Microamps (A Measurement, Turn the rotary switch on the Meter - test leads

Page 18 highlights

902 Users Manual Microamps µA Measurement The µA dc (G) function on the Meter is primarily for HVAC flame rod testing. To test a heating system flame rod (refer to Figure 3): 1. Turn the heating unit off and locate the wire between the gas-burner controller and the flame rod. 2. Break this connection. 3. Turn the rotary switch on the Meter to G. 4. Using alligator clips, connect test leads between the flame sensor probe and control-module wire. 5. Turn heating unit on and check the reading on the Meter. 6. Refer to the heating unit documentation for what the desired reading should be. 12