Maytag MEDB850WQ Installation Guide - Page 15

Connect Inlet Hoses, Install Vent System - steam dryer

Page 15 highlights

Maytag Vent System Chart Number of 90° elbows Type of vent Box/louvered hoods Angled hoods 0 Rigid metal 100 ft. (30.5 m) 94 ft. (28.7 m) 1 Rigid metal 90 ft. (27.4 m) 84 ft. (25.6 m) 2 Rigid metal 80 ft. (24.4 m) 74 ft. (22.6 m) 3 Rigid metal 71 ft. (21.6 m) 65 ft. (19.8 m) 4 Rigid metal 63 ft. (19.2 m) 57 ft. (17.4 m) NOTE: Bottom exhaust installations have a 90° turn inside the dryer. To determine maximum exhaust length, add one 90° turn to the charts. INStall VENT SYSTEM 1. Install exhaust hood 12" min. (305 mm) CONNECT INLET HOSES For non-steam models, skip to "Connect Vent" on page 16. The dryer must be connected to the cold water faucet using the new inlet hoses. Do not use old hoses. 1. Turn cold water off, remove and replace rubber washer Turn cold water faucet off and remove washer inlet hose. Check and see if rubber washer is in the "Y" connector. Remove old rubber washer from inlet hose and replace with new rubber washer provided. 2. Attach short hose and "Y" connector 12" min. (305 mm) Install exhaust hood and use caulking compound to seal exterior wall opening around exhaust hood. 2. Connect vent to exhaust hood Fig. A Fig. B If space permits, attach the brass female end of the "Y" connector to the cold water faucet. See figure A. If "Y" connector cannot be attached directly to the cold water faucet, the short hose must be used. See figure B. Attach short hose to cold water faucet. Screw on coupling by hand until it is seated on faucet. Then attach "Y" connector to brass male end of the short hose. Screw on coupling by hand until it is seated on connector. 3. Tighten couplings Vent must fit over the exhaust hood. Secure vent to exhaust hood with 4" (102 mm) clamp. Run vent to dryer location using straightest path possible. Avoid 90° turns. Use clamps to seal all joints. Do not use duct tape, screws, or other fastening devices that extend into interior of vent to secure vent, because they can catch lint. Using pliers, tighten the couplings with additional two-thirds turn. NOTE: Do not overtighten. Damage to the coupling can result. 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

15
2.
Connect vent to exhaust hood
Vent must fit over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location using
straightest path possible. Avoid 90° turns. Use clamps to seal
all joints. Do not use duct tape, screws, or other fastening
devices that extend into interior of vent to secure vent,
because they can catch lint.
Turn cold water off, remove and
replace rubber washer
1.
Turn cold water faucet off and remove washer inlet hose.
Check and see if rubber washer is in the “Y” connector.
Remove old rubber washer from inlet hose and replace
with new rubber washer provided.
For non-steam models, skip to “Connect Vent” on page 16.
The dryer must be connected to the cold water faucet using
the new inlet hoses. Do not use old hoses.
CONNECT INLET HOSES
Tighten couplings
3.
Using pliers, tighten the couplings with additional two-thirds
turn.
NOTE:
Do not overtighten. Damage to the coupling can result.
Attach short hose and
“Y” connector
2.
If space permits, attach the brass female end of the “Y”
connector to the cold water faucet. See figure A.
If “Y” connector cannot be attached directly to the cold water
faucet, the short hose must be used. See figure B. Attach short
hose to cold water faucet. Screw on coupling by hand until it is
seated on faucet. Then attach “Y” connector to brass male end
of the short hose. Screw on coupling by hand until it is seated
on connector.
Fig. A
Fig. B
INSTALL VENT SYSTEM
12" min.
(305 mm)
12" min.
(305 mm)
Install exhaust hood
1.
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
NOTE:
Bottom exhaust installations have a 90° turn inside the
dryer. To determine maximum exhaust length, add one 90° turn
to the charts.
Maytag Vent System Chart
Number of
90° elbows
Type
of vent
Box/louvered
hoods
Angled
hoods
1
4
3
2
0
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Rigid metal
100 ft. (30.5 m)
90 ft. (27.4 m)
80 ft. (24.4 m)
71 ft. (21.6 m)
63 ft. (19.2 m)
94 ft. (28.7 m)
84 ft. (25.6 m)
74 ft. (22.6 m)
65 ft. (19.8 m)
57 ft. (17.4 m)