Haier HBU-42HF03 User Manual - Page 20

Preparation For The Installation

Page 20 highlights

Installation Procedure 33. PREPARATION FOR THE INSTALLATION (1) Position of ceiling opening between unit and suspending bolt. HBU-42CF03 HBU-42HF03 860-890 (Ceiling opening) 780 (Distance between suspending bolts) HBU-28CF03 HBU-28HF03 Refrigerant pipe (Distance 620 between suspending bolts) *Ceiling 860-890 opening) (160) 950(Ornament panel) 890(Ceiling opening) 840(Indoor unit) 680 (Distance between suspending bolts) Ceiling Suspending bracket A Suspending bolts * 680 (Distance between suspending bolts) 840(Indoor unit) *890(Ceiling opening) 950(Ornament panel) A Note: Dimension of ceiling opening marked with * can be as large as 910mm, but the matching part of ceiling with ornament panel shall be over 20mm. 20 Over (2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer (3) Install a suspending bolt. (Use a M10 bolt) To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field. Before going on installing adjust space between ceiling. 50~100 Roof Anchor bolt Long nut Suspending bolt Ceiling Note: All the above mentioned parts shall be prepared in field. 18

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26

3.
PREPARATION FOR THE INSTALLATION
(1) Position of ceiling opening between unit and suspending bolt.
3
18
HBU-42CF03
HBU-42HF03
HBU-28CF03
HBU-28HF03
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new
ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
<Installation example>
Note: All the above mentioned parts shall be prepared in field.
Ceiling
50~100
Roof
Anchor bolt
Long nut
Suspending bolt
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.
Contact your real estate dealer
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
680
(Distance between suspending bolts)
(Distance between suspending bolts)
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
Suspending bolts
Refrigerant pipe
*
*
680
780
(Distance between suspending bolts)
620
(Distance between suspending bolts)
860-890
860-890
*
Ceiling opening)
(Ceiling
opening)
Note:
Dimension of ceiling opening marked with
*
can be as
large as 910mm, but the matching part of ceiling with
ornament panel shall be over 20mm.
20 Over
(160)
Suspending bracket
Ceiling
A
A
Installation Procedure