Rheem SolPak Use and Care Manual - Page 19

circulate the fluid using the pressure pump until

Page 19 highlights

flow meter is recommended as an optional system component. A flow meter allows you to monitor and adjust the flow rate through the piping and also to visually inspect the HTF fluid quality. Set the controller to the "off" position and proceed to the next step. 4.9.4 Mix the Dowfrost HD propylene glycol and distilled water mixture in accordance with Table 4 and Table 5 in a large clean bucket. You will need a second empty bucket as well. The charging process also will require a low flow diaphragm pump (Flojet or equal) to fill and pressurize the collector loop. Connect the discharge side of the pressure pump to the upper isolation/drain valve (No. 7) Place the pump suction side hose in the glycol solution. Close the isolation ball valve (No. 7) and connect a second hose to the lower isolation/drain valve (No. 6). Place the other end of the hose in the empty bucket. Table 4 Percent (volume) Glycol Concentration Required Temperature F 20 10 0 -10 -20 -30 -40 -50 -60 For Freeze Protection 18% 29 36 42 46 50 54 57 60 For Burst Protection 12% 20 24 28 30 33 35 35 35 Table 5 Total Collector Loop Fluid Capacity In Gallons* Open the upper drain valve and allow the pressure from the expansion tank to push the water in the glycol loop back to prime the pressure pump. When the hose in the bucket containing the glycol mixture stops bubbling you may begin charging the collector loop with glycol. With both drain valves (No. 6 & 7) faucets now open, run the Flojet pressure pump until the pinkish glycol mixture begins flowing into the empty bucket. Quickly switch the hose from the empty/return bucket to the bucket containing the glycol mixture. Continue to circulate the fluid using the pressure pump until the bubbling has stopped and the air has been purged. 4.9.5 After charging the collector loop, shut the lower drain valve (No. 6) and let the pressure pump drive up the loop pressure to the appropriate level (Generally in the range of 25 PSI). To more accurately calculate the proper pressure measure the height of the solar collector above the solar storage tank and divide this number by 2.31. Then add 20 PSI to this number. As a word of caution, the pressure in the glycol loop should not exceed 45 PSI when the system is operational on a good sunny day. Contact your solar contractor if the charged collector loop pressure exceeds this threshold. Your solar water heating system must be charged and the fluid quality maintained by an experienced contractor. If the system is drained during the winter, or you notice a significant drop in collector loop pressure, contact your installation contractor immediately for service. The glycol HTF provides the freeze protection for your system and must be properly maintained. An experienced contractor should periodically check the HTF fluid quality. 1 Collector System 2 Collector System 4 Gallons 5 Gallons 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

19
flow meter is recommended as an optional
system component. A flow meter allows you
to monitor and adjust the flow rate through the
piping and also to visually inspect the HTF fluid
quality.
Set the controller to the "off" position and
proceed to the next step.
4.9.4
Mix the Dowfrost HD propylene glycol and
distilled water mixture in accordance with
Table 4 and Table 5 in a large clean bucket.
You will need a second empty bucket as well.
The charging process also will require a low
flow diaphragm pump (Flojet or equal) to fill
and pressurize the collector loop.
Connect the discharge side of the pressure
pump to the upper isolation/drain valve (No.
7) Place the pump suction side hose in the
glycol solution. Close the isolation ball valve
(No. 7) and connect a second hose to the lower
isolation/drain valve (No. 6). Place the other
end of the hose in the empty bucket.
Open the upper drain valve and allow the
pressure from the expansion tank to push the
water in the glycol loop back to prime the
pressure pump. When the hose in the bucket
containing the glycol mixture stops bubbling
you may begin charging the collector loop with
glycol.
With both drain valves (No. 6 & 7) faucets
now open, run the Flojet pressure pump until
the pinkish glycol mixture begins flowing into
the empty bucket. Quickly switch the hose
from the empty/return bucket to the bucket
containing the glycol mixture. Continue to
circulate the fluid using the pressure pump until
the bubbling has stopped and the air has been
purged.
4.9.5
After charging the collector loop, shut the
lower drain valve (No. 6) and let the pressure
pump drive up the loop pressure to the
appropriate level (Generally in the range of
25 PSI). To more accurately calculate the
proper pressure measure the height of the solar
collector above the solar storage tank and
divide this number by 2.31. Then add 20 PSI to
this number. As a word of caution, the pressure
in the glycol loop should not exceed 45 PSI
when the system is operational on a good
sunny day. Contact your solar contractor if the
charged collector loop pressure exceeds this
threshold.
Your solar water heating system must be
charged and the fluid quality maintained by an
experienced contractor. If the system is drained
during the winter, or you notice a significant
drop in collector loop pressure, contact your
installation contractor immediately for service.
The glycol HTF provides the freeze protection
for your system and must be properly
maintained. An experienced contractor should
periodically check the HTF fluid quality.
Table 4
Percent (volume) Glycol Concentration Required
Temperature F
For Freeze Protection
For Burst Protection
20
18%
12%
10
29
20
0
36
24
-10
42
28
-20
46
30
-30
50
33
-40
54
35
-50
57
35
-60
60
35
Table 5
Total Collector Loop Fluid Capacity In Gallons*
1 Collector System
4 Gallons
2 Collector System
5 Gallons