Tripp Lite 9PX1000RT Product Datasheet - Page 3

Hot-swappable, user replaceable batteries. UPS requires 1 Replacement Battery Cartridge.

Page 3 highlights

1000 Eaton Boulevard Cleveland, OH 44122 United States Output Receptacles (8) 5-15R Individually Controllable Load Banks Yes BATTERY Battery Type Full Load Runtime (min.) Half Load Runtime (min.) Expandable Runtime Expandable Runtime Description DC System Voltage (VDC) Battery Access Internal UPS Replacement Battery Cartridge Battery Replacement Description Valve Regulated Lead Acid (VRLA) 6 min. (900W) 18 min. (450W) Yes Add up to 4 extended battery modules (EBM). Part number 9PXEBM36RT 36 Battery access door 744-A3960 Hot-swappable, user replaceable batteries. UPS requires 1 Replacement Battery Cartridge. USER INTERFACE, ALERTS & CONTROLS Front Panel LCD Display LCD graphical display Switches RPO / ROO Alarm Cancel Operation Press ESC to silence the alarm Audible Alarm Audible alarm indicates utility failure, low-battery, overload, other UPS/Battery fault or remote shutdown conditions LED Indicators 4 status-indicating LEDs SURGE / NOISE SUPPRESSION UPS AC Suppression Joule Rating UPS AC Suppression Response Time EMI / RFI AC Noise Suppression 190 0 ms Yes PHYSICAL Primary Form Factor Rack Height Cooling Method Unit Dimensions (hwd / in.) Rackmount; Tower 2U Fan 3.400 x 17.300 x 17.700 ENVIRONMENTAL Operating Temperature Range Relative Humidity AC Mode Efficiency Rating (100% Load) 0° to 40°C (32° to 104°F) 0-96% non-condensing 90.3 3 / 4

  • 1
  • 2
  • 3
  • 4

1000 Eaton Boulevard
Cleveland, OH 44122
United States
Output Receptacles
(8) 5-15R
Individually Controllable Load Banks
Yes
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Full Load Runtime (min.)
6 min. (900W)
Half Load Runtime (min.)
18 min. (450W)
Expandable Runtime
Yes
Expandable Runtime Description
Add up to 4 extended battery modules (EBM). Part number 9PXEBM36RT
DC System Voltage (VDC)
36
Battery Access
Battery access door
Internal UPS Replacement Battery
Cartridge
744-A3960
Battery Replacement Description
Hot-swappable, user replaceable batteries. UPS requires 1 Replacement Battery Cartridge.
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
LCD graphical display
Switches
RPO / ROO
Alarm Cancel Operation
Press ESC to silence the alarm
Audible Alarm
Audible alarm indicates utility failure, low-battery, overload, other UPS/Battery fault or remote shutdown conditions
LED Indicators
4 status-indicating LEDs
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
190
UPS AC Suppression Response
Time
0 ms
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Rackmount; Tower
Rack Height
2U
Cooling Method
Fan
Unit Dimensions (hwd / in.)
3.400 x 17.300 x 17.700
ENVIRONMENTAL
Operating Temperature Range
0° to 40°C (32° to 104°F)
Relative Humidity
0-96% non-condensing
AC Mode Efficiency Rating (100%
Load)
90.3
3 / 4