ENGLISH 6. Communication 6.1 Communication ports • RS232 or USB communication ports The RS232 and USB communication ports cannot operate simultaneously. 1. Connect the RS232 16 or USB 17 communication cable to 16 the serial or USB port on the computer. 17 2. Connect the other end of the communication cable 16 or 17 to the RS232 1 or USB 2 communication port on the UPS. The UPS can now communicate with EATON power management software. • Relay output contacts The UPS incorporates four relay outputs; each information is available with a close or open contact. 54321 98 7 6 n.c. n.o. n.c. n.o. n.o. n.c. n.o. n.c. common Status active information: (if contact between pin and common is closed) • Pin 1: not on Bypass • Pin 2: load not protected • Pin 3: not low battery • Pin 4: not on Battery • Pin 5: user common • Pin 6: on Bypass • Pin 7: low battery • Pin 8: load protected • Pin 9: on Battery • n.o.: contact normally open • n.c.: contact normally closed The relay output contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of 250 Vac/5A. 8-11kVA US_EN Page 31

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 31
8-11kVA US_EN
ENGLISH
6. Communication
6.1
Communication ports
RS232 or USB communication ports
The RS232 and USB communication ports cannot operate simultaneously.
16
17
Relay output contacts
The UPS incorporates four relay outputs; each information is available with a close or open contact.
1
6
7
8
9
n.c.
n.o.
n.c.
common
n.o.
n.o.
n.c.
n.o.
n.c.
2
3
4
5
Status active information: (if contact between pin and common is closed)
Pin 1: not on Bypass
Pin 2: load not protected
Pin 3: not low battery
Pin 4: not on Battery
Pin 5: user common
Pin 6: on Bypass
Pin 7: low battery
Pin 8: load protected
Pin 9: on Battery
n.o.: contact normally open
n.c.: contact normally closed
The relay output contacts must not be connected to any utility connected circuits.
Reinforced insulation to the utility is required. The relay output contacts have a maximum rating
of 250 Vac/5A.
1.
Connect the RS232
16
or USB
17
communication cable to
the serial or USB port on
the computer.
2.
Connect the other end of the
communication cable
16
or
17
to the RS232
1
or USB
2
communication port on
the UPS.
The
UPS
can now communicate
with EATON power management
software.