Condensing Unit Refrigerant Line Size Information

Page 31 highlights

Refrigerant Line Size Information Air RARL- JEZ Series Condensing Unit Refrigerant Line Size Information 2-Stage R-410A System Capacity Model Liquid Line Connection Size (Inch I.D.) Line Size (Inch O.D.) [mm] 25 [7.62] 1/4* [6.35] 0 2 Ton 5/16″ [7.94] 5/16 [7.94] 0 3/8 [9.53] 0 3 Ton 5/16″ [7.94] 5/16* [7.94] 3/8 [9.53] 0 0 4 Ton 3/8″ [9.53] 5/16* [7.94] 3/8 [9.53] 0 0 5 Ton 3/8″ [9.53] 3/8* [9.53] 1/2 [12.7] 0 0 NOTES: N/A = Application not recommended. *Standard line size Liquid Line Size Outdoor unit above Indoor Coil (Cooling Only) Liquid Line Size Outdoor unit Below Indoor Coil (Cooling Only) Total Equivalent Length-Feet [m] Total Equivalent Length-Feet [m] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72] 25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72] Minimum Vertical Separation-Feet [m] Maximum Vertical Separation-Feet [m] 0 17 [5.18] 43 [13.10] 70 [21.33] 95 [28.95] 25 [7.62] 10 [3.04] N/A N/A N/A N/A 0 0 0 0 0 25 [7.62] 50 [15.24] 40 [12.19] 35 [10.66] 29 [8.83] 22 [6.70] 0 0 0 0 0 25 [7.62] 50 [15.24] 45 [13.71] 42 [12.80] 39 [11.88] 37 [11.28] 0 0 0 0 7 25 [7.62] 39 [11.88] 28 [8.53] 16 [4.87] 5 [1.52] N/A 0 0 0 0 0 25 [7.62] 50 [15.24] 51 [15.54] 48 [14.63] 44 [13.41] 40 [12.19] 0 8 [2.43] 32 [9.75] 55 [16.76] 80 [24.38] 25 [7.62] 15 [4.57] N/A N/A N/A N/A 0 0 0 0 0 25 [7.62] 47 [14.32] 40 [12.19] 32 [9.75] 24 [7.31] 17 [5.18] 0 0 0 0 0 25 [7.62] 41 [12.49] 30 [9.14] 20 [6.09] 10 [3.04] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 56 [17.06] 54 [16.45] 52 [15.84] 50 [15.24] 2-Stage R-410A System Capacity Model Suction Line Connection Size Suction Line Run Feet [m] 25' [7.62] Optional Standard Optional 50' [15.24] Optional Standard Optional 100' [30.48] Optional Standard Optional 150' [45.72] Optional Standard Optional Suction Line Length/Size and Capacity Multiplier 2 Ton 3 Ton 3/4" [19.05] I.D. 5/8" [15.88 mm] O.D. Std.* 3/4" [19.05 mm] O.D. Opt. 5/8" [15.88 mm] O.D. Opt. 3/4" [19.05 mm] O.D. Std.* - .99 1.00 1.00 1.00 N/A - 0.98 0.99 0.99 1.00 N/A - 0.95 0.97 0.97 0.98 N/A - 0.91 0.95 0.95 0.97 N/A NOTES: Line size not recommended due to inadequate oil return. *Standard line size [ ] Designates Metric Conversions 4 Ton 5 Ton 7/8" [22.23] I.D. 3/4" [19.05 mm] O.D. Opt. 7/8" [22.23 mm] O.D. Std.* 1.00 .99 1.00 1.00 N/A N/A 0.98 0.98 0.99 0.99 N/A N/A 0.95 0.94 0.97 0.97 N/A N/A 0.93 0.91 0.95 0.95 N/A N/A 31

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Air
Refrigerant Line Size Information
RARL- JEZ Series
Suction Line Run
Feet [m]
25'
[7.62]
50'
[15.24]
100'
[30.48]
150'
[45.72]
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
5
/
8
"[15.88 mm]O.D. Std.*
3
/
4
" [19.05 mm]O.D. Opt.
1.00
1.00
0
.99
1.00
0
.97
0
.98
0
.95
0
.97
Suction Line Length/Size and Capacity Multiplier
2-Stage R-410A
System Capacity Model
2 Ton
3 Ton
5
/
8
"[15.88 mm]O.D. Opt.
3
/
4
" [19.05 mm]O.D. Std.*
.99
1.00
N/A
0
.98
0
.99
N/A
0
.95
0
.97
N/A
0
.91
0
.95
N/A
4 Ton
3
/
4
" [19.05 mm]O.D. Opt.
7
/
8
" [22.23 mm]O.D. Std.*
1.00
1.00
N/A
0
.98
0
.99
N/A
0
.95
0
.97
N/A
0
.93
0
.95
N/A
5 Ton
.99
1.00
N/A
0
.98
0
.99
N/A
0
.94
0
.97
N/A
0
.91
0
.95
N/A
Suction Line Connection Size
3/4" [19.05] I.D.
7/8" [22.23] I.D.
2-Stage
R-410A
System
Capacity
Model
Line Size
(Inch O.D.)
[mm]
Liquid Line Size
Outdoor unit above Indoor Coil (Cooling Only)
Liquid Line Size
Outdoor unit Below Indoor Coil (Cooling Only)
Minimum Vertical Separation—Feet [m]
Maximum Vertical Separation—Feet [m]
25
[7.62]
50
[15.24]
75
[22.86]
100
[30.48]
125
[38.10]
150
[45.72]
25
[7.62]
50
[15.24]
75
[22.86]
100
[30.48]
125
[38.10]
150
[45.72]
Total Equivalent Length—Feet [m]
Total Equivalent Length—Feet [m]
5/16
[7.94]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
40 [12.19]
35 [10.66]
29
[8.83]
22
[6.70]
2 Ton
1/4*
[6.35]
0
0
17 [5.18]
43 [13.10]
70 [21.33]
95 [28.95]
25 [7.62]
10
[3.04]
N/A
N/A
N/A
N/A
5/16
[7.94]
Liquid Line
Connection
Size
(Inch I.D.)
3/8
[9.53]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
51 [15.54]
48 [14.63]
44 [13.41]
40 [12.19]
3 Ton
5/16* [7.94]
0
0
0
0
0
7
25 [7.62]
39 [11.88]
28
[8.53]
16
[4.87]
5
[1.52]
N/A
5/16
[7.94]
3/8
[9.53]
0
0
0
0
0
0
25 [7.62]
47 [14.32]
40 [12.19]
32
[9.75]
24
[7.31]
17
[5.18]
4 Ton
5/16* [7.94]
0
0
8 [2.43]
32 [9.75]
55 [16.76]
80 [24.38]
25 [7.62]
15
[4.57]
N/A
N/A
N/A
N/A
3/8
[9.53]
1/2
[12.7]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
56 [17.06]
54 [16.45]
52 [15.84]
50 [15.24]
5 Ton
3/8*
[9.53]
0
0
0
0
0
0
25 [7.62]
41 [12.49]
30
[9.14]
20
[6.09]
10
[3.04]
0
3/8
[9.53]
3/8
[9.53]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
45 [13.71]
42 [12.80]
39 [11.88]
37 [11.28]
NOTES: N/A = Application not recommended.
*Standard line size
NOTES: Line size not recommended due to inadequate oil return.
*Standard line size
[
] Designates Metric Conversions
Condensing Unit Refrigerant Line Size Information
31