Model Number, AC Input, Power watts, Heat Diss., BTU/hr, Input Current, Table B-5
View all HP Cisco MDS 9216 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 86 highlights
Power Specifications Appendix B Technical Specifications Send documentation comments to [email protected] Table B-5 Power and Heat Dissipation for AC Input Power Supply Model Number/ Cisco MDS 9134 Switch (with fan modules) Cisco MDS 9124 Switch (with fan modules) Cisco MDS 9140 Switch (with fan modules) Cisco MDS 9120 Switch (with fan modules) AC Input Heat Diss. Power (watts) (BTU/hr) 96 maximum 330 85 VAC (amps) 1.41 Input Current 110 VAC (amps) 220 VAC (amps) 1.10 .55 96 maximum 330 1.41 1.10 .55 204 maximum 870 3.0 2.32 1.16 180 maximum 752 2.65 2.05 1.02 Tip To prevent a loss of input power, ensure that the total maximum load on each circuit supplying the power supply is within the current ratings of the wiring and breakers. Table B-6 provides a sample calculation of power and heat dissipation for the Cisco MDS 9100 Series AC input power supply. Table B-6 Power and Heat Dissipation for DC Input Power Supply Model Number/ Cisco MDS 9134 Switch (with fan modules) Cisco MDS 9124 Switch (with fan modules) Cisco MDS 9140 Switch (with fan modules) Cisco MDS 9120 Switch (with fan modules) DC Input Heat Diss. Power (watts) (BTU/hr) Not supported - Input Current 48 VDC (amps) 60 VDC (amps) - - Not supported - - - 204 maximum 928 5.67 4.53 180 maximum 819 5.00 4.00 Cisco MDS 9100 Series Hardware Installation Guide B-4 OL-17951-02