Tripp Lite SU3000XL Runtime Chart for UPS Model SU3000XL - Page 1
Tripp Lite SU3000XL Manual
View all Tripp Lite SU3000XL manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 1 highlights
SU3000XL Estimated Runtime Load in Watts UPS SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL SU3000XL Battery Pack Internal Batteries 1 BP72V15-2U 1 BP72V28RT-3U 2 BP72V28RT-3U 3 BP72V28RT-3U 4 BP72V28RT-3U 5 BP72V28RT-3U 6 BP72V28RT-3U 7 BP72V28RT-3U 8 BP72V28RT-3U 9 BP72V28RT-3U 10 BP72V28RT-3U 500W 39 111 204 395 587 779 968 1,154 1,339 1,521 1,700 1,877 1,000W 17 51 96 193 294 396 498 600 702 803 903 1,003 1,100W 15 45 86 174 266 359 452 545 639 731 824 915 1,200W 14 41 78 158 242 327 413 499 585 671 756 841 1,300W 12 37 70 144 221 300 379 459 538 618 697 776 1,400W 11 34 64 132 203 276 350 424 498 572 646 719 1,500W 10 31 59 122 188 256 325 394 463 532 601 670 1,600W 9.2 28 55 113 175 238 302 367 432 497 562 626 1,700W 8.4 26 51 105 163 222 283 344 405 466 527 588 1,800W 7.8 24 47 98 152 208 265 323 381 438 496 554 1,900W 7.2 23 44 92 143 196 250 304 359 414 468 523 2,000W 6.7 21 41 86 135 185 236 287 339 391 443 495 2,200W 5.9 19 37 77 120 165 212 258 305 353 400 448 2,400W 5.0 17 33 69 108 150 192 234 277 321 364 407 All runtime values are in minutes.