Toro 53765 User Guide - Page 14

Connecting the Power Source, Connecting a Pump Start Relay

Page 14 highlights

Connecting a Pump Start Relay CAUTION: To prevent timer damage, ensure the relay current draw does not exceed 0.30 Amps. Do not connect the timer directly to the pump starter. 1. For pump relay wires, install a 1/2" conduit adapter and conduit. 2. Connect a wire pair to the pump relay terminals and route the cable through the conduit and into the timer housing. 3. Connect one wire to the terminal labeled COM (12). Connect the remaining wire to the terminal labeled PUMP/MV (13) as shown below. Jumper Wire 12 13 24 V a.c. Valve Common Wire Pump Relay CAUTION: To prevent pump damage due to "dead-heading," connect a jumper wire from any unused zone terminal to a zone terminal with a valve connected. Note: Refer to "Pump Control" section on page 29 for 12 important pump circuit control information. Connecting the Power Source WARNING: AC power wiring must be installed and connected by qualified personnel only. All electrical components and installation procedures must comply with all applicable local and national electrical codes. Some codes may require a means of disconnection from the AC power source installed in the fixed wiring and having a contact separation of at least 0.120" in the line and neutral poles. Make sure the power source is OFF prior to connecting the timer. 1. Route the power and equipment ground wires from the power source, through the conduit and into the timer transformer compartment. Note: The timer terminal block accepts wire size up to 14 gauge. 2. Remove 3/8" insulation from the wire ends. 3. Using a small flat blade screwdriver, secure the wires as shown to the terminal block as follows: Line or Line 1 (L1) to L, Neutral or Line 2 (L2) to N and Equipment Ground to . 4. Install and secure the transformer compartment cover. 5. Apply power to the timer. Note: The display will begin flashing 12:00 AM. Press any button to stop the display from flashing.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44

CAUTION: To prevent timer damage, ensure the
relay current draw does not exceed 0.30 Amps. Do
not connect the timer directly to the pump starter.
1.
For pump relay wires, install a 1/2" conduit adapter
and conduit.
2.
Connect a wire pair to the pump relay terminals and
route the cable through the conduit and into the timer
housing.
3.
Connect one wire to the terminal labeled COM (12).
Connect the remaining wire to the terminal labeled
PUMP/MV (13) as shown below.
CAUTION: To prevent pump damage due to
“dead-heading,” connect a jumper wire from any
unused zone terminal to a zone terminal with a valve
connected.
Note:
Refer to “Pump Control” section on page 29 for
important pump circuit control information.
1.
Route the power and equipment ground wires from the
power source, through the conduit and into the timer
transformer compartment.
Note:
The timer terminal block accepts wire size up to
14 gauge.
2.
Remove 3/8" insulation from the wire ends.
3.
Using a small flat blade screwdriver, secure the wires
as shown to the terminal block as follows:
Line or Line 1 (L1) to
L
, Neutral or Line 2 (L2) to
N
and Equipment Ground to
.
4.
Install and secure the transformer compartment
cover.
5.
Apply power to the timer.
Note:
The display will begin flashing 12:00
AM
. Press any
button to stop the display from flashing.
Connecting the Power Source
Connecting a Pump Start Relay
12
24 V a.c.
Pump Relay
Valve Common Wire
Jumper Wire
WARNING:
AC power wiring must be installed and connected
by qualified personnel only. All electrical compo-
nents and installation procedures must comply
with all applicable local and national electrical
codes. Some codes may require a means of discon-
nection from the AC power source installed in the
fixed wiring and having a contact separation of at
least 0.120" in the line and neutral poles.
Make sure the power source is OFF prior to con-
necting the timer.
12
13