TP-Link T2600G-28TS TL-SG3424 T2600G-28TS V1 Installation Guide - Page 16
used. If any requirements cannot be met, you can add a steel tube or metal raceway
View all TP-Link T2600G-28TS TL-SG3424 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
Gigabit L2 Managed Switch ■■ Requirements for the distance between Ethernet cable and other pipelines are shown in the table. Other Pipelines Ethernet Cable Min Parallel Net Length Min Parallel-overlapping Net Height L (mm) H (mm) Down-conductor 1000 300 PE 50 20 Service pipe 150 20 Compressed air pipe 150 20 Thermal pipe (not wrapped) 500 500 Thermal pipe (wrapped) 300 300 Gas pipe 300 20 The two diagrams below demonstrate parallel net length and parallel-overlapping net height. 10 Lightning Protection Note: The above minimum net length/height is required when metal raceway is not used. If any requirements cannot be met, you can add a steel tube or metal raceway for shielding. ■■ Requirements for the distance between Ethernet cable and high-power electric devices are in following tables. Cable Pave Way 5kVA powerline Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Min Parallel Length (mm) 130 70 10 300 150 80 600 300 150 Device Switch case Transformer room Elevator tower Air-conditioner room Min Distance (m) 1.00 2.00 2.00 2.00