Haier HSU18VHJ User Manual - Page 2

Indoor unit

Page 2 highlights

Accessory parts Remote controller (1) Drain hose (1) R-03 dry battery (2) Cushion (4) Mounting plate (1) Drain-elbow (1) Plastic cap (4) Ø4X25 Screw (4) Pipe supporting plate (1) Selection of pipe Liquid pipe (Ø) Gas pipe (Ø) For 12K 6.35mm(1/4") 9.52mm(3/8") For 18K 6.35mm(1/4") 12.7mm (1/2") NOTE˖The thickness of the pipe must be 0.8mm at least. Indoor unit  Fitting of the Mounting Plate and Positioning of the wall Hole When the mounting plate is first fixed 1. Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail. 2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail. 3. Find the wall hole location A using a measuring tape B= Ø70mm A=145mm 35mm B= 70mm 35mm A=150mm When the mounting plate is fixed side bar and lintel ƽ Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar. ƽ Refer to the previous article, " When the mounting plate is first fixed ", for the position of wall hole.  Making a Hole on the Wall and Fitting the Piping Hole Cover ƽ Make a hole of 70 mm in diameter, slightly descending to outside the wall. ƽ Install piping hole cover and seal it off with putty after installation Wall hole Ø70mm Indoor side (Section of wall hole) Outdoor side Thickness of wall G Piping hole pipe  Installation of the Indoor Unit Drawing of pipe [ Rear piping ] ƽ Draw pipes and the drain hose, then fasten them with the adhesive tape [ LeftɾLeft-rear piping ] ƽ In case of left side piping, cut away, with a nipper, the lid for left piping. ƽ In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials. 2 1. Insert the drain hose into the dent of heat insulation materials of indoor unit. 2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them. 3. Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials, cover with adhesive tape. Lid for right piping Lid for under piping pipe Lid for left piping Heat insulation material Drain hose Indoor/outdoor electric cable Piping Pipe supporting plate Fix with adhesive tape ƽ Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping with protecting tape. [ Other direction piping ] ƽ Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according to the position of wall hole. When bending, be careful not to crash pipes. ƽ Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part specially. Fixing the indoor unit body ƽ Hang the unit body securely onto the upper notches of the mounting plate. Move the body from side to side to verify its secure fixing. ƽ In order to fix the body onto the mounting plate,hold up the body aslant from the underside and then put it down perpendicularly. mounting plate Unloading of indoor unit body ƽWhen you unload the indoor unit, please use your hand to raise the body, then lift the bottom of the body outward slightly and lift the unit until it leaves the mounting plate. agraffe mounting plate  Connecting the indoor/outdoor Electric Cable Removing the wiring cover ƽ Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws. When connecting the cable after installing the indoor unit 1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed. 2. Pull out the cable on the front side, and connect the cable making a loop. When connecting the cable before installing the indoor unit ƽ Insert the cord from the back side of the unit, then pull it out on the front side. ƽ Fasten the unit wire harness to the conduit holder using the lock nut. ƽ Position the conduit holder to its original state using screw. Conduit holder Cut the 6 slit sear Note When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not correct, proper operation can not be carried out and will cause defect.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12

Indoor unit
Fix to side bar and lintel a mounting bar, Which is separately sold, and then
fasten the plate to the fixed mounting bar.
Refer to the previous article, “ When the mounting plate is
position of wall hole.
Make a hole of
7
0 mm in diameter, slightly descending to outside the wall.
Install piping hole cover and seal it off with putty after installation
When the mounting plate is first fixed
1. Carry out, based on the neighboring pillars or lintels, a
to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by
hanging a thread with a
weight from the central top of the
plate, then fasten securely the plate with the
attachment steel nail.
3. Find the wall hole location A using a measuring tape
When the mounting plate is fixed side
bar and lintel
Fitting of the Mounting Plate and Positioning of the wall Hole
Lid for right
piping
Lid for under piping pipe
Fix with adhesive tape
Lid for left piping
Indoor/outdoor electric cable and drain hose must be bound with refrigerant
[ Other direction piping ]
Cut away, with a nipper, the lid for piping according to the piping direction and
then bend the pipe according to the position of wall hole. When bending, be
careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the
connected to the heat insulation of
connecting part specially.
proper leveling for the plate
first fixed “, for the
Making a Hole on the Wall and Fitting the Piping Hole Cover
Drawing of pipe
Installation of the Indoor Unit
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left
Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to
the mark of hole for left-rear piping which is marked on heat insulation materials.
1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it
out on the front side, then connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes.
Fixing the indoor unit body
In order to fix the body onto the mounting plate,hold up
the body aslant from the underside and then put it down
perpendicularly.
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then take
off wiring cover by removing its screws.
1. Insert from outside the room cable into left side of the wall
hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable
making a loop.
Note
When connecting the cable, confirm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, proper operation can not
be carried out and will cause defect.
mounting plate
When connecting the cable after installing the indoor unit
When connecting the cable before installing the indoor unit
When you unload the indoor unit, please use
bottom of the body outward slightly
and lift the unit until it leaves the
mounting plate.
agraffe
mounting plate
Unloading of indoor unit body
your hand to raise the body, then lift the
Remote controller (1)
R-03 dry battery (2)
Mounting plate (1)
Drain hose (1)
Ø4X25 Screw (4)
Plastic cap (4)
Drain-elbow (1)
Cushion (4)
Pipe supporting plate (1)
Accessory parts
Liquid pipe (Ø)
6.35mm(1/4”)
Gas pipe (Ø)
9.52mm(3/8”)
NOTE
The thickness of the pipe must be 0.8mm at least.
Selection of pipe
2
A=145mm
35mm
B=
70mm
Ø
For 12K
For 18K
6.35mm(1/4”)
12.7mm(1/2”)
Insert the cord from the back side of the unit, then pull it out on the front side.
Fasten the unit wire harness to the conduit holder using the lock nut.
Position the conduit holder to its original state using screw.
Conduit holder
Cut the 6 slit sear
Cover the connection part with heat insulation materials, cover with adhesive tape.
piping with protecting tape.
Hang the unit body securely onto the upper notches of the
mounting plate. Move the body from side to side to verify
its secure fixing.
Indoor side
Outdoor side
Ø70mm
Wall hole
Thickness of wall
(Section of wall hole)
Piping hole pipe
Heat insulation
material
Drain hose
Piping
Pipe supporting
plate
Indoor/outdoor electric cable
G
A=150mm
B=
70mm
35mm