can be converted to L.P. gas. When rigid pipe is used it should be 1/2" IPS. When
acceptable to the gas supplier and local codes, 3/8" approved tubing may be used for lengths under 20 ft (6.1 m). For lengths over 20 ft (6.1 m), larger
tubing should be used. Pipe-joint compounds resistant to the action of L.P. gas must be used. An individual manual shutoff valve must be installed
within 6 ft (1.8 m) of the dryer in accordance with the National Fuel Gas Code ANSI Z223.1.
WATER (STEAM MODELS ONLY) REQUIREMENTS
Determine vent path:
Select route that will provide straightest and most direct
path outdoors.
Plan installation to use fewest number of elbows and
turns.
When using elbows or making turns, allow as much
room
as possible.
Bend vent gradually to avoid kinking.
Use as few 90° turns as possible.
INSTALLATION REQUIREMENTS
ELECTRICAL REQUIREMENTS - Electric models only
To supply the required 3 or 4 wire, single phase, 120/240 volt, 60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt electrical supply, if specified
on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect
to an individual branch circuit.
NOTE:
Bottom exhaust installations have a 90° turn inside the
dryer. To determine maximum exhaust length, add one 90° turn
to the charts.
The “Vent System Chart” provides venting requirements that
will help achieve best drying performance.
Number of
90° turns
or elbows
Type
of vent
Box/louvered
hoods
Angled
hoods
0
Rigid metal
64 ft. (20 m)
58 ft. (17.7 m)
1
Rigid metal
54 ft. (16.5 m)
48 ft. (14.6 m)
2
Rigid metal
44 ft. (13.4 m)
38 ft. (11.6 m)
3
Rigid metal
35 ft. (10.7 m)
29 ft. (8.8 m)
4
Rigid metal
27 ft. (8.2 m)
21 ft. (6.4 m)
Vent System Chart