Tripp Lite 5PX3000RTNG2 Owners Manual for 5PX1000RTG2 5PX1000RTNG2 5PX1500RTG2 - Page 22

In ABM® cycling mode: [No test] [Every ABM® cycle], Every ABM® cycle]

Page 22 highlights

Submenu Forced reboot Available settings [Yes] [No] [Timer] [10s] ... [180s] When mains recovers during a shutdown sequence: If set to Enabled, shutdown sequence will complete and wait 10 seconds prior to restart, If set to Disabled, shutdown sequence will not complete, UPS stays on. Default settings [Yes] [10s] Energy saving (W,%, delay) [Yes] [No] [Time] [1min] ... [15min] [Level] [10W] ... [1000W-3000W] If Enabled, UPS will shut-down after defined duration of back-up time, if load is less than set value. [No] [5min] [100W] Sleep Mode + timer [Enabled] [Disabled] [Timer] [10min] ... [120min] If Disabled, LCD and communication will turn OFF immediately after UPS is OFF. If Enabled, LCD and communication stays ON for the set time period after UPS is OFF (default 90 min). [Enabled] [90min] Site Wiring Fault [Enabled] [Disabled] Prevents the UPS from starting if the phase and neutral wires are swapped.. [Enebled] Power Off alert [Yes] [No] If enabled, activates a confirmation screen that requires user confirmation after pressing the power button, before UPS shutdown occurs. [Yes] Auto battery test In ABM® cycling mode: [No test] [Every ABM® cycle] In constant charge mode: [No test] [Daily] [Weekly] [Monthly] [Every ABM® cycle] [Weekly] Battery Battery life settings warning [Enabled] [Disabled] [6-120] Battery Age warning If Enabled, the UPS displays a battery replacement reminder through the front LCD and any installed network communication card after the indicated timeframe has elapsed (default 48 months). [Enable] [48 Month] Low battery warning (capacity + remain. time) [Capacity] [0%] ... [100%] [Runtime] [0min] ... [60min] The alarm triggers when the set percentage of battery capacity or remaining back-up time is reached. [0%] [3min] 614-40095-00 22

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42

614-40095-00
22
Submenu
Available settings
Default settings
Forced
reboot
[Yes] [No]
[Timer] [10s] … [180s]
When mains recovers during a shutdown sequence:
If set to Enabled, shutdown sequence will complete and
wait 10 seconds prior to restart,
If set to Disabled, shutdown sequence will not complete,
UPS stays on.
[Yes]
[10s]
Energy saving
(W,%, delay)
[Yes] [No]
[Time] [1min] … [15min]
[Level] [10W] … [1000W-3000W]
If Enabled, UPS will shut-down after defined duration of
back-up time, if load is less than set value.
[No]
[5min]
[100W]
Sleep Mode +
timer
[Enabled] [Disabled]
[Timer] [10min] … [120min]
If Disabled, LCD and communication will turn OFF
immediately after UPS is OFF.
If Enabled, LCD and communication stays ON for the set
time period after UPS is OFF (default 90 min).
[Enabled]
[90min]
Site Wiring
Fault
[Enabled] [Disabled]
Prevents the UPS from starting if the phase and neutral
wires are swapped..
[Enebled]
Power Off
alert
[Yes] [No]
If enabled, activates a confirmation screen that requires
user confirmation after pressing the power button, before
UPS shutdown occurs.
[Yes]
Battery
settings
Auto battery
test
In ABM® cycling mode: [No test] [Every ABM® cycle]
In constant charge mode: [No test] [Daily] [Weekly]
[Monthly]
[Every ABM® cycle]
[Weekly]
Battery life
warning
[Enabled] [Disabled]
[6-120]
Battery Age warning
If Enabled, the UPS displays a battery replacement
reminder through the front LCD and any installed network
communication card after the indicated timeframe has
elapsed (default 48 months).
[Enable]
[48 Month]
Low battery
warning
(capacity +
remain. time)
[Capacity] [0%] … [100%]
[Runtime] [0min] … [60min]
The alarm triggers when the set percentage of battery
capacity or remaining back-up time is reached.
[0%]
[3min]