Whirlpool UXL5430BSS Installation Guide - Page 6

Non-Vented recirculating Installations Through - cfm

Page 6 highlights

Cold weather installations An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break. The break should be as close as possible to where the vent system enters the heated portion of the house. Makeup air Local building codes may require the use of makeup air systems when using ventilation systems with greater than specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your area. Venting Methods This range hood is factory set for venting through the roof or through the wall. The vent system needed for installation is not included. A 6" (15.2 cm) round vent system is recommended. Roof Venting Wall Venting B A A B A. 6" (15.2 cm) vent through the roof B. Roof cap A. 6" (15.2 cm) vent through the wall B. Wall cap Calculate Vent System Length The recommended vent system is 6" (15.2 cm) round vent with a maximum length of 35 ft (10.7 m). For the best performance, use no more than three 90° elbows. To calculate the length of the system, add the equivalent feet (meters) for each of the vent pieces used in the system. Vent Piece 6" (15.2 cm) 45° elbow 2.5 ft (0.8 m) Example vent system - 6" (15.2 cm) 90˚ elbow 6 ft (1.8 m) Wall cap 3 ft (0.93 m) Maximum Length = 35 ft (10.7 m) 1 - 90° elbow 1 - wall cap 9 ft (2.8 m) straight System length = 5 ft (1.5 m) = 0 ft (0 m) = 9 ft (2.8 m) = 14 ft (4.3 m) Non-Vented (recirculating) Installations Through the Soffit/Cabinet If it is not possible to vent cooking fumes and vapors to the outside, the range hood can be used in the non-vented (recirculating) version, using a charcoal filter. Recirculation Kit Part Number W10490330 is available from the dealer or an authorized parts distributor. Through Cabinet Through Soffit A A B G G B C D F D F I E E H A. Ceiling B. Vent cover C. Soffit D. 6" (15.2 cm) vent E. Range hood F. Cabinet G. Wall H. 12" (30.5 cm) min. cabinet height I. 17" (43.2 cm) min. vent cover height NOTE: 12" (30.5 cm) high cabinets without a soffit may allow the 6" vent and vent cover to be seen. 90° elbow 5.0 ft (1.5 m) 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

6
Cold weather installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup air
Local building codes may require the use of makeup air systems
when using ventilation systems with greater than specified CFM
of air movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
This range hood is factory set for venting through the roof or
through the wall.
The vent system needed for installation is not included.
A 6" (15.2 cm) round vent system is recommended.
Calculate Vent System Length
The recommended vent system is 6" (15.2 cm) round vent with a
maximum length of 35 ft (10.7 m). For the best performance, use
no more than three 90° elbows.
To calculate the length of the system, add the equivalent feet
(meters) for each of the vent pieces used in the system.
Example vent system - 6" (15.2 cm)
Non-Vented (recirculating) Installations Through the
Soffit/Cabinet
If it is not possible to vent cooking fumes and vapors to the
outside, the range hood can be used in the non-vented
(recirculating) version, using a charcoal filter. Recirculation Kit
Part Number W10490330 is available from the dealer or an
authorized parts distributor.
NOTE:
12" (30.5 cm) high cabinets without a soffit may allow the
6" vent and vent cover to be seen.
Roof Venting
Wall Venting
A. 6" (15.2 cm) vent through
the roof
B. Roof cap
A. 6" (15.2 cm) vent through
the wall
B. Wall cap
Vent Piece
6" (15.2 cm)
45° elbow
2.5 ft
(0.8 m)
90° elbow
5.0 ft
(1.5 m)
A
B
A
B
Maximum Length
= 35 ft (10.7 m)
1 - 90° elbow
= 5 ft (1.5 m)
1 - wall cap
= 0 ft (0 m)
9 ft (2.8 m) straight
= 9 ft (2.8 m)
System length
= 14 ft (4.3 m)
Through Cabinet
Through Soffit
A. Ceiling
B. Vent cover
C. Soffit
D. 6" (15.2 cm) vent
E. Range hood
F. Cabinet
G. Wall
H. 12" (30.5 cm) min. cabinet
height
I. 17" (43.2 cm) min. vent cover
height
90˚ elbow
3 ft
(0.93 m)
6 ft (1.8 m)
Wall cap
A
A
B
B
C
D
D
E
E
F
F
G
G
I
H