Tripp Lite SU3000RTXR3U Runtime Chart for UPS Model SU3000RTXR3U - Page 1
Tripp Lite SU3000RTXR3U Manual
View all Tripp Lite SU3000RTXR3U manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 1 highlights
SU3000RTXR3U Estimated Runtime Load in Watts UPS SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U SU3000RTXR3U Battery Pack Internal Batteries 1 BP72V15-2U 1 BP72V28RT-3U 2 BP72V28RT-3U 3 BP72V28RT-3U 4 BP72V28RT-3U 5 BP72V28RT-3U 6 BP72V28RT-3U 7 BP72V28RT-3U 8 BP72V28RT-3U 9 BP72V28RT-3U 10 BP72V28RT-3U 500W 82 157 251 443 635 826 1,015 1,201 1,385 1,566 1,745 1,921 1,000W 37 73 120 218 319 421 524 626 727 828 928 1,028 1,100W 33 65 107 197 289 382 475 569 662 754 847 938 1,200W 30 59 97 179 263 349 435 521 607 692 777 862 1,300W 27 53 88 163 241 320 399 479 558 638 717 795 1,400W 25 49 81 150 222 295 369 443 516 590 664 737 1,500W 22 45 74 138 205 273 342 411 480 549 618 687 1,600W 21 41 69 128 190 254 319 383 448 513 578 643 1,700W 19 38 64 119 178 237 298 359 420 481 542 603 1,800W 18 36 59 111 166 223 280 337 395 453 511 568 1,900W 17 33 56 104 156 209 263 318 373 427 482 537 2,000W 15 31 52 98 147 197 249 300 352 404 456 509 2,200W 14 28 46 88 132 177 223 270 317 365 412 459 2,400W 12 25 42 79 119 160 202 245 288 331 375 418 All runtime values are in minutes.