HP Integrity Superdome 2 8/16 HP Integrity Superdome 2 User Service Guide - Page 27
HP Integrity Superdome 2 utilizes variable speed fans to realize the most efficient use of air.
View all HP Integrity Superdome 2 8/16 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 27 highlights
HP Integrity Superdome 2 utilizes variable speed fans to realize the most efficient use of air. The volume of air required varies with the temperature of the air supplied to the inlet of HP Integrity Superdome 2. The following table and chart illustrate the necessary volume of air to enable proper operation. IMPORTANT: Equipment orientation will best be served in a parallel fashion to the air flow supply and return. Supply air will flow down cold aisles which are parallel to equipment rows, and return air to CRAC through parallel air flow. Perpendicular air flow causes too much room mixing, places higher electrical loads on room, and can lead to unexpected equipment problems. Table 15 Required airflow for inlet temperature Inlet air temperature (°C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Required airflow (CFM) 803 812 821 831 842 854 866 880 894 910 927 945 964 985 1007 1031 1057 1085 Environmental specifications 27