SETTING THE KEYPAD ADDRESS The keypad can either be set for an address of 00-30, or to the non-addressable mode (31). The keypad's default address is 31. To change the keypad's address, do the following: 1. Enter address mode: Power up the keypad. Within 60 seconds of power-up, press and hold down the [1] and [3] keys at the same time for 3 seconds. (If unable to enter address mode, power up and try again.) The current keypad address will be displayed, and the cursor will be under the "tens" digit. If 10 seconds have passed with no key entry, the keypad automatically exits address mode. You must power down, power up and start address mode again. NOTE: The keypad will not enter address mode if the panel to which it is connected is in programming mode. 2. Set the current address to "00": Press [0] to clear the current "tens" digit. The cursor will move to the "ones" digit position. Press [0] to clear the current "ones" digit. The cursor will move back to the "tens" digit position. 3. Enter the keypad's address: Enter the proper "tens" digit of the keypad's address. The cursor will move to the "ones" digit position. Enter the proper "ones" digit of the keypad's address. Note that address "31" sets the keypad to non-addressable mode. 4. Exit address mode: Press [✻] to save the displayed address and exit address mode. VIEWING THE KEYPAD ADDRESS Press and hold down the [1] and [3] keys at the same time for about 3 seconds. The current address is displayed. No key entry is allowed. Press any key to exit or wait 10 seconds to exit viewing mode. FUNCTION KEY LABELS A set of adhesive-backed labels with some typical function symbols (i.e., fire, police, personal emergency, etc.) is provided. These labels can be placed on or next to the keys to identify each key's function for the end user (as determined by the control panel's capability and programming; see the control's instructions). OPERATING THE KEYPAD For operating instructions, see the User Guide for the control panel used with this keypad. SPECIFICATIONS Physical: 5-9/16"H x 6-3/4"W x 1"D Displays: 2 x 16 alpha-numeric supertwist LCD, backlit. Sounder: Speaker. Voltage: 12VDC (power-limited) Current: 150mA in alarm (ARMED LED lit, LCD backlight and sounder on), reduces to 40mA when panel is operating in standby mode (backlight off). NFPA-72 Compliant. REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM. Ê800-03612rŠ 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright 2009 Honeywell International Inc. www.security.honeywell.com 800-03612 1/09 Rev. B WWW.DIYWALWARMWFO.RUDM.ICOYM ALARMFORUM.COM

  • 1
  • 2

SETTING THE KEYPAD ADDRESS
The keypad can either be set for an address of 00-30, or to
the non-addressable mode (31). The keypad's default
address is 31.
To change the keypad's address, do the following:
1. Enter address mode: Power up the keypad.
Within 60
seconds of power-up, press and hold down the [1] and [3]
keys at the same time for 3 seconds.
(If unable to enter
address mode, power up and try again.)
The current keypad address will be displayed, and the
cursor will be under the "tens" digit.
If 10 seconds have
passed with no key entry, the keypad automatically exits
address mode.
You must power down, power up and
start address mode again.
NOTE
: The keypad will not enter address mode if the
panel to which it is connected is in programming mode.
2. Set the current address to "00": Press [0] to clear the
current "tens" digit.
The cursor will move to the "ones"
digit position.
Press [0] to clear the current "ones" digit.
The cursor will move back to the "tens" digit position.
3. Enter the keypad's address: Enter the proper "tens" digit
of the keypad's address.
The cursor will move to the
"ones" digit position.
Enter the proper "ones" digit of the
keypad's address.
Note that address "31" sets the
keypad to non-addressable mode.
4. Exit address mode:
Press [
] to save the displayed address and exit address
mode.
VIEWING THE KEYPAD ADDRESS
Press and hold down the [1] and [3] keys at the same time
for about 3 seconds.
The current address is displayed.
No
key entry is allowed.
Press any key to exit or wait 10
seconds to exit viewing mode.
FUNCTION KEY LABELS
A set of adhesive-backed labels with some typical function
symbols (i.e., fire, police, personal emergency, etc.) is
provided.
These labels can be placed on or next to the keys
to identify each key's function for the end user (as
determined by the control panel's capability and
programming; see the control's instructions).
OPERATING THE KEYPAD
For operating instructions, see the User Guide for the
control panel used with this keypad.
SPECIFICATIONS
Physical:
5-9/16"H x 6-3/4"W x 1"D
Displays:
2 x 16 alpha-numeric supertwist LCD,
backlit.
Sounder:
Speaker.
Voltage:
12VDC (power-limited)
Current:
150mA in alarm (ARMED LED lit, LCD
backlight and sounder on), reduces to 40mA
when panel is operating in standby mode
(backlight off).
NFPA-72
Compliant.
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY
INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM.