LG LMN090HE Service Manual - Page 47

Function of Outdoor Unit - model number

Page 47 highlights

Operation Function of Outdoor Unit Outdoor Unit Two Comp algorithm • Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion. Operating Step • Compressor step varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on. LEV Control • LEV pulse is modulated to keep constant superheat or subcooling. Out door Fan Control • Outdoor fan operates at High or Off to respond to the load condition. R/Valve Control(Heating Model Only) • Convert R/Valve to change cooling to heating, heating to cooling. Defrost Function • After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below 5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min cooing mode. • To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to Oil Return System • In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours. Comp Overload Protection • To protect comp from being overload, protector will turn off the comp. High Pressure Protction • If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A Service Manual 47

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86

Service Manual
47
Operation
Function of Outdoor Unit
Outdoor Unit
Two Comp algorithm
Operating Step
LEV Control
Out door Fan Control
• Compressor step varies considering condition such as room temp,outdoor temp, operating room
number,Temp gap between room temp and set temp and so on.
• LEV pulse is modulated to keep constant superheat or subcooling.
• Outdoor fan operates at High or Off to respond to the load condition.
R/Valve Control(Heating Model Only)
• Convert R/Valve to change cooling to heating, heating to cooling.
Defrost Function
• After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -
5
°
C(23
°
F) and released from deice operation in case outdoor pipe temp is over 12
°
C(53.6
°
F) or 9 min
cooing mode.
• To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to
Oil Return System
• In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.
Comp Overload Protection
• To protect comp from being overload, protector will turn off the comp.
High Pressure Protction
• If cycle pressure is too high(around 36.7 kgf/cm
2
), it will turn off comp A
• Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion.