Tripp Lite 9PX11KPM Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use
Tripp Lite 9PX11KPM Manual
View all Tripp Lite 9PX11KPM manuals
Add to My Manuals
Save this manual to your list of manuals |
Tripp Lite 9PX11KPM manual content summary:
- Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 1
ENGLISH 9PX 8000 9PX 11000 9PX EBM 240V Installation and user manual Copyright © 2013 EATON All rights reserved. Service and support: Call your local service representative 8-11kVA US_EN - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 2
. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 3
present within the system. It should be opened exclusively by qualified service personnel. • The system must be properly grounded. • The battery grounded supply circuit). Product safety • The UPS connection instructions and operation described in the manual must be followed in the indicated order. • - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 4
SAFETY INSTRUCTIONS Special precautions • The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations. • All handling operations will require at least two people (unpacking, lifting, installation in rack system). • Straps are provided only for unpacking manually - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 5
...36 7.5 Replacing the UPS equipped with a HotSwap MBP 38 7.6 Recycling the used equipment 38 8. Troubleshooting 39 8.1 Typical alarms and faults 39 8.2 Silencing the alarm...41 8.3 Service and support...41 9. Specifications 42 9.1 Model specifications...42 10. Glossary 46 Page 5 ENGLISH - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 6
9PX, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products of life EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in charge of - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 7
least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, Modules (EBMs) per UPS. • Firmware that is easily upgradable without a service call. • Remote On/Off control through Remote On/Off (ROO) and Remote - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 8
2. Presentation 2.1 Standard installations Tower installation Power module Battery module W D H Rack installation W Power module Battery module D H Description Weights (lb/kg) 9PX 8000 Power Module 42 / 19 9PX 11000 Power Module 46 / 21 9PX EBM 240V 143 / 65 Dimensions (inch/mm) D xW x H - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 9
ENGLISH 2.2 Rear panels 9PX 8000 (Power Module) 6 743 5 8 12 9PX 11000 (Power Module) 6 7 43 2. Presentation 10 9 1 RS232 communication port 2 USB communication port 3 Dry (relay) contacts communication port 4 Connector for ROO (Remote On/Off) control 5 Connectors for automatic - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 10
terminal blocks 2 Input/Output terminal blocks for connection to the UPS 3 Normal AC source switch 4 Connector for HotSwap MBP detection 5 Manual Bypass switch 6 (3) 30A outlets 7 30A circuit breaker 9PXTFMR5 1 L6-30P input power cable 2 (18) 5-20R 120V outlets 3 20A circuit breaker - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 11
ENGLISH 9PXTFMR11 5 4 7 6 SC240RT 3 2 2. Presentation 3 12 1 Input/Output terminal blocks 2 208V/240V input voltage selection 3 50A output circuit breaker 4 (2) L14-30R 120V/240V outlet 5 30A circuit breaker 6 (8) 5-20R 120V outlets 7 20A circuit breaker 1 Input AC/Output DC - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 12
The UPS is on Battery mode. On Orange On Red The UPS is on Bypass mode. The UPS has an active alarm or fault. See troubleshooting on page 39 for additional information. Page 12 8-11kVA US_EN - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 13
status Efficiency information The following table describes the status information provided by the UPS Note: If other indicator appears, see troubleshooting on page 39 for additional information. Operation status Standby mode Cause The UPS is Off. Description Equipment is not powered until - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 14
usage] Wh since date Transfers the UPS on Bypass mode Starts a manual battery test Clears active fault Returns all settings to original values Clears average first time. UPS fault, Event Log data and settings are in all supported languages. Date/ time Format: [US] [International] [US] LCD - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 15
Enabled] [Disabled] [Disabled] [Enabled] [Enabled] [Disabled] [Every ABM cycle] [20%] [0%] [ABM cycling] [Auto detection] [Auto detection] [Manual EBM set.] Using standard EBM, UPS [Manual battery set.] detects automatically the [No battery] number of EBM connected [Yes] [No] [Yes] If set - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 16
damage: 1. File with the carrier within 15 days of receipt of the equipment; 2. Send a copy of the damage claim within 15 days to your service representative. Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 17
card 5 RS232 communication cable 6 USB communication cable 7 User manual 8 Safety instructions 9 Warranty sheet 10 Software CD-ROM 11 Screwdriver 1 3 Rack kit for 19-inch enclosures 4 EBM Installation manual. 4 1 3 2 Discard the EBM user's guide if you are installing the EBM with a new UPS at - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 18
(s). 4. Check that the battery circuit breaker is switched to the "I" position (On) 3.5 Connecting other accessories If you ordered other UPS accessories, refer to specific user manuals to check the connection to the UPS. Page 18 8-11kVA US_EN - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 19
ENGLISH 3. Installation 3.6 Tower installation If you ordered other UPS accessories, refer to specific user manuals to check the tower installation with the UPS. To install the cabinet: 1. Place the UPS on a flat, stable surface in its final location. 2. Always keep - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 20
If you ordered other UPS accessories, refer to specific user manuals to check the rack installation with the UPS. • Prepare slide the packs out slowly on to a flat and stable surface. Use two hands to support the battery packs. Set them aside for reinstalling after that the EBM is rack mounted. 5. - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 21
ENGLISH • Rack mounting of UPS, EBM, and accessory modules. Follow steps 1 to 4 for module mounting on the rails. 1 1 2 3 3. Installation 3 4 4 The rails and necessary hardware are supplied by EATON. 8-11kVA US_EN Page 21 - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 22
50A D curve - 70A 2 poles circuit breaker L1 N(L2) to UPS Normal AC / Bypass AC source G N(L2) L1 Read the Safety instructions page 3 regarding backfeed protection requirements. 2. Recommended cable cross-sections Terminal position L1 N(L2) Wire function Phase Neutral (Phase) Ground Terminal - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 23
ENGLISH 3. Installation 3.9 Installation depending on the system earthing arrangement (SEA) • UPS with common Normal and Bypass AC inputs Main low voltage switchboard (MLVS) Bypass AC 11 10 8 Normal AC Load Change in SEA between upstream and downstream or galvanic isolation required Main - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 24
3. Installation • UPS with separate Normal and Bypass AC inputs, supplied by separate sources MLVS1 Bypass AC 11 Isolation transformer MLVS2 10 8 Normal AC Load MLVS1 MLVS2 Bypass AC 11 Isolation transformer 10 Normal AC Isolation transformer 8 Load Change in SEA between upstream and - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 25
AC source and Bypass AC source) are open "O" (Off). Always connect the ground wire first If you ordered a HotSwap MBP, refer to the specific user manual to check the terminal blocks connection of the UPS with the MBP. BYPASS AC SOURCE N(L2) t L1 N(L2) t OUTPUT NORMAL AC SOURCE t N(L2) L1 - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 26
AC source and Bypass AC source) are open "O" (Off). Always connect the ground wire first If you ordered a HotSwap MBP, refer to the specific user manual to check the terminal blocks connection of the UPS with the MBP. BYPASS AC SOURCE N(L2) t L1 N(L2) t OUTPUT NORMAL AC SOURCE t N(L2) L1 - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 27
If you ordered a HotSwap MBP, refer to the specific user manual to check the startup sequence of the UPS with the MBP. display for active alarms or notices. Resolve any active alarms before conti- nuing. See "Troubleshooting" on page 39. If the indicator is on, do not proceed until all alarms are - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 28
5. Operation 5.2 Operating modes The Eaton 9PX front panel indicates the UPS status through the UPS indicators, see page 14. Online mode During Online mode, the indicator illuminates solid and the UPS is powered from the utility. The UPS monitors and charges the batteries as needed and provides - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 29
goes below 20%. This threshold can be modified. External battery setting The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in Ah. Deep discharge protection This setting is recommended to avoid damaging the battery. Warranty is void if deep - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 30
5. Operation 5.7 Retrieving the Event log To retrieve the Event log through the display: 1. Press any button to activate the menu options, then select Event log. 2. Scroll through the listed events. 5.8 Retrieving the Fault log To retrieve the Fault log through the display: 1. Press any button to - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 31
ENGLISH 6. Communication 6.1 Communication ports • RS232 or USB communication ports The RS232 and USB communication ports cannot operate simultaneously. 1. Connect the RS232 16 or USB 17 communication cable to 16 the serial or USB port on the computer. 17 2. Connect the other end of the - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 32
6. Communication • Remote On/Off Remote On/Off allows remote action of button to switch On/Off the UPS. Normally open When contact changes from open to closed, the UPS is switched-on (or stays On). When contact changes from closed to open, the UPS is switched-off (or stays Off). On/Off control - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 33
ENGLISH 6. Communication Remote control connection and test 1. Check the UPS is shut down and the electrical supply network disconnected. 2. Remove RPO connector from the UPS by unfitting the screws. 3. Connect a normally closed volt-free contact between the two pins of connector. Contact open: - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 34
the 2 screws. 6.2 Eaton Intelligent Power Software suite Each 9PX UPS ships with Eaton Intelligent Power Software suite. To begin installing, see the instructions accompanying the Software suite CD. Eaton Software suite provides up-to-date graphics of UPS power and system data and power flow. It - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 35
recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use them. Contact your service representative. 7.3 When to replace batteries When the battery replacement screen is displayed, it is recommended to replace the batteries. Contact your - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 36
Wear rubber gloves and boots. • When replacing batteries, replace with the same type and number of batteries or battery packs. Contact your service representative to order new batteries. • Proper disposal of batteries is required. Refer to your local codes for disposal requirements. • Never dispose - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 37
ENGLISH 7. UPS maintenance • Replacing the EBM(s) The EBM is heavy. Lifting the cabinet into a rack requires a minimum of two people. To replace the EBM(s): 1. Unplug the EBM power cable and battery detection cable from the UPS. If additional EBM(s) are installed, unplug the EBM power cable and - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 38
7. UPS maintenance 7.5 Replacing the UPS equipped with a HotSwap MBP The HotSwap MBP allows to service or replace the UPS without interrupting the connected loads. Refer to the specific user manual for more information about HotSwap MBP. To remove the UPS: 1. Press any button to activate the menu - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 39
8. Troubleshooting The Eaton 9PX is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur hours to charge the batteries. If the condition persists, contact your service representative. Equipment is powered but not protected by the UPS. Check - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 40
8. Troubleshooting UPS overtemperature LED is On. 1 beep every 3 seconds. The UPS the UPS is not restricted. Restart the UPS. If the condition continues to persist, contact your service representative. The UPS does not start. The input source is not connected Check the input connections. - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 41
ENGLISH 8. Troubleshooting 8.2 Silencing the alarm Press the ESC (Escape) button on the front overriding the previous alarm silencing. 8.3 Service and support If you have any questions or problems with the UPS, call your Local Distributor or your local service representative and ask for a UPS - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 42
lb / kg) 42 / 19 46 / 21 Weight (lb / kg) 143 / 65 Table 4. Electrical input Nominal frequency Frequency range Bypass voltage range Noise filtering Model 9PX8KPM 9PX11KPM 50/60Hz auto-sensing 50Hz : 40-60Hz before transfer to battery 60Hz : 50-70Hz before transfer to battery -20% / +15% of nominal - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 43
250V are derated at 10000VA 9000W, 220V is derated at 9900W for 11kVA models. Table 7. Electrical output connections Model Output connection 9PX8KPM Hardwired 9PX11KPM Table 8. Environmental and safety EMC certifications EMC (Emissions)* EMC (Immunity) * for output cable < 10m. IEC/EN 62040 - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 44
Battery port EBM battery cable length EBMs 9PXEBM240RT: 240Vdc Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25°C (77°F). Lifetime is reduced above 30 °C. Advanced monitoring for earlier failure detection and warning External three-pole SBS75G - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 45
ENGLISH EATON Customer Care Center Technical Support and Product Services ? Technical questions? If you encounter a problem while following the instructions in this manual, or have questions about the operation, repair, or servicing of your equipment, please visit our web site www. eaton.com for - Tripp Lite 9PX11KPM | Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and Use - Page 46
bypass Rotary switch controlled by the user, used to connect the loads directly to the AC source. Transfer of the load to the manual bypass enables UPS maintenance without interrupting the supply of power to the connected loads. Normal (double conversion) mode The normal UPS operating mode in
ENGLISH
9PX 8000
9PX 11000
9PX EBM 240V
Installation
and user manual
Copyright © 2013
EATON
All rights reserved.
Service and support:
Call your local service representative
8-11kVA US_EN