VENTING DESIGN SPECIFICATIONS This section is intended for architectural designer and builder/ contractor reference only. NOTES: ■■ Vent materials needed for installation are not provided with microwave hood combination. ■■ We do not recommend using a flexible metal vent. ■■ To avoid possible product damage, be sure to vent air outside, unless using recirculation installation. Do not vent exhaust air into concealed spaces, such as spaces within walls or ceilings, attics, crawl spaces, or garages. For optimal venting installation, we recommend: ■■ Using roof or wall caps that have back draft dampers ■■ Using a rigid metal vent ■■ Using the most direct route by minimizing the length of the vent and number of elbows to provide efficient performance ■■ Using uniformly sized vents ■■ Using duct tape to seal all joints in the vent system ■■ Using caulking compound to seal exterior wall or roof opening around cap ■■ Not installing 2 elbows together for optimal hood performance If venting through the wall, be sure that there is proper clearance within the wall for the damper to open fully. If venting through the roof, and rectangular-to-round transition is used, be sure there are at least 3" (7.6 cm) of clearance between the top of the microwave oven and the transition piece. See "Rectangular-to-Round Transition" illustration. Rectangular-to-Round Transition NOTE: The minimum 3" (7.6 cm) clearance must exist between the top of the microwave oven and the rectangular to round transition piece so that the damper can open freely and fully. A B C D E 3" (7.6 cm) F A. Roof cap B. 6" (15.2 cm) min. diameter round vent C. Elbow (for wall venting only) D. Wall cap E. 3¹⁄₄" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm) rectangular to round transition piece F. Vent extension piece, at least 3" (7.6 cm) high Recommended Standard Fittings The following length equivalents are for use when figuring vent length. See the examples in "Recommended Vent Length." A B C Roof venting Roof cap Wall venting Wall cap D E F G A. Rectangular-to-round transition piece: 3¹⁄₄" x 10" to 6" = 5 ft (8.3 x 25.4 cm to 15.2 cm = 1.5 m) B. Roof cap: 3¹⁄₄" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m) C. 90° elbow: 3¹\₄" x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m) D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m) E. Wall cap: 3¹⁄₄" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m) F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m) G. 90° flat elbow: 3¹⁄₄" x 10" = 10 ft (8.3 x 25.4 cm = 3 m) 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12

11
VENTING DESIGN SPECIFICATIONS
This section is intended for architectural designer and builder/
contractor reference only.
NOTES:
Vent materials needed for installation are not provided with
microwave hood combination.
We do not recommend using a flexible metal vent.
To avoid possible product damage, be sure to vent air
outside, unless using recirculation installation. Do not vent
exhaust air into concealed spaces, such as spaces within
walls or ceilings, attics, crawl spaces, or garages.
For optimal venting installation, we recommend:
Using roof or wall caps that have back draft dampers
Using a rigid metal vent
Using the most direct route by minimizing the length of the
vent and number of elbows to provide efficient performance
Using uniformly sized vents
Using duct tape to seal all joints in the vent system
Using caulking compound to seal exterior wall or roof
opening around cap
Not installing 2 elbows together for optimal hood
performance
If venting through the wall, be sure that there is proper clearance
within the wall for the damper to open fully.
If venting through the roof, and rectangular-to-round transition
is used, be sure there are at least 3" (7.6 cm) of clearance
between the top of the microwave oven and the transition
piece. See “Rectangular-to-Round Transition” illustration.
Roof venting
Roof cap
Wall venting
Wall cap
Rectangular-to-Round Transition
NOTE:
The minimum 3" (7.6 cm) clearance must exist between
the top of the microwave oven and the rectangular to round
transition piece so that the damper can open freely and fully.
A
B
C
E
F
D
3" (7.6 cm)
A. Roof cap
B. 6" (15.2 cm) min. diameter round vent
C. Elbow (for wall venting only)
D. Wall cap
E. 3
Z\v
" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm)
rectangular to round transition piece
F. Vent extension piece, at least 3" (7.6 cm) high
Recommended Standard Fittings
The following length equivalents are for use when figuring vent
length. See the examples in “Recommended Vent Length.”
A
B
C
D
E
F
G
A. Rectangular-to-round transition piece: 3
Z\v
" x 10" to 6" = 5 ft
(8.3 x 25.4 cm to 15.2 cm = 1.5 m)
B. Roof cap: 3
Z\v
" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)
C. 90° elbow: 3
Z\v
" x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)
D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)
E. Wall cap: 3
Z\v
" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)
F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)
G. 90° flat elbow: 3
Z\v
" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)