Tripp Lite SU40K Owner's Manual for 3-Phase UPS 932764 - Page 31

Manual Bypass Procedure Parallel UPS

Page 31 highlights

9 - Start-Up, Shutdown and Bypass (continued) 1 9-10 Manual Bypass Procedure (Parallel UPS) Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass power source and will not receive battery backup during a utility power failure. 2 •1 For the first UPS system you wish to shut down, press the OFF button A for 3 seconds (until you hear a beep), then release the button. If the other UPS system can support the connected equipment loads alone, the UPS system that was turned off will shut down its inverter and its LCD screen will read "LOAD NOT POWERED". The other UPS system's LCD screen will read "ONLINE MODE". If the total connected equipment load is too large to be handled by a single UPS system, both UPS systems will shut down their inverters and switch to bypass mode, and their 1 LCD screens will read "ON AUTO BYPASS". Repeat step 1 for the second UPS system you wish to shut down. 3 A 4 •2 Switch off the main input circuit breaker switch Q1 of each UPS system. Q1 5 Output Manual Bypass Main 2 •3 Confirm that both UPS systems are shut down, then switch on Bypass Input Input 6 the manual bypass input circuit breaker switch Q3 of each UPS system. The bypass power source will power the loads and the LCD screen will read "ON MANUAL BYPASS". Q3 7 Output Manual Bypass Main 3 •4 Switch off the bypass input circuit breaker switch Q2 and the Bypass Input Input 8 output circuit breaker switch Q4 of each UPS system. The LCD screen will turn off completely. Q4 Q2 9 Output Manual Bypass Main 4 Bypass Input Input •5 If the UPS systems have external battery cabinets connected, 10 switch off the external battery cabinet circuit breaker switch A of each battery pack. A 11 •6 In this mode, only the manual bypass path (including the manual bypass circuit breaker Q3 , the load terminals of the output circuit breaker switch Q4 and the terminal block B contain hazardous voltage, allowing qualified service personnel to perform maintenance or repair. Note: Qualified service personnel may prefer to de-energize the UPS systems completely, depending on local codes and the nature of the maintenance or repair. 5 Q4 Q3 6 31 12 B 13 14

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

9
5
1
2
3
4
A
Output
Output
Output
Manual
Bypass
Manual
Bypass
Manual
Bypass
Bypass
Input
Bypass
Input
Bypass
Input
Main
Input
Main
Input
Main
Input
Q1
Q3
Q2
Q4
A
6
Q4
Q3
B
31
9 – Start-Up, Shutdown and Bypass
(continued)
If the UPS systems have external battery cabinets connected,
switch off the external battery cabinet circuit breaker switch
A
of
each battery pack.
In this mode, only the manual bypass path (including the manual
bypass circuit breaker
Q3
, the load terminals of the output
circuit breaker switch
Q4
and the terminal block
B
contain
hazardous voltage, allowing qualified service personnel to perform
maintenance or repair.
Note: Qualified service personnel may
prefer to de-energize the UPS systems completely, depending on
local codes and the nature of the maintenance or repair.
9-10 Manual Bypass Procedure (Parallel UPS)
Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass
power source and will not receive battery backup during a utility power failure.
For the first UPS system you wish to shut down, press the OFF
button
A
for 3 seconds (until you hear a beep), then release
the button. If the other UPS system can support the connected
equipment loads alone, the UPS system that was turned off will
shut down its inverter and its LCD screen will read “LOAD NOT
POWERED”. The other UPS system’s LCD screen will read
“ONLINE MODE”. If the total connected equipment load is too
large to be handled by a single UPS system, both UPS systems
will shut down their inverters and switch to bypass mode, and their
LCD screens will read “ON AUTO BYPASS”. Repeat step 1 for
the second UPS system you wish to shut down.
Switch off the main input circuit breaker switch
Q1
of each UPS
system.
Confirm that both UPS systems are shut down, then switch on
the manual bypass input circuit breaker switch
Q3
of each UPS
system. The bypass power source will power the loads and the
LCD screen will read “ON MANUAL BYPASS”.
Switch off the bypass input circuit breaker switch
Q2
and the
output circuit breaker switch
Q4
of each UPS system. The LCD
screen will turn off completely.
5
1
6
2
3
4