Tripp Lite SU750RTXL2U Owner's Manual for SmartOnline Rack/Tower UPS 932471 - Page 12
Troubleshooting
View all Tripp Lite SU750RTXL2U manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 12 highlights
Troubleshooting The UPS's control panel lights will turn on in the sequences below to signal that the UPS is having operational difficulties. Lights (On/Flashing) and Condition Solution On: REPLACE BATT Condition: Replace Battery Let the UPS system charge for at least 12 hours and perform a self test using the "ON/Test Switch" as described in the Basic Operation section. If the light continues to stay on, contact Tripp Lite for service. On: BATT LOW, ON BATT Condition: Battery Low Prepare for imminent UPS shutdown. On: BYPASS, LINE, LOAD, OVERLOAD Reduce the load the UPS supports. Condition: On Bypass due to Overload Flashing: OVERLOAD Condition: Short Circuit Remove the cause of the short circuit from the UPS output. On: FAULT Condition: Wiring Fault Check the utility line for wiring problems such as reversed line and neutral or a missing ground. On: FAULT, 100% Condition: Battery Voltage too High Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: FAULT, BYPASS, LINE, 50% Condition: On Bypass due to High Output Voltage Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: FAULT, BYPASS, LINE Flashing: 50% Condition: On Bypass due to Low Output Voltage Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: FAULT, BYPASS, LINE, 25% Restart the UPS. If the problem persists, contact Condition: On Bypass due to High Bus Tripp Lite for repairs. Voltage On: FAULT, BYPASS, LINE Flashing: 25% Condition: On Bypass due to Low Bus Voltage Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: BYPASS, LINE Flashing: FAULT Condition: On Bypass due to High Internal Temperature Check the UPS to be sure that there is adequate space for air to circulate near the vents and that the fan is working properly. Restart the UPS. Flashing: LINE Condition: Input Abnormal This indicates that utility power is too high or low for the UPS to operate in BYPASS mode, so if an inverter failure occurs, the UPS will deliver no output. On: FAULT, 50% Flashing: LINE Condition: No Output due to High Output Voltage and Abnormal Input Restart the UPS. If the problem persists, contact Tripp Lite for repairs. 12 201102199 93-2471.indb 12 3/30/2011 9:14:05 AM